F
E
D
C
21 53 4
B
A
1 2 3 4 5
76 98
F
E
D
C
678 9
B
A
DRAFT. CHECKED BY
ACCESSORIES
FILE NAME PAGE N.
DIRECTORY DATE
G G
A.FRIZZIERO A.FRIZZIERO
1/4
MASTER
DOMOTICA
blue wire
28/05/2021
NHI MED LOW VAL1 VAL2 L
WALL PAD
LOW
VAL1VAL2
TO SLAVE UNIT
DELAY MED HI N
CONTACT
L
N
PUMP
L
N
FILTER
L
N
HEATER
N
COOLING
L
HEATING
FUSE
LNGND
IN AC230V DC MOTOR
ROOMCOM1STEP1
DIP SWITCH
321
ON
ME
5
4
WATER
N
L
230V-50 Hz
N
L1
PE KEEP ATTENTION TO DON'T
INVERT PHASE AND
NEUTRAL IN BOTH MASTER
AND SLAVE UNITS.
DIP SWITCH :
1 ON
2 ON
3 ON
4 OFF
5 OFF
SW1~3: Motor speed setting
DIP switch description
SW4
OFF
ON
Control setting
Wall Pad
Infrared Handset Remote Control
SW5
OFF
ON
Pipes Setting
2 pipes
4 pipes
Standard setting as indicated above.
Refer to the manual, for different RPM settings.
HI
MED
LOW
VAL1 TO FIRST SLAVE
VAL2
n11
l11
COIL
TEMPERATURE
PROBE (2)
(OPTIONAL)
WINDOW
CONTACT (1)
Ventilconvettore
Fan coil
Gebläsekonvektoren
Ventilconvecteureurs
Ventilconvectores
CTOP2WF
1 2 3 4 5 6 7 8 9
REVERSO + CTOP2WF + V2AM
AC220V-L
AC220V-N
HIGH
MED
OPEN
CLOSE
LOW
OPEN
CLOSE
HEAT VALVE
COOL VALVE
brown wire
grey wire
black wire
to heat pump or
external unit as free
contact (see note "A"
last page
(2) THE PROBE MUST BE POSITIONED, IN PROXIMITY OF
THE INLET, AS INDICATED IN THE INSTRUCTIONS. IT
WILL MEASURE THE WATER TEMPERATURE AND IN
HEATING MODE, THE FAN WILL RUN ONLY IF THE
TEMPERATURE IS OVER THAN THE 35°C (MINIMUM
THERMOSTAT FUNCTION)
(1) IT IS POSSIBLE TO REMOVE THE ELECTRIC BRIDGE BY
FACTORY AND TO USE THE CONTACT AS A
OCCUPANCY SENSOR. IN THIS SENSE, IF THE CONTACT
IS CLOSED, THE UNIT WILL RUN IN ACCORDANCE TO
ITS SETTINGS. INSTEAD IF THE CONTACT IS OPENED,
THE UNIT WILL BE TURNED OFF AFTER 30 SECONDS.
WHEN THE CONTACT IS CLOSED AGAIN, THE UNIT
WILL RUN IN ACCORDANCE TO ITS SETTING.