<7. Operation of EJXMVTool>
7-19
IM 01C25R51-01E
7.2.2 Basic Mode Setup
SelectaFluidTypefrom“Gas”orLiquid”.
(1) Gas (Default)
Figure 7.19 Basic Mode Setup Screen
Input Reference Temperature (Tb), Reference Static Pressure (SPb), and Kfactor.
NOTE
The static pressure value is according to the transmitter’s abs and gauge selection (A/G select).
But same unit character is used for both absolute and gauge.
The procedure for setting the BASIC Mode is as follows. For details on how to calculate the
Kfactor, refer to the EJX910A and EJX930A Multivariable Transmitters User’s Manual (IM
01C25R01-01E).
Table 7.11 Flow Operational Expression
T0701E.ai
*1: mark indicate User Input
*2: Kfactor must be calculated according to the Flow unit category
*3: Reter to table 7.5, 7.6, 7.7
× ∆P × T/Tb × SPb/SP
Fluid
type
Flow unit
Category
*3
Kfactor
*2
Flow Equation
Mass Flow
Mass Flow
Volume Flow
Volume Flow
Gas
Liquid
Normal·Standard
Volume Flow
Normal·Standard
Volume Flow
Kfactor = /4 × Nc × C/ 1−β
4
× ε × d
2
× 2 × ρb
× 2 × ρb / ρ norm
× 2 / ρb
× 2 × ρb × 1/K
× 2 × ρb × 1/K / ρ norm
× 2/(ρb × 1/K)
Qm or Qv or Qv_norm
= Kfactor
Qm or Qv_norm
= Kfactor
× ∆P × Tb/T × SP/SPb
Qv= Kfactor
Kfactor = /4 × Nc × C/ 1−β
4
× ε × d
2
Kfactor = /4 × Nc × C/ 1−β
4
× ε × d
2
Kfactor = /4 × Nc × C/ 1−β
4
× ε × d
2
Kfactor = /4 × Nc × C/ 1−β
4
× ε × d
2
Kfactor = /4 × Nc × C/ 1−β
4
× ε × d
2
× ∆P × (1+Temp K1 × (T–Tb))
*1
*1
*1
112


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Yokogawa FSA120 Flow Configuration Software at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Yokogawa FSA120 Flow Configuration Software in the language / languages: English as an attachment in your email.

The manual is 12,52 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Yokogawa FSA120 Flow Configuration Software

Yokogawa FSA120 Flow Configuration Software Quick start guide - English - 16 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info