Protect PV.500 Operating Instructions
58 of 70 80000031354 BAL
X3: When a signal is received, the contact between the two
contact points with the lower numbers is closed (normally open
or "NO").
X4: When a signal is received, the contact between the two
contact points with the lower numbers is opened (normally
closed or "NC").
X5: The control signal is active when the input is bridged
(normally open). The inverter is switched off.
The following default signals are used for remote signalling:
X3.1-2 3 Inverter feed operation (NO)
X3.4-5 6 DC distribution message* (NO)
X3.7-8 9 AC distribution message* (NO)
X3.10-11 12 Incoming mains fault (NO)
X4.1 2-3 Inverter fault* (NC)
X5.1-2 Inverter remote switch-off (NO)
*): Collective signals that contain all messages and faults
Figure 23 shows the normally closed contact in the state that
applies when the signal is not active (normally open) or the voltage
is zero.
The service switch enables maintenance work on the unit to be
signalled to the MultiCom interface using various protocols.
62


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for AEG Protect PV 500 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of AEG Protect PV 500 in the language / languages: English as an attachment in your email.

The manual is 1,99 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of AEG Protect PV 500

AEG Protect PV 500 User Manual - German - 136 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info