7.4 Dichtheid van het rookgassysteem controleren
Bij ruimteluchtonafhankelijke werking moet het rookgassysteem via een O2-meting op
dichtheid gecontroleerd worden.
Slang 2 via het meetpunt in de ringvormige luchttoevoeropening 1 in het toestel
leiden.
Meetpunt in ringvormige luchttoevoeropening afdichten.
Meetsonde 3 aan de slang aansluiten.
Frontbekleding monteren.
Vermogen manueel verhogen tot maximum (zie hfst. 6.4).
O2-meting bij maximaal vermogen doorvoeren.
Meting uitvoeren gedurende minstens 5 minuten.
Het O2-gehalte mag de gemeten waarde van de omgevingslucht met maximum
0,2 % onderschrijden.
Montage- en bedieningsrichtlijnen
Condenserende gasketel WTC 45-A en WTC 60-A
7 Inbedrijfstelling
83240707 • 1/2013-07 • La
68-111
68


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Weishaupt WTC 45-A Thermo Condens at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Weishaupt WTC 45-A Thermo Condens in the language / languages: Dutch as an attachment in your email.

The manual is 4,49 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Weishaupt WTC 45-A Thermo Condens

Weishaupt WTC 45-A Thermo Condens User Manual - Dutch - 8 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info