IMDCFJ. 12.05 6343841_03
Alarms summary table
The units envision two types of malfunction-
ing signals:
• Pre-alarm
• Alarm
The first type is indicated by the flashing
of the red LED on the display, successive
pressing of the bell key allows to display
except for the switch-on of the fixed red
LED. Before rearming the unit, it is recom-
mended to contact the after-sales service.
To rearm the unit, switch it off and back on
again using the stand-by key.
the list of alarms (with index and cause
indicated in the table below). A pre-alarm
remains such for 60 seconds: if after this
time the condition that caused the pre-
alarm has not disappeared, the same
becomes an alarm. The alarms are dis-
played in the same way as the pre-alarms,
ATTENTION:
The pre-alarms can become alarms when:
• A time has passed longer than or equal to 60 seconds, in the pre-alarm condition.
The maximum number of pre-alarms in one hour (five) has been exceeded. In this case, every successive pre-alarm will be dis-
played directly as an alarm, and as such, will stop the machine until the reason for the same is solved.
Code
Alarm
Code
Pre-alarm
Causes Notes
1 101
Compressor magnet circuit breaker
This signal intervenes if the contact relative to the magnet circuit
breaker switch protecting the MTC compressor opens (Table 2,
contact ID1, clamps M7.1 - M7.2, normally closed)
Fan magnet circuit breaker
Pump magnet circuit breaker
2 102 Fan magnet circuit breaker
This signal intervenes if the contact relative to the magnet circuit
breaker switch protecting the MTV fans opens (Table 2, contact
ID6, clamps M7S.3 - M7S.4, normally closed) This code is dis-
played only if the board is used as a board spare part with SW up
to version 3.6.
3 103 High pressure switch
This signal DOES NOT give the state of the high pressure switch
itself but of the compressor switch. The high pressure switch oper-
ates directly on the compressor switches. If the board commands
compressor switch-on and the switch does not become active
after 3 seconds, this signal occurs. This alarm can also be caused
by an operating defect of the return relay from the compressor
switch to the board (indicated as RAP in the wiring diagrams).
This signal occurs if the compressor switch deactivates during
operation. AP (Table 2, contact ID4, clamps M7.7 – M7.8, normally
closed)
4 104
Flow switch
This signal occurs with the opening of the contact relative to the
differential flow switch or pressure switch; this alarm is not relative
for the first 40" from pump start-up. The machine blocks in alarm
mode when the maximum number of flow switch interventions
allowed (expressed by the set_factory parameter (y): default 5)
is exceeded. If the frost protection in standby mode is activated
(and therefore also the pump), the state of the flow switch is also
controlled. FL/PD (Table 2, contact ID2, clamps M7.3 – M7.4, nor-
mally closed)
Water differential pressure switch
5 105 Low pressure switch
This signal intervenes when the contact relative to the low pres-
sure switch opens (compressor intake). BP (Table 2, contact ID5,
clamps M7S.1 – M7S.2)
6 106 No water inlet probe This signal occurs when the water inlet probe is disconnected
7 107 No water outlet probe This signal occurs when the water outlet probe is disconnected
8 108 Water freezing
This signal occurs when the anti-freeze threshold is reached
(set_installer (6) default: 3°C) from the output water temperature.
The pre-alarm state is exited with outlet water temperature tem-
perature exceeding the set_installer (6) + set_factory (J) (default
3+1=4°C).
The anti-freeze alarm is suspended (in heating mode) for a period
of time equal to 3' (set_factory parameter (H)) from compressor
switch on.
9 109 No pressing line probe
This signal occurs when the pressing line gas probe is absent
10 110 High pressing line gas temperature
This signal occurs when the temperature of the pressing line gas
(SGP probe) exceeds the threshold envisioned by the parameter
(set_factory (6), default 135°C). The pre-alarm state is exited with
set_factory (7) temperature (default 135 – 10 = 125 °C)
11 111
Flow pressure transducer
no compressor
This signal occurs when the compressor flow transducer is absent
and the machine is set as heat pump or the presence of the DCP
is set
70


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Aermec MODUCONTROL at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Aermec MODUCONTROL in the language / languages: English, German, French, Italian, Spanish as an attachment in your email.

The manual is 3,21 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info