590225
11
Zoom out
Zoom in
Previous page
1/13
Next page
For proper system operation, each communication cable has to be connected to the corresponding indoor unit, following the
refrigerant tubes. This means that the communication lines Ca, Cb, Cc, and Cd has to be connected to the indoor units A, B,
C, and D respectively.
To serve this purpose the system is designed to have the "Installation Test Mode". When this mode is set, the unit verifies
whether the correct connections were made or not.
Notes:
1. The miswiring check cannot be performed while outdoor temperature is below 5 C. In this situation the display will show
"OAT".
O
2. The miswiring check cannot be performed if some components in the unit are out of operation. In this situation the
display will show the error code "xxx".
3. The indoor units are turned automatically to installation test mode, no need to turn them on.
Please follow all the steps below:
1. Make sure all wiring and piping to indoor units are properly connected.
2. Turn on the power breaker.
3. by scrolling down to installation test (it) press the "Down" button until "it" shows on the display and
then press select for entering installation test mode.
Enter the Test
4. During installation test the system works without the installer interference. It can be observed that the compressor,
outdoor fan and indoor fans are stopped and starts according to preset procedure.
5. The system exits installation test either by continuous press on the escape button for 5 seconds or when the system
finishes installation test by itself after 20 to 40 minutes.
6. After installation test, the system stops for 5 minutes, and then it resumes its normal operation. The judgment code is
shown on the display - either "pass" or "fail".
7. Upon the judgment code, if required, the installer should correct the communication wiring.
INSTALLATION TEST MISWIRING CHECK
6
1. Outdoor Temperature below 5 C
O
2. Unit malfunction (example: code O01)
Display Board
Select
Esc
Up
Down
2. Select
1. Scroll
Down
Entering miswiring check
Display Board Menu list
Outdoor Unit (oxx)
Indoor Unit A (axx)
Indoor Unit B (bxx)
Indoor Unit C (cxx)
Indoor Unit D (dxx)
Technician Test Cool (ttC)
Technician Test Heat (ttH)
First IDU Wins (idu)
IDU A is master (a-p)
IDU B is master (b-p)
IDU C is master (c-p)
IDU D is master (d-p)
'Forced mode' input (Frc)
Technician Test (tt)
Installation Test (it)
Diagnostics (dia)
Set Up (Stp)
Installation test passed with success Installation test fail
11


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Airwell Multisplit YAZE QUATTRO DCI at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Airwell Multisplit YAZE QUATTRO DCI in the language / languages: English as an attachment in your email.

The manual is 0,89 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info