Appendix II – Notes on Security System
85
Appendix II – Notes on Security System
The TERXON L burglar alarm centre enables you
to configure each of the 8 (max. 264) alarm
zones optimally to suit your operating conditions.
Recommendations:
Distribute the external detectors in as small
groups as possible to the zones (e.g.,
ground-floor detector to zone 1, etc.); activate
detectors singly; if possible, use all zones of
the alarm centre.
The acoustic signal (bell) of the signal
transmitter should be shorter than the visual
signal (strobe). Alarm times must be set
according to local regulations. (E.g., in
Germany, the acoustic alarm must be limited
to 3 minutes.)
The delay time should not be finally set until
a practical test has been conducted.
Choose a random 4-digit or 6-digit
combination for the user and program code.
Only persons of trust should be given the
code.
When operating the alarm centre, enter the
code in such a way that it is concealed from
persons standing nearby.
The cable recommended for connecting the
components (minimum diameter: 0.22
mm2/wire) is normally colour-coded.
The user and program codes must be
different.
For reasons of clear layout, use the following
colour coding:
Red: +12V voltage supply
Black: 0V ground
Yellow: Alarm contact
Green: Alarm contact
Brown: Tamper contact
White: Tamper contact
Use distributors when connecting more than one
detector to an alarm zone. Cable extensions can
be soldered or screwed together. Ensure good
insulation (insulating tape, shrink-on tubing) to
avoid short-circuiting and false alarms.
Proceed as follows:
Read the operating instructions carefully.
Draw up a plan of the object that includes the
installation location of the detectors and the
alarm centre and all cables required.
Lay the cables as required.
Install the detectors and the alarm centre.
Connect the cables to the detectors and the
alarm centre.
Connect the power supply (battery, mains).
Program the device.
As mentioned above, the alarm centre evaluates
the alarm zones via the existing current flow.
Most alarm detectors are normally closed, which
means that the detectors interrupt the alarm zone
in the event of an alarm. The sensors are called
NC (normally closed). Also NO (Normally Open)
contacts can be used with the Terxon L. These
contacts close the circuit if an alarm is triggered.
Sometimes it is necessary to combine several
alarm contacts in a zone. Connect the contacts
serially.
91


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Abus Terxon LX - AZ4200 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Abus Terxon LX - AZ4200 in the language / languages: English as an attachment in your email.

The manual is 1,17 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Abus Terxon LX - AZ4200

Abus Terxon LX - AZ4200 User Manual - English - 16 pages

Abus Terxon LX - AZ4200 Installation Guide - German - 31 pages

Abus Terxon LX - AZ4200 User Manual - German - 16 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info