5-1
IM 1F5B2-01E
5. WIRING
5. WIRING
IMPORTANT
When wiring ULTRA YEWFLO, avoid locating it near such sources of noise as
transformers, motors or electromotive power supplies with large current capacities.
Remove the terminal cover and dust-prevention plug on the wiring port before wiring
ULTRA YEWFLO.
ALWAYS waterproof all threaded parts. (A silicon-resin, non-hardening sealing
material is recommended for the waterproof treatment.)
To protect against noise, do not allow the signal cable and electromotive cables to
run through the same duct.
Explosion-proof models of ULTRA YEWFLO must be wired in compliance with
applicable regulations to ensure explosion-proof performance.
Refer to “Installation and Operating Precautions for Flameproof Instruments” at the
end of this manual to wire ULTRA YEWFLO correctly.
5.1 Selecting the Cable
Observe the following precautions when choosing cables for use with the transmission
loop line.
Use a twisted cable equal to or better than 600V grade polyvinyl chloride insulated
wiring (JIS C3307).
When wiring ULTRA YEWFLO in an area susceptible to noise, use a shielded cable.
If ULTRA YEWFLO will be used in a simultaneous analog-pulse output mode,
separately shielded two-wire cables may become necessary. (See Section 5.5 for
more information.)
When wiring ULTRA YEWFLO in an area where the ambient temperature is
comparatively high or low, use a cable suited for the place of use.
When using ULTRA YEWFLO in an area where a harmful gas, liquid, oil and/or
solvent is present, use a cable resistant to these substances.
Crimp-on terminals (for 4-mm screws) with insulated sleeves are recommended as
the cable-end configuration.
CAUTION
For the remote type, using UYF021 signal cable to connect the converter and remote
type flowmeter.
28


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Yokogawa UYF200 Ultrasonic Vortex Flowmeter at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Yokogawa UYF200 Ultrasonic Vortex Flowmeter in the language / languages: English as an attachment in your email.

The manual is 0,93 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info