NOTE: The use of silicone sealants may hinder the effectiveness of some leak detectors.
Intrinsically safe components do not need to be sealed before working on them.
10. repair of intrinsically safe components
Do not apply a permanent inductive load or capacitive load to the circuit without ensuring that
this does not exceed the permissible voltage and current for the equipment being used.
Intrinsically safe components are the only types that can be worked on while connected to the
mains in the presence of a flammable atmosphere. The test equipment must have the correct
ratings. Replace components only with parts specified by the manufacturer. Other parts may
cause the refrigerant to ignite in the atmosphere due to a leak.
11. wiring
Check that the wiring is not subject to wear, corrosion, excessive pressure, vibration, sharp
edges or other harmful environmental effects. The test must also take into account the effects of
ageing or continuous vibration from sources such as compressors or fans.
12. detection of flammable refrigerants
Under no circumstances should potential sources of ignition be used when searching for or
detecting refrigerant leaks. A halogen search lamp (or any other search device that uses open
flames) must not be used.
13. leak detection methods
The following leak detection methods are considered acceptable for systems containing
flammable refrigerants.
Electronic leak detectors must be used to detect flammable refrigerants, but their sensitivity may
not be sufficient or they may need to be recalibrated. (Detection equipment must be calibrated
in a refrigerant-free area.) Ensure that the leak detector is not a potential source of ignition and
that it is suitable for the refrigerant being used. Leak detection equipment must be set to a
percentage of the lower explosion limit and must be calibrated to the refrigerant used and the
adequate percentage of gas (25% maximum) must be confirmed.
Leak detection fluids are suitable for use with most refrigerants, but the use of cleaning agents
containing chlorine must be avoided as chlorine can react with the refrigerant and degrade the
copper piping.
If a leak is suspected, remove/extinguish all naked flames.
If a refrigerant leak is detected that requires brazing, all refrigerant must be recovered from the
refrigeration system or isolated (by shutting off valves) in a part of the system remote from the
leak. Oxygen-free nitrogen must then be purged through the system before and during the
brazing process.
14. removal and emptying
If you intervene in the refrigerant circuit to carry out repairs - or for any other reason -
conventional methods must be used. However, it is important that best practices are always
followed, as flammability must be considered. The following procedure should be followed:
- Remove the refrigerant
- Purge the circuit with inert gas
- Deflate
- Rinse again with inert gas
- Open the circuit by cutting or soldering
6


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for WDH 930EEW at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of WDH 930EEW in the language / languages: English as an attachment in your email.

The manual is 0.87 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of WDH 930EEW

WDH 930EEW User Manual - German - 16 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info