If Refresh by Key is selected, the first pressing of any key
(except Fire and Emergency) will cause normal display
return and the second press will perform the key function.
Regarding the Fire and Emergency keys, the first key
press will cause normal display return and also will perform
the Fire/Emergency function.
Options: scrn saver OFF, refresh by code, refresh by key.
4.4.33 Confirm Alarm
(Fig. 4.4, location 33). Here you determine that if 2
successive alarms will occur during a specific period, the
second alarm will be considered as a confirmed alarm
(for confirmed alarm reporting, (see par. 4.5.3).
Options: disable 30 min., 45 min., 60 min., or 90 min.
4.4.34 AC FAIL REP
(Fig. 4.4, location 34). Here you determine the time interval
between AC power failure occurrence and the failure
reporting. Options: 5 minutes, 30 minutes, 60 minutes or
180 minutes.
Note: To comply with EN requirements, set to 60 min. max.
4.4.36 User Permission
(Fig. 4.4, location 36). Here you determine whether the
access to the INSTALLER MODE requires user permission.
If you select ENABLE, the installer mode will be accessible
only through the user menu after entering the user code.
Options: Enable, Disable.
Note: To comply with EN requirements, "Enable" must be
selected.
4.4.39 Key Zones Options (Optional)
(Fig. 4.4, location 39). Here you determine whether or not
the system can be armed and disarmed by zones 21-28, 29
or 21-29, provided that for these zones "non-alarm type"
and "z-key enable" was predefined (see par. 4.3 and
Appendix C14).
Key zones can be wireless or wired zones.
When using wireless key zones, only the MCT-100 and
MCT-102 transmitters are used. The right pushbutton on
the MCT-102 transmitter or input 2 of the MCT-100
transmitter is used for arming in AWAY mode. The left
pushbutton on the MCT-102 transmitter or input 1 of the
MCT-100 transmitter is used for disarming.
When using wired key zones an open circuit arms the
alarm system in AWAY mode and a closed circuit changes
the state of the alarm system from AWAY mode to Disarm.
(For information on how to connect to wired key zones,
see Fig. 3.1C Zones and Sirens Wiring.
IMPORTANT! Enrolment of the MCT-100 or MCT-102
transmitter must be performed via the right pushbutton on
the MCT-102 transmitter or input 2 of the MCT-100
transmitter (see section 4.3).
Note: Key Zones does not comply with Belgium TO14A
and EN 50131-5-3.
Caution! Arming the system using a transmitter
assigned to zones 21 and 28, or via wired zone 29
compromises security. This function is, therefore, only
available in specific PowerMaxExpress versions
according to the customer's request.
Options: disable option, z. 21-28 enable, z. 29 enable, or
z. 21-29 enable.
4.4.41 Cancel Announcement
(Fig. 4.4, location 41). (Applicable in the USA only).
Here you determine whether a special beep will sound
when an alarm cancel event is sent to the central station.
Options: Enable, Disable.
4.4.42 Abort Announcement
(Fig. 4.4, location 42). (Applicable in the USA only)
Here you determine that when the user disarms the
system within the allowed abort interval, a special beep will
sound to indicate "no alarm transmission".
Options: Enable, Disable.
4.4.43 CP-01
(Fig. 4.4, location 43). (Applicable in the USA only)
Here you determine whether to enable or disable some of
the CP-01 standard requirements.
Options: Enable, Disable.
16


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Visonic PowerMax Express at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Visonic PowerMax Express in the language / languages: English as an attachment in your email.

The manual is 3,94 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Visonic PowerMax Express

Visonic PowerMax Express User Manual - Dutch - 35 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info