Pre-Installation
Greenstar Danesmoor Utility 2022+ and Utility System 2022+ - 6 721 846 263 (2022/01) 15
4.5 Condensate discharge
For correct installation and trouble free operation of the appliance the
following advice should be followed:
1. All condensate pipework must ‘fall’ from the appliance by a minimum
of 3 degrees (52mm per metre) to ensure adequate condensate
flow.
2. The pipework route must allow air to be supplied back to the
appliance for correct operation of the condensate trap.
3. Connection to a rainwater down pipe must include an air break.
Also:
Keep external pipework as short as possible and not exceed 3 metres
length.
External pipework should be increased to a minimum diameter of
32mm and ideally be insulated.
Minimise the number of bends and connectors.
Remove burrs after cutting pipe.
Remove surplus solvent from the interior of the pipe.
4.5.1 Condensate pipe work
4.5.2 Internal connections
In order to minimise risk of freezing during prolonged cold spells, the
following methods of installing condensate drainage pipe should be
adopted, in order of priority.
Wherever possible, the condensate drainage pipe should be routed and
terminated so that the condensate drains away from the boiler under
gravity to a suitable internal foul water discharge point such as an
internal soil and vent stack. A suitable permanent connection to the foul
waste pipe should be used.
Fig. 13 Disposal to soil vent stack
Alternatively if the first option is not possible an internal kitchen,
bathroom or washing machine waste pipe etc. can be used.
Ensure that the condensate drain pipe is connected “down stream” of
the waste trap.
Fig. 14 Disposal to a waste pipe
CONDENSATE PUMP
Where “gravity discharge” to an internal termination is not physically
possible, or where very long internal runs would be required to reach a
suitable discharge point, condensate should be removed using a
proprietary condensate pump, of a specification recommended by the
boiler or condensate pump manufacturer.
The pump outlet pipe should discharge to a suitable internal foul water
discharge point such as an internal soil and vent stack or if not possible
to internal kitchen, bathroom or washing machine waste pipe etc. A
suitable permanent connection to the foul waste pipe should be used.
Fig. 15 Condensate pump disposal
Follow HHIC guidance and recommendations for
condensate disposal
NOTICE:
Where a new or replacement boiler is being installed,
access to an internal “gravity discharge” point should
be one of the factors considered in determining
boiler location.
The condensate pipe must be nominally
21.5mm Ø polypropylene pipe.
The condensate pipe work must fall at least 52mm
per metre towards the outlet and should take the
shortest practicable route.
Ensure there are no blockages in the pipe run.
NOTICE: Unheated internal areas.
The condensate discharge may freeze in areas during
prolonged cold temperatures.
Internal pipe runs in unheated areas such as lofts,
basements and garages should be treated as external
runs.
Key to condensate illustrations, figures 12, 13, 14 & 15
1 Condensate discharge from boiler
2 Soil and vent stack
3 Minimum 450mm and up to three storeys
4 Visible air break at plug hole
5 Sink or basin with integrated overflow
6 75mm sink waste trap
7Condensate pump
Table 5 Key to Internal condensate disposal methods
6720644744-06.4Wo
21.5mm Ø
1
3
2
6720819188-03.3Wo
21.5mm Ø
75mm
min.
1
1
75mm
min.
21.5mm Ø
5
6
6
5
6720819188-12.2Wo
21.5mm Ø
2
1
73
15


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Worcester-Bosch Greenstar Danesmoor Utility Regular - Utility System at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Worcester-Bosch Greenstar Danesmoor Utility Regular - Utility System in the language / languages: English as an attachment in your email.

The manual is 14.85 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info