Protect PV.500 Operating Instructions
80000031354 BAL 37 of 70
Change of status to single operation:
If capacity utilisation in the inverter which is switched on rises
above a certain value, once a delay has elapsed, the two inverters
are switched to single operation.
First, the inverter which is switched on is switched off. Then, the tie
switch is opened. Once the tie switch is open, both inverters are
switched on.
Change of status to linked operation in the event of a fault:
In the event of a deactivating or self-acknowledging fault in the
inverter which is switched on, the system switches to linked
operation.
The inverter which is switched off is switched on. The faulty
inverter is shut down due to the fault.
5.5.2 Single Operation
Both inverters are switched on and are feeding power into the
mains. The tie switch is open.
This operating mode is active when insolation levels are high.
Figure 11 Single operation in compain operating mode
Change of status to linked operation:
If the capacity utilisation of the two inverters falls below a certain
value, once a delay has elapsed, the system switches to linked
operation.
The MPP tracker is switched off in both inverters and an attempt is
made to regulate the two inverters to the same DC voltage. When
the DC voltages are approximately identical, the tie switch is
closed and one inverter is switched off. If the DC voltages cannot
be regulated to the same value in a certain time, the two MPP
trackers switch back on. Once a delay has elapsed, the MPP
trackers are switched back off again and the next attempt to match
the DC voltage is started.
Change of status to linked operation in the event of a fault:
In the event of a deactivating or self-acknowledging fault in one
inverter, the two inverters are switched to linked operation.
41


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for AEG Protect PV 500 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of AEG Protect PV 500 in the language / languages: English as an attachment in your email.

The manual is 1,99 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of AEG Protect PV 500

AEG Protect PV 500 User Manual - German - 136 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info