cated with the cylinder. The tundish must also be in a position visible to the occupants, and positioned away from
any electrical devices. The discharge pipe from the tundish should terminate in a safe place where there is no risk to
persons in the vicinity of the discharge and to be of metal.
2) Discharge pipes from the temperature & pressure relief and pressure relief valve may be joined together.
3) The pipe diameter must be at least one pipe size larger than the nominal outlet size of the safety device unless its
total equivalent hydraulic resistance exceeds that of a straight pipe 9 m long.
i.e. Discharge pipes between 9 m and 18 m equivalent resistance length should be at least 2 sizes larger than the
nominal outlet size of the safety device. Between 18 m and 27 m at least 3 times larger, and so on.
Bends must be taken into account in calculating the ow resistance. See g.1 and Table 2.
4) The discharge pipe must have a vertical section of pipe at least 300 mm in length, below the tundish before any
elbows or bends in the pipe work.
5) The discharge pipe must be installed with a continuous fall.
6) The discharge must be visible at both the tundish and the nal point of discharge, but where this is not possible or
practically dicult; there should be clear visibility at one or other of these locations. Examples of acceptance are:
i) Ideally below a xed grating and above the water seal in a trapped gully.
ii) Downward discharges at a low level; i.e. up to 100 mm above external surfaces such as car parks, hard standings,
grassed areas etc. These are acceptable providing that where children may play or otherwise come into contact with
discharges, a wire cage or similar guard is positioned to prevent contact, whilst maintaining visibility.
iii) Discharges at high level; i.e. into a metal hopper and metal down pipe with the end of the discharge pipe clearly vis
-
ible (tundish visible or not). Or onto a roof capable of withstanding high temperature discharges of water 3 m from
any plastic guttering systems that would collect such a discharge (tundish visible).
3) The pipe diameter must be at least one pipe size larger than the nominal outlet size
of the safety device unless it’s total equivalent hydraulic resistance exceeds that of a
straight pipe 9 m long.
i.e. Discharge pipes between 9 m and 18 m equivalent resistance length should be at
least 2 sizes larger than the nominal outlet size of the safety device. Between 18
m and 27 m at least 3 times larger, and so on.
Bends must be taken into account in calculating the flow resistance.
See fi
g..5 and Table 2.
4) The discharge pipe must have a vertical section of pipe at least 300 mm in length,
below the tundish before any elbows or bends in the pipe work.
5) The discharge pipe must be installed with a continuous fall.
6) The discharge must be visible at both the tundish and the final point of discharge,
but where this is not possible or practically difficult; there should be clear visibility at
one or other of these locations. Examples of acceptance are:
i) Ideally belo
w a fixed grating and above the water seal in a trapped gully.
ii) Downward discharges at a low level; i.e. up to 100 mm above external surfaces
such as car parks, hard standings, grassed areas etc. These are acceptable providing
that where children may play or otherwise come into contact with discharges, a wire
cage or similar guard is positioned to prevent contact, whilst maintaining visibility.
iii) Discharges at high level; i.e. into a metal hopper and metal down pipe with
the
end of the discharge pipe clearly visible (tundish visible or not). Or onto a roof capable
15
600 mm Max.
300 mm
Min.
Temperature & pressure
relief valve
Metal discharge pipe (D1) from
temperature & pressure relief valve.
to tundish.
Metal discharge pipe (D2) from tundish
with continuous fall. See Table 2 and worked
example.
Tundish
Fixed grating
Trapped gulley
Discharge below
fixed grating.
(see page 6 for
alternative points
of discharge).
Fig.. 4
Suggest ways of terminating discharge pipes safely
42.0.01.07204.03 pag. 9-20.qxd:42.0.01.07204.01 pag. 9-20 7-10-2016 11:28 Pagina 15
iv) Where a single pipe serves a number of discharges, such as in blocks of ats, the number served should be limited to
no more than 6 systems so that any installation can be traced reasonably easily. The single common discharge pipe
should be at least one pipe size large than the largest individual discharge pipe to be connected. If unvented hot
water storage systems are installed where discharges from safety devices may not be apparent i.e. in dwellings oc
-
cupied by the blind, inrm or disabled people, consideration should be given to the installation of an electronically
9


Need help? Post your question in this forum.

Forumrules
1

Forum

ariston-pro-1-eco

Reset search

  • How to adjust the temp as it keeps returning to full temp Submitted on 13-8-2022 at 11:02

    Reply Report abuse


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Ariston Pro 1 Eco at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Ariston Pro 1 Eco in the language / languages: English as an attachment in your email.

The manual is 1,62 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Ariston Pro 1 Eco

Ariston Pro 1 Eco User Manual - Dutch - 16 pages

Ariston Pro 1 Eco User Manual - French - 24 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info