Malfunction or failure
17
Greenstar 2000 – 6 721 839 343 (2023/04)
System gassing
WARNING
If you suspect the heating system is gassing, you must exercise
caution when carrying out testing or remedial work as the gasses
produced can be flammable.
Do not vent air from radiators whilst the central heating is switched
on. Allow 30mins after venting the radiators before using the
central heating or hot water.
Whilst venting radiators, do not allow the pressure on the boiler to
drop below the point at which it is normally set.
If the system is to be drained, the boiler must be electrically isolated.
CAUTION
If system pressure is repeatedly increasing, even when the
appliance is not operating, you should first check that the filling link
is fully closed and confirm that it is not passing. If radiators are also
not heating to the top of the panels and repeatedly need venting, the
heating system may be suffering from gassing. This is an indication
that corrosion is taking place and requires the system being cleaned
and treated to BS7593.
This should be confirmed by taking water samples to check pH levels
and turbidity.
Failure to properly maintain the heating system may result in damage
to the system and appliance, and may affect the boiler warranty.
Table 8 System gassing flow chart
Is your system pressure constantly increasing even when the boiler is off for extended
periods of time?
NO YES
Does system pressure increase
when the boiler is on?
Have you confirmed that the filling link is not
stuck open/passing water in any way?
YES YES
NO NO Does the problem
persist?
Is your system pressure regularly
dropping (i.e. you constantly have to
top up your boilers pressure)
Does system pressure increase above
2.5bar or enter the high pressure red
zone (Max operating pressure) on the
pressure gauge/display?
Confirm the filling link is closed
and check that the Plate Heat
Exchanger is not cross leaking
YES NO
The boiler
is fine
Plate heat exchanger leaking?NO YES NO YES
The boiler
is fine
Does your Pressure
Relief Valve
regularly drip?
The boiler
is fine
Is the Expansion Vessel
pre-charged higher than
expected?
Replace Plate Heat
Exchanger
NO YES
Do the radiators have to be
regularly vented?
NO YES NO YES
Most likely a cross-leaking
component in the boiler.
Further investigation
required
Check the CH
system for leaks
Check/replace
Pressure Relief
Valve
Is the Expansion Vessel
pre-charge too low?
YES NO
NO YES
Corrosion is probably occurring within the heating
system which is causing system gassing.
The system should be cleaned and treated to comply with
BS 7593
Check Expansion Vessel is
sized correctly for the
system
Repressurise the
Expansion Vessel
17


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Worcester-Bosch Greenstar 2000 - GR2301iW at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Worcester-Bosch Greenstar 2000 - GR2301iW in the language / languages: English as an attachment in your email.

The manual is 3.86 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info