702728
4
Zoom out
Zoom in
Previous page
1/12
Next page
- 4 -
6. ALIGNING AND OPERATING THE UNIT (FIGURE d)
1. Vertical adjustment screw. Clockwise: upwards. Counter-clockwise:
downwards; 2. Horizontal adjustment; 3. View finder.
Supply power to the unit with the cover removed. Set the same beam
channel for both the transmitter and receiver (factory default is channel
1). To align the transmitter lens to the receiver lens, position the
viewfinder between the two lenses and look through it. Line-up the
optics horizontally and vertically until the opposite unit is visible.
Figure e: Fine tuning the alignment.
1. Continue fine tuning the unit until the receiver attenuation LED turns OFF
(figure e: 1. Alarm LED; 2. Attenuation LED; 3. Tester 3-10 VDC;
4. Attenuation sheet).
2. If the unit is used outdoors, place an attenuation sheet over the receiver
optics and continue fine tuning until the receiver LED turns OFF. It is
recommended to use a tester when doing adjustments. Confirm the
beam level by inserting the tester in the monitor jack of the receiver. See
table of figure e for monitor output voltage (1) by recommended beam
level for outdoor (2) and indoor (3) usage. Low readings need to be
readjusted (4).
Note: Table shows voltage under non-attenuation sheet condition.
Testing the unit: Test monthly. Walk in front of the receiver and see if
the walk test LED lights when the beam is blocked. Confirm the relay
function by observing the status light on the control panel.
Maintaining the unit: The units are virtually maintenance free except
for units located in dusty or dirty locations. Clean dirty units with a damp
cloth as necessary.
7. ADJUSTING THE RESPONSE TIME
Figure f: Response time (seconds).
1. Response 0.05 sec: Running at full speed.
2. Response 0.3 sec: Walking quickly.
3. Response 0.7 sec: Walking.
The unit cannot detect objects that move faster than the set response
time. However, increasing the set response time may result in the unit
not detecting people.
8. CHANGING BEAM FREQUENCY
Change the beam frequency to prevent cross talk or bypass of beams.
This can occur with line or 2-stacked protection.
Figure g: Setting the beam channel.
1. Set the transmitter and receiver to the same channel. The units do not
provide protection if set to different channels.
2. See figure g to set the beam channel when installing two or more
units in a line or 2-stacked protection. A: Line protection; B: 2-stacked
protection; C. Line and 2-stacked protection.
Note: When multi-stacked or line protection is used, it is recom-
mended that beam alignment is done with a tester to improve
reliability as well using the beam frequency change-over function.
When multi-stacked protection is used, both upper and lower
sensors should have the same model numbers.
9. EXTERNAL DIMENSIONS (FIGURE h)
1. Knockout; 2. Wire lead.
INSTALLATION I NSTRUCTIONS
1. PRODUCT DESCRIPTION
The PB501/ PB511/ PB521 photoelectric beam sensors have an infrared
transmitter (Tx) and receiver (Rx). They are designed to be AND
gated". An alarm is initiated only when two stacked beams are simulta-
neously interrupted. If one beam is interrupted (eg, by an insect or a
leaf) it does not initiate an alarm. Four beam frequency channels are
available to prevent cross talk when using multiple units.
2. PARTS DESCRIPTION (FIGURE )
The product is shipped with the following items. Please check that they
are all included.
1. Terminals; 2. Beam channel; 3. Lens; 4. View finder; 5. Operation
LED; 6. Horizontal adjustment; 7. Vertical adjustment screw; 8. Cover;
9. Mounting plate; 10. Alarm LED; 11. Attenuation LED; 12. Response
time adjustment; 13. Monitor jack; 14. Tapping screw; 15. Pole-mounting
plate; 16. Pole bracket; 17. Attenuation sheet.
Figure : Dos and Donts on where to install the sensor. No obstruc-
tions (consider seasonal changes). Avoid strong light. Avoid splashing
the unit. Avoid unstable ground.
Figure : Indoor and outdoor protection distances between transmitter
and receiver.
3. GUIDELINES WHEN INSTALLING SENSORS
Avoid overhead wiring.
When installing indoors, use similar procedures as for telephones/
intercoms. Outdoor wiring should be in PVC if used below ground or
use a burial cable. Use conduit for above-ground wiring.
Figure : Recommended installation height.
Figure : Adjust the lens vertically (1) and horizontally (2) so that the
unit can work in all directions. See examples A-C.
Figure : Calculating beam expansion (A). (B= protection distance)
4. WIRING THE SYSTEM
Figure : Terminal configuration.
Figure : Examples of connections.
Figure : Wiring distance (m).
Note 1: The maximum wiring distance when two or more sets are
connected is the value shown divided by the number of sets.
Note 2: The signal line can be wired up to approximately 1000 m
with AWG22 (diameter 0.65 mm) telephone wire.
5. INSTALLING THE SYSTEM
Installing a wall-mounted unit (figure a)
Remove the cover from the unit and detach the mounting plate .
Break the grommet on the mounting plate and pull the wire thorough
(plug the opening between the grommet and the wire with a sealing
material.) Secure the plate with screws. Pull the wire through the
sensor body and attach to the sensor plate.
Once the wiring is completed, adjust the alignment, check the operation
and re-attach the cover. It is not necessary to seal the unit as it is
waterproof.
If surface-wired, break the knockouts on the rear of the unit:
A= wiring from the top; B= wiring from the bottom; C= knockouts. Pull
the wire through as shown and attach it to the mounting plate.
Installing a pole-mounted system (figure b)
Insert two oval countersunk head screws (M4x20) in a pole bracket .
Fix the pole mounting plate to the pole with the bracket. Remove the
cover from the unit and detach the mounting plate. Insert two M4x10
screws in the pole-mounting plate and fix the sensor mounting plate
to them. Continue as explained for wall-mounted units.
Installing a back-to-back pole-mounted system & right-
angle pole mounted system (figure c)
Fix the pole-mounting plate for the first unit. Position the pole bracket of
the second unit underneath the first pole-mounting bracket and fix the
second pole-mounting plate upside down. Continue as explained for
wall-mounted units.
GB
4


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Aritech PB501 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Aritech PB501 in the language / languages: English, French, Swedish as an attachment in your email.

The manual is 0,74 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info