LRP NT Plus 1 - 14
4.5. Technische specificaties
4.5.1. Pyronox LRP NT Plus
Technische gegevens LRP NT plus (huisbrandolie)
LRP NT plus 1234567891011121314
Vermogens
Nuttig vermogen qN (80/60°C)
max. 70 90 120 145 165 190 225 260 300 335 370 440 510 580
min.
2
39 43 59 65 69 76 93 100 115 135 154 190 216 259
min.
3
28 31 42 46 49 53 62 60 67 80 89 103 117 158
Warmtebelasting qF
max. 76 98 130 158 179 207 245 284 329 366 405 478 556 634
min.
2
41 46 62 69 73 80 98 105 122 143 162 201 228 273
min.
3
29 32 44 48 51 56 65 62 71 84 93 108 122 165
Modulatie 60 / 80 °C
2
54% 47% 48% 44% 41% 39% 40% 37% 37% 39% 40% 42% 41% 43%
3
38% 33% 34% 30% 28% 27% 27% 22% 22% 23% 23% 23% 22% 26%
Modulatie @ tm = 40 °C
2
75% 64% 67% 63% 65% 61% 64% 61% 57% 61% 60% 67% 62% 62%
3
60% 51% 53% 47% 45% 45% 47% 44% 42% 45% 45% 49% 47% 48%
Rendementen
Thermisch rendement 60 / 80 °C
100%
%
92.0 91.6 92.2 91.7 92.0 91.5 91.7 91.7 91.2 91.6 91.4 92.1 91.7 91.4
Thermisch rendement
@
tm=40 °
C
30%
2
%
94.6 94.7 94.8 94.8 94.9 95.0 94.9 95.0 95.0 95.0 95.0 95.0 95.1 95.1
Thermisch rendement @ tm = 40
°
30%
3
%
95.6 95.7 95.7 95.8 95.8 95.9 95.9 95.9 96.0 96.0 96.0 96.0 96.0 96.0
Rendement DIN4702-8, 60 / 75 °
C
η
N
2
%
93.7 93.9 94.0 94.1 94.2 94.3 94.3 94.3 94.3 94.4 94.4 94.5 94.6 94.6
Debieten
debiet huisbrandolie
max.
1
6.4 8.3 10.9 13.3 15.1 17.5 20.7 24.0 27.8 30.9 34.2 40.3 46.9 53.5
min.
1,2
3.5 3.9 5.3 5.8 6.1 6.8 8.3 8.9 10.3 12.0 13.7 16.9 19.2 23.0
Rookgasdebiet
max. nat 0.03 0.04 0.06 0.07 0.08 0.09 0.11 0.12 0.14 0.16 0.17 0.21 0.24 0.27
min. nat
2
0.02 0.02 0.03 0.03 0.03 0.03 0.04 0.05 0.05 0.06 0.07 0.09 0.10 0.12
Rookgasgegevens, verliezen
Druk verbrandingskamer
max.
mbar
0.44 0.86 0.98 1.61 1.77 2.64 1.97 2.27 3.43 2.83 3.80 2.48 3.75 5.74
Rookgastemperatuur bij 80/60 °C
max. 176 187 175 187 183 192 189 191 201 192 197 181 191 196
min.
2
min.
3
Rookgasverliezen bij 80/60 °C
max.
%
7.3 7.9 7.3 7.9 7.7 8.1 8.0 8.1 8.6 8.1 8.4 7.6 8.1 8.4
Stilstandverliezen qB
70 °C
W
343 343 442 442 451 451 539 552 552 659 659 779 779 779
Hydraulische gegevens
Waterweerstand
t=10K
43 71 40 58 76 100 48 66 87 108 132 81 108 140
t=20K
11 18 10 15 19 25 12 17 22 27 33 20 27 35
Waterdebiet
max. 6.0 7.7 10.3 12.5 14.2 16.3 19.3 22.3 25.8 28.8 31.8 37.8 43.8 49.8
Bedrijfstemperaturen
max.
TVB
Gegevens volgens EN304 bij:
3zugskessel, V-07/06
- lamda=1.2, CO2=12.7%
OG
- T-Lucht=20°C, rel. hum.=60%, p-baro=100kPa
1: Hi = 11.85 kWh/kg
2: S-gehalte in olie tot 0.2%
3: S-gehalte in olie maximaal 0.005% (50 ppm)
m3/h
°C
110
90
kg/h
°C
100
kW
kW
mbar
kg/s
120
90
100
110
120
130
140
150
160
170
180
190
200
0 50 100 150 200 250 300 350 400 450 500 550 600
QN [kW]
[°C]
65
75
85
95
105
115
125
135
145
155
165
175
[°C]
OG
1
2
3
4
5
678
9
10
14
11
12
13
Smax = 0.2%
Smax = 0.05% (500 ppm)
Smax = 50 ppm
tm = 70°C tm = 40°C
Temperaturen rookgassen LRP NT Plus, olie bij schone ketel
tm = gemiddelde keteltemperatuur (zie ook par. 4.6.1)
Maat- en constructiewijzigingen voorbehouden! 7 editie 16.7.2007
© Copyright YGNIS AG CH-Ruswil
9


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Ygnis Pyronox LRP NT Plus at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Ygnis Pyronox LRP NT Plus in the language / languages: Dutch as an attachment in your email.

The manual is 1,18 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Ygnis Pyronox LRP NT Plus

Ygnis Pyronox LRP NT Plus Installation Guide - English - 20 pages

Ygnis Pyronox LRP NT Plus Installation Guide - German - 32 pages

Ygnis Pyronox LRP NT Plus Installation Guide - German, Dutch, French, Italian, Spanish - 20 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info