LR, LRK, LR-NT, LRK-NT 21 - 32
We reserve the right to make changes to dimensions and construction 28 edition 30.10.2007
4.8. Correction values for different operating conditions
4.8.1. Flue gas temperature correction values LR, LR-NT
Average boiler water temperature tm °C 50 60 70 80 90 100
Flue gas temperature difference t K - 16 - 8 ± 0 + 8 + 16 + 24
Excess air λ 1.10 1.15 1.20 1.25 1.30 1.35
Flue gas temperature difference t K -6 -3 ± 0 +3 +6 +8
4.8.2. Modulation range
In chapter 4.5 modulation ranges are indicated for an average boiler water temperature of tm = 70°C.
Since the minimum power of the boiler is limited by the minimum allowable flue gas temperature, the modulation
range increases when the average boiler temperature increases. This is exemplary illustrated in the figure below
(example for oil operation with a minimum flue temperature of 120°C).
100
120
140
160
180
200
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
QN [%]
[°C]
tm = 80 °C
tm = 70 °C
(60 / 80 °C)
Δ
t = +8 °C
Mod 70°
Mod 80°
Flue gas temperature – Boiler power diagram, example for two average boiler water temperatures
4.8.3. Stand-by loss correction values
Average temperature difference *
Δtm
°C 30 40 50 60 70
Stand-by loss correction
ΔqB
% -40 -20 ± 0 20 40
* Average temperature difference = Average boiler water temperature minus ambient air temperature
Average boiler water temperature = Average of supply and return temperature
© Copyright YGNIS AG CH-Ruswil
30


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Ygnis Pyronox LRK-NT at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Ygnis Pyronox LRK-NT in the language / languages: English as an attachment in your email.

The manual is 1,29 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Ygnis Pyronox LRK-NT

Ygnis Pyronox LRK-NT Usermanual and installation guide - Dutch - 46 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info