<Appendix B. Device Information>
B-9
IM 01C25R51-01E
Step 3 Check the alarm in AR Block
ConrmthatthefollowingalarmsarenotdisplayedinDiagnosticListoftheDeviceStatusscreen.
If any alarm is displayed for AR Block, take the appropriate measure by referring to the table
below.
Table B3.1 Alarm list of AR Block for ow conguration
Alarm No. Alarm Label Counter Measure
AL-85 AR Not Scheduled Make a schedule of AR Block
AL-86 AR Range Conf. Err C
hangethevalueasARRangeHigh(AR.RANGE_HI)islarger
thanARRangeLow(AR.RANGE_LO)
AL-87 AR Temp. IN Over Range T
hiscaseisoutofspecication.RefertoIM01F06F00-01Eor
Check the engineering setting or AR Temperature Unit
(AR.AR_TEMPERATURE_UNIT)
AL-88 AR Press IN Over Range T
hiscaseisoutofspecication.RefertoIM01F06F00-01Eor
ChecktheengineeringsettingorARPressureUnit(AR.AR_
PRESSURE_UNIT)andARBiasInput2(AR.BIAS_IN_2)
AL-89 AR Flow IN NotConnected C
onnectthevolumetricowdataintoARInput(AR.IN)
AL-90 AR Temp. IN NotConnected C
onnectthetemperaturedataintoARInput1(AR.IN_1)
AL-91 AR Press IN NotConnected C
onnectthepressuredataintoARInput2(AR.IN_2)
AL-92 AR Comp. Coef. Conf. Err E
xecuteFlowCongurationWizard”againanddownloadtothe
device.
AL-93 AR Output Unit Conf. Err Refer to IM 01F06F00-01E or Check the AR Output Range.Units
I
ndex(AR.OUT_RANGE.UnitIndex)andARArithmeticType
(AR.ARITH_TYPE)
NOTE
AsfordevicealarmsotherthanARBlock,refertoInstructionManual"ModelDYVortex
Flowmeter,ModelDYAVortexFlowConverter,andFieldbusCommunicationType"(IM
01F06F00-01E).
156


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Yokogawa FSA120 Flow Configuration Software at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Yokogawa FSA120 Flow Configuration Software in the language / languages: English as an attachment in your email.

The manual is 12,52 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Yokogawa FSA120 Flow Configuration Software

Yokogawa FSA120 Flow Configuration Software Quick start guide - English - 16 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info