Fault Finding
Greenstar Highflow CDi ErP– 6 720 818 076 (2015/12)
7.1 Error codes 7.2 Extreme cold weather
In some instances where the condensate pipe work is run
externally or in an unheated area, such as a garage, the
condensate pipe work can be at risk of freezing, even if well
insulated.
A frozen/blocked condensate pipe will cause the boiler to shut
down.
If the condensate pipe has frozen:
Locate the blockage.
It is likely that the pipe is frozen at the most exposed point
outside the building or where there is an obstruction to
flow.
This could be the open end of the pipe, at a bend or elbow,
or where there is a sag in the pipe in which condensate can
collect.
The location of the blockage should be identified as closely
as possible before taking further action.
Thaw the frozen pipe.
The pipe can be thawed by applying a hot water bottle, a
microwaveable heating pack (the sort used for muscular
aches and pains) or a cloth soaked in hot water to the
exterior of the pipe, close to the point of blockage.
Hot water, but not boiling, can also be poured onto the pipe
from a watering can or similar container.
Once the pipe has been thawed the boiler must be reset,
press the reset button for five seconds and wait two to
three minutes for the boiler to restart.
If the boiler does not restart, contact Worcester, Bosch
Group Appointments Team (see back cover for details).
Contact your installer in order to find a permanent solution
to the problem.
When calling Worcester, Bosch Group, you
may be asked for the error code. This table is
for you to help identify the possible cause of
the fault.
Do not try to rectify any of the faults listed
below by yourself.
Contact a Worcester, Bosch Group service
engineer, or other Gas Safe registered
engineer.
Error code Description
A7 Hot water NTC sensor defective.
A8 Break in communication to weather
compensating clip-in control or Greenstar
Comfort II RF
b1 Code plug not detected.
C6 Fan speed too low.
d5 Condensate pump fault
E2 CH flow NTC sensor defective.
E9 Safety temp. limiter in CH flow has tripped.
EA Flame not detected.
Check, if it is safe to do so:
if gas is on in the house
for frozen condensate pipe
for blocked flue outlet
F0 Internal error.
F7 Flame detected even though boiler switched
off.
FA Flame detected after gas shut off.
Fd Reset button pressed by mistake.
SE Service required
U1 Boiler flow temperature is too high,
the boiler will shut down until it has cooled
down
U2
U3
WARNING: Falling hazard!
Failure to follow this guidance may result in
personal injury.
Only attempt to thaw a condense pipe that
is at ground level, and that is easily
accessible.
Never attempt to thaw a condense pipe
that is at height.
CAUTION: Pipe damage
DO NOT use boiling water to thaw the
condensate pipe!
CAUTION: Slip hazard
Ensure that the subsequent freezing of any
water does not result in a slip hazard
14


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Worcester-Bosch Greenstar Highflow CDi 2016-2023 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Worcester-Bosch Greenstar Highflow CDi 2016-2023 in the language / languages: English as an attachment in your email.

The manual is 1.92 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info