VARINO GRANDE 350 - 600
We reserve the right to make changes to dimensions and construction 18 Edition 10.07.2015
© Copyright YGNIS AG CH-Ruswil
6.9.3. Sensor assembly
Junction boxes or sockets are to be avoided. Sensor and extra-low-voltage cables must be laid separately from
mains lines. Use own sensor cable with max. 100 m length, cable 2 x 1 mm
2
not screened
Cable length: up to 25 m cable cross section: 0.25 mm
2
Cable length: up to 50 m cable cross section: 0.5 mm
2
Cable length: up to 100 m cable cross section: 1.0 mm
2
External sensor: In 2/3 facade height or on 1
st
floor not above windows or below roof preferably
installed on the north or north west side. Avoid direct sunlight. Position to be
arranged with heating planner.
Forward flow sensor: Supply flow clip-on sensor
assemble directly behind the pump (approx. 0.5 m) in the supply flow of the heating
or, if the pump is assembled in the return flow, approx. 1.5 m after the mixer position.
Assembly: assemble on the bare pipe with supplied clamp band, without conductive
paste
Supply flow immersion sensor
assemble directly behind the pump (approx. 0.5 m) in the supply flow of the heating
or, if the pump is assembled in the return flow, approx. 1.5 m after the mixer position.
Assembly: assemble in the pipe bend against the flow direction of the heat transfer
medium
Room remote controls Assemble in the main living quarters on the interior wall. Do not subject to the
influence of sun or external heat (chimney wall, radiator proximity, drafts, televisions,
lighting fixtures). Do not cover with furniture or curtains, mount approx. 1.2 1.5 m
over the floor. Seal installation pipe against drafts. All room sensors and room
remote controls are "active" and therefore directly connected to the device bus. The
cable lengths of all lines on the device bus must not exceed the maximum length of
200 m! Cables 2x1 mm
2
, wires not screened, lay separately from power lines,
junction boxes and sockets are to be avoided.
Return flow sensor, boiler sensor, safety temperature limit devices and temperature monitor are positioned by
works and supplied as-wired.
The O2-sensor is delivered separately and is mounted at commissioning in order to prevent eventual damage to
the sensor during the construction period.
The electrical cables and lines must be laid and secured as shown in the illustration. For strain relief, the cables
should be fastened with cable binders to the threaded rod of the boiler nose peace. Mains and extra-low-voltage
cables (sensor lines, bus lines etc.) are to be routed separately. Unnecessarily long cable loops must not be
rolled up inside of the boiler casing.
20


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Ygnis VARINO GRANDE at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Ygnis VARINO GRANDE in the language / languages: English as an attachment in your email.

The manual is 1,43 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Ygnis VARINO GRANDE

Ygnis VARINO GRANDE Installation Guide - English, German, Dutch - 48 pages

Ygnis VARINO GRANDE Usermanual and installation guide - Dutch - 34 pages

Ygnis VARINO GRANDE Installation Guide - French, Italian, Spanish - 48 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info