7. FUNCTIONS
- Heat Cool input signal (Master mode switch 1 OFF)
When BT-HCM02 RF is in master mode for Heat/Cool, it decides if system is in heating mode or in cooling
mode according to H&C imputs:
o Free contact input (manual switch or automatic from heat pump):
if contact is opened then system is in heating mode
if contact is closed then system is in cooling mode
o NTC Sensor 10K connected on the water inlet:
if temperature > 24°C, system is in heating mode
if temperature < 20°C, system is in cooling mode
Heating or cooling switch is delayed 2sec / 5minutes depending on the state of DIP switch 3.
For system initialisation, when you are using a water sensor, unplug the sensor to trigger the system in the
proper mode, then plug the sensor.
- Heat output: (free contact)
Heat relay is closed when system is in heating mode.
- Cold output: (free contact)
Cold relay is closed when system is in cooling mode.
- Dehumidifier output: (free contact)
Humidity relay is closed when
o system is in cooling mode
o AND there is a detection of humidity on at least one of thermostat with humidity sensor BT-D(P)02-
RF RH (refer to its instruction manual to have more information about humidity configuration)
o AND humidity function is activate (DIP switch 2 OFF)
- 230V Pump output: (live contact)
230V relay is closed when there is at least one demand on the system, a typpical application to this output
is Pump output.
Note: to use this output, installer needs to strap the “SECU” connector
8


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Watts BT-HCM02 - Heat and cool module at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Watts BT-HCM02 - Heat and cool module in the language / languages: English, German, Dutch, French, Italian as an attachment in your email.

The manual is 1.91 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info