Installation Manual
DESCRIPTION
The AD044 is a universal external interface between
conventional detector devices and the Advisor MASTER
ATS1290 Addressable Devices DGP. It supports up to four
inputs and four supervised outputs.
You can connect four generic detectors with a dual zone
configuration (2-resistor EOL connection, 2 x 47kohm).
The outputs can be used, for example, to enable / disable
the alarm LED on the detector (depending on the detector’s
other functionalities, which can be programmed or activating
devices).
Output supervision is useful for monitoring outputs, such as
fire sounders, etc. (UL requirement).
DEVICE CATEGORY
The AD044 belongs to device category I/O, type 1, and will
be automatically recognised after learning the device into
the ATS1290 DGP.
MOUNTING THE UNIT
1. Pull the wiring through the wire access opening in the
unit base. See Figure n. Exploded view: 1. Lid; 2.
Circuit board; 3. Bracket; 4. Base; 5. Wire access
opening.
CAUTION! You must be free of static
electricity before handling sensor circuit
boards. Touch a grounded, bare metal
surface before touching circuit boards
or wear a grounding strap.
2. Mount the base using the appropriate mounting holes.
3. Mount the metal bracket to the base.
4. Mount the circuit board to the metal bracket.
CONNECTING THE UNIT
Connect the AD044 to the detector and Bus system. See
Figure
q.
1. Connect the wires to the appropriate screw terminals
on the circuit board and tighten the screws. See
Figure
o: 1. Bus In; 2. Bus Out; 3. Monitor*; 4. Inputs;
5. Outputs**, 6. Power supply
*Note 1: An open contact on the AC monitor input
causes an AC fault to be transmitted to the control
panel. An open contact on the battery monitor input
causes a battery fault to be transmitted to the control
panel. When both contacts are closed or hard wired
to close, these inputs will force the AC and battery
monitor to normal state.
**Note 2: Outputs connect the supply voltage (12 or
24 VDC) across the load when ON.
2. Set the address DIP-switches. See Figure
p.
Note 3: Devices are shipped with the DIP switches set
to 255. This is an invalid address. The device will not
communicate with the control panel until a valid
address has been set. Refer to the ATS1290 manual
to determine the correct address setting for each unit.
3. Attach the unit lid to the base. See Figure
n.
4. Test the unit when the Bus system is completely
installed and the control panel is powered.
ADDRESS SETTING, ZONE NUMBERS AND OUTPUT NUMBERS
Set the AD044 to its unique address on the Point ID bus.
For details, see figure p.
The AD044 normally occupies four consecutive addresses,
where the DIP switch represents the main address. Where
output-supervision is used, the AD044 occupies up to eight
consecutive addresses.
THE ATS INPUTS
Input 1 is linked to main address.
Input 2 is linked to main address + 1.
Input 3 is linked to main address + 2.
Input 4 is linked to main address + 3.
THE ATS OUTPUTS
Output 1 is linked to main address.
Output 2 is linked to main address + 1.
Output 3 is linked to main address + 2.
Output 4 is linked to main address + 3.
OUTPUT SUPERVISION
The AD044 can support output supervision on all four
outputs. Supervision of Output 1 is linked to Input 5 and
onwards.
In the default setting, all output are supervised. If an output
(e.g. Output 1) is open, it misses the EOL resistor (47K), the
linked input (input 5) is in Alarm. The relay output will not
follow the linked output of the control panel.
Note 4: The EOL resistor must be available before the
outputs of the AD044 work properly.
The supervision for Outputs 1 to 4 are linked to the
consecutive input addresses:
Supervision Output 1 is linked to Input 5 with main
address+4.
Supervision Output 2 is linked to Input 6 with main
address+5.
Supervision Output 3 is linked to Input 7 with main
address+6.
Supervision Output 4 is linked to Input 8 with main
address+7.
1. It is possible to map another PID device within the
AD044 range. For example, when the AD044 is set
to Address 0 and the AD011 is set to Address 2, the
AD044 occupies Address 0 (I/O 1), 1 (I/O 2) and 3 (I/O
4), and AD011 occupies Address 2. I/O 3 of the AD044
is not available.
2


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Aritech AD044 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Aritech AD044 in the language / languages: English, Dutch, French, Italian as an attachment in your email.

The manual is 0,21 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info