5.2.2. Forced mode operation
If an IDU is defined as a priority unit, the operational mode (Cool/Heat) will be defined according to the priority unit request.
If no unit is selected (as the default value) the first unit turned on determines the unit mode.
Setup the Forced Mode dry contact to
the required mode as per the following:
Open-Cool
Shorted-Heat
Cool open
Heat - shorted
When "Forced Mode" dry contact is shorted, the unit will be forced to heat mode.
5.3.1. Night mode qui t operation (Cool Mode)e
5.3. Features setup with Dry Contacts (Inputs)
The 'Input' Dry contacts are used for controlling.
An external circuitry, which may include a switch or a relay, should be used for closing the internal circuit to indicate that
some change is required.
A solid wires and not stranded one is recommended to be used and up to 0.5 mm .
2
NO external power should be used in this case!
Open-Normal operation
Shorted- Qui t operatione
When "Night" dry contact is shorted, the unit will enter to a special night mode and reduce the compressor and
outdoor fan speeds to allow qui t operation.e
5.3.2. Standby
Open-Normal operation
Shorted Unit in standby
When "Standby" dry contact is shorted, the unit will stopped and stay in standby.
9


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Airwell Multisplit YAZE QUATTRO DCI at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Airwell Multisplit YAZE QUATTRO DCI in the language / languages: English as an attachment in your email.

The manual is 0,89 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info