813057
54
Zoom out
Zoom in
Previous page
1/68
Next page
Manual_S5_Airplus_2015_04_20 Page 54 / 68
© Wodtke GmbH - Tübingen. All Rights and Changes Reserved.Printed 04/2015 Part No. 950 976
Fault code
Class 1
Cause of fault
Target values
Resolution of fault
TR =
Flue gas temperature
too low. Measurement point:
Combustion chamber.
Sensor NiCrNi
Image / case 1
Do not ignite! Empty pot
first. See to the right
Flue gas fan temperature TR
too low. There are often also unburned
pellets in the burner pot.
Case 1: False start; burner pot filled
with pellets, no flame. TR temperature
not reached:
Burner pot / unit not cleaned
false start
Negative pressure in installa-
tion room (resulting in flow re-
versal in the ignition) false
start (often associated with flue
gas escaping from the unit)
Ignition cartridge defective
false start
TR ≥ 150 °C
Query occurs 18
minutes after the
start signal for
the furnace for
the first time, and
is then monitored
continually.
Upon restart, the
query waits 18
minutes again.
Always clean / empty burner
pot before restarting. Atten-
tion: Never empty content of
burner pot into the storage
container risk of fire from
embers!
Troubleshooting: Inspect,
verify combustion air supply.
Negative pressure in the in-
stallation room of the furnace
due to exhaust hood, residen-
tial ventilation or pneumatic
conveyance systems is not
permitted and dangerous.
Also see country-specific reg-
ulations and separate tech-
nical information. Inspect igni-
tion cartridge. Only after-
wards, perform manual reset
via I/O button
Image / case 2
Do not ignite! Empty pot
first. See to the right
Case 2 cause: Shut-down in opera-
tion, because there aren't enough pel-
lets in the storage container or container
has run empty (there are only a few pel-
lets in the burner pot)
Remedy for case 2: refill pel-
lets, empty / clean burner pot.
Reset and restart.
TP =
Pellet chute temperature too
high
Measurement point: Pellet
chute
Measurement sensor: TP 1000
External error!
Caused for example by negative pres-
sure due to ventilation system or extrac-
tion hood. Or chimney draught much too
low with voltage failure (fan). Or pellets
with through-put/heating value that is
much too high.
TP < 200 °C
There is not a unit defect!
Allow unit to cool until TP is
below threshold.
Find and resolve exter-
nal cause. Only afterwards,
manual reset via I/O button
See above regarding nega-
tive pressure
ST =
safety temperature limiter STB
has triggered!
Measurement point of air units:
capillary sensor on storage
container radiation plate
STB measurement sensor ac-
cording to DIN 3440. Notice,
the STB is a mandatory, au-
tonomous safety component
with its own switch housing
and operates decoupled
from the control.
External error!
Unit temperature is too high. STB trig-
gered because temperature is too high
(safety function). Normally an external
cause, not a unit fault, because STB is
only triggered if the heat generated by
the unit is not withdrawn.
Causes: Overheating
T STB ≤ 95 °C
no query possi-
ble.
There is not a unit defect.
Find and resolve external
cause. Inspect convection
air inlets and outlets. Re-
duce heating output if the
room temperature is too
high.
Allow unit to cool until STB
is below threshold. Only af-
terwards, unlock the STB+
manual reset via I/O button
54


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Wodtke Family.nrg at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Wodtke Family.nrg in the language / languages: English as an attachment in your email.

The manual is 6.01 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Wodtke Family.nrg

Wodtke Family.nrg Usermanual and installation guide - German - 72 pages

Wodtke Family.nrg User Manual - French - 72 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info