61180019L1-5A Issue 1, May 2004 9
Up to 14 dual LIU systems or 28 single LIU systems
may be daisy chained to a single output from the timing
source. This results in a requirement for only one wire
run from the timing source for an installation of up to 14
or 28 Total Access 1500 shelves. Use wire of the same
type as the wire run from the CO clock source to the
Total Access 1500 19-Inch Chassis. The following steps
provide instructions for connecting multiple Total
Access 1500 shelves to a single external timing source.
1. Determine the length of wire required to run from
the first chassis, connector
P14, to the second chas-
sis, connector
P14. Leave approximately 1 to 1-1/2
inches for wire wrapping.
2. Using wire strippers, strip approximately 1 to
1-1/2 inches from both ends of the wire run.
3. Using a wire-wrap tool, wire wrap the “+”, “–” and
drain wires to the “+”, “–” and ground terminal
pins of connector
P14, Clk out Pri, on the top of
the backplane.
4. Run the wire from
P14 on the “source” chassis to
connector
P14, Clk in Pri, on the “receiving”
chassis.
5. Wire wrap the “+”, “–” of the wire run to the “+”,
“–” terminals of
P14 on the “receiving” chassis.
6. Set
SW3 on the “source” chassis to the IN position,
and Set
SW3 on the “receiving” chassis to the OUT
position.
NOTE
In any daisy chain of Total Access 1500
shelves using a single timing source, only the
first chassis in the chain should have switch
SW3 set to IN. All the remaining chassis in the
chain should have SW3 set to OUT.
7. Repeat steps 1 through 6 for each Total Access
1500 shelf that is to be connected to the single CO
timing source.
8. Repeat steps 1 through 7 for secondary clock.
NOTE
If connecting the secondary clock source, set
SW1 to the SW3 settings.
Figure 7 illustrates a daisy-chained composite clock
configuration.
Composite Clock Output
Because some applications may require the Total
Access 1500 System to provide source timing, an
additional connection is provided on
P12 labeled Local
Clk (+, -)
to provide a 64 kHz composite clock output.
This output clock can be used as a timing source for up
to 14 dual LIU systems or 28 single LIU systems.
Mechanized Loop Testing Connections
A four-lead (T, R, I, and drain) common test access bus
is provided for mechanized loop test access to all
customer loops, labeled
P6 on the backplane. Instruc-
tions for connecting the Total Access 1500 19-Inch
Chassis for mechanized loop test access are as follows:
1. After locating the test loops and running them to
the Total Access 1500 19-Inch Chassis, use wire
strippers to strip approximately 1 to 1-1/2 inches
from the test leads.
2. Using the wire-wrap tool, wire wrap the central
office “T” and “R” leads to the Total Access 1500
19-Inch Chassis
R and T pins, respectively, on
terminal
P6.
3. Wire wrap the inhibit wire of the cable to the pin
labeled
I on P6.
4. Wire wrap the drain wire of the cable to the pin
labeled ground on
P6.
5. Neatly tie down the test cable pair.
Alarm Output Connections
Alarm interpretation is dependent on how the Total
Access 1500 System is configured. When the system is
deployed in a single or dual T1 feed, the SCU should be
provisioned for D4 Conventional Alarm Relay
Mapping. The alarm outputs will be designated as
follows:
VIS MAJ (Visual Major)
VIS MIN (Visual Minor)
AUD MAJ (Audible Major)
AUD MIN (Audible Minor)
AUX (Auxiliary)
•PWR
When deployed in a DLC configuration using a quad T1
feed, the SCU can be provisioned for T1 Mapping
which provides the following alarm outputs:
T1A (A Digroup Major)
T1B (B Digroup Major)
T1C (C Digroup Major)
T1D (D Digroup Major)
9


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Adtran total access 1500 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Adtran total access 1500 in the language / languages: English as an attachment in your email.

The manual is 4,25 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info