The refrigerant charge must be prepared in the correct preparation cylinders. The system must
be "purged" with oxygen-free nitrogen to keep the unit safe. This process may need to be
repeated several times. Compressed air or oxygen must not be used for this purpose.
Purging can be achieved by intervening in the vacuum in the system with oxygen-free nitrogen
and continuing to charge until the working pressure is reached and then releasing to
atmosphere and finally drawing into a vacuum. This process must be repeated until there is no
more refrigerant in the system. When the last charge of oxygen-free nitrogen is made, the
system must be vented to atmospheric pressure. This is absolutely necessary if soldering work
has to take place on the piping. Make sure that the outlet for the vacuum pump is not near
sources of ignition and that there is ventilation.
15. Filling process
In addition to conventional filling operations, the following requirements must be followed:
- Ensure that there is no contamination of the various refrigerants when charging the equipment.
Hoses or cables must be as short as possible to minimise the amount of refrigerant they
contain.
- Cylinders must remain upright.
- Make sure that the cooling system is earthed before charging the system with refrigerant.
- Mark the system when filling is complete (if not already done).
- Extreme care must be taken not to overfill the cooling system.
Before refilling the system, the pressure must be tested with oxygen-free nitrogen. The system
must be tested for leakage at the end of filling but before commissioning. A verification leakage
test must be carried out before leaving the site.
16. Decommissioning
Before performing this procedure, it is necessary for the technician to be fully familiar with the
equipment and its details. It is a recommended standard that all refrigerants are safely
reprocessed. Prior to the task to be performed, an oil sample and a refrigerant sample must be
taken in case analysis is required before reusing the recycled refrigerant. It is necessary that
electrical power is available before the task is started.
a) Familiarise yourself with the equipment and its operation.
b) Disconnect the system electrically.
c) Before performing the operation, make sure:
that mechanical handling equipment is available; if necessary also for the
Handling refrigerant cylinders;
that personal protective equipment is available and properly worn;
that the reprocessing process is supervised by a competent person at all times;
that the treatment equipment and cylinders comply with the applicable standards.
d) Pump out the refrigerant system if possible.
e) If a vacuum is not possible, make a manifold so that the coolant can be removed from the
various parts of the system.
f) Make sure that the cylinder is on the scales.
g) Start the treatment plant and operate it according to the manufacturer's instructions.
h) Do not overfill the cylinders (not more than 80 % capacity liquid filling).
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been properly filled and the operation is complete, ensure that the
cylinders and equipment are immediately removed from the site and that all shut-off valves on
the equipment are closed.
(k) Reconditioned refrigerant shall not be charged into other refrigeration systems unless it has
been purified and tested.
7


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for WDH 310EKW at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of WDH 310EKW in the language / languages: English as an attachment in your email.

The manual is 0.55 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of WDH 310EKW

WDH 310EKW User Manual - German - 16 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info