Installation and operating instruction
Oil burner WL20/1-C Z
7 Commissioning
83307602 1/2019-04 La 39-84
7.4 Check combustion
Determine excess air
Slowly close air damper(s) in the relevant stage until the combustion limit is
reached (smoke number approx.1).
Measure and document O2 content.
Read air number (λ).
Increase air number to ensure sufficient excess air:
by 0.15 … 0.2 (equates to 15 … 20 % excess air),
by more than 0.2 for more difficult conditions, such as:
dirty combustion air,
fluctuating intake temperature,
fluctuating chimney draught.
Example
λ + 0.15 = λ*
Set air number (λ*), do not exceed CO content of 50 ppm.
Measure and document O2 content.
Check flue gas temperature
Check flue gas temperature.
Ensure that the flue gas temperature complies with the data provided by the
boiler manufacturer.
If necessary adjust flue gas temperature, e g.:
Increase burner capacity in partial load to avoid condensation in the flue gas
ducts, except on condensing units.
Reduce burner capacity in full load to improve efficiency.
Adjust heat exchanger to the data provided by the manufacturer.
Determine flue gas losses
Drive to full load.
Measure combustion air temperature (tL) near the air damper(s).
Measure oxygen content (O2) and flue gas temperature (tA) at the same time at
one point.
Determine flue gas losses using the following formula:
qA= (tA- tL) ( A2
21- O2
) + B
qAFlue gas losses [%]
tAFlue gas temperature [°C]
tLCombustion air temperature [°C]
O2Volumetric content of oxygen in dry flue gas [%]
Fuel factors Fuel oil
A2 0.68
B 0.007
39


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Weishaupt WL20-1-C at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Weishaupt WL20-1-C in the language / languages: English as an attachment in your email.

The manual is 2.11 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Weishaupt WL20-1-C

Weishaupt WL20-1-C User Manual - German - 40 pages

Weishaupt WL20-1-C Installation Guide - Dutch - 32 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info