Rated voltage: 230 V–
Rated frequency: 50 Hz
Rated current: 6.3 A
Safety class: I
Protection: IP X 4 D to
EN 60529
Permissible ambient temperature
&
during operation: 0 to +40 °C
&
during storage
and transport:
-20 to +65 °C
Electronic tempera-
ture limiter setting:
82 °C
Temperature limiter
setting:
100 °C (fixed)
Line fuse (mains): max. 16 A
Power consumption
&
Circulation
pumps:
max. 220 W
&
Burner: max. 40 W
&
Control unit: max. 10 W
Gas fired condensing compact boiler, category II
2ELL3P
Rated output range TV/TR 50/30 °C kW 4.2 to 13
Rated thermal load range
&
for central heating
&
for DHW heating
kW
kW
3.9 to 12.3
3.9 to 16.7
Connection values
relative to the max. load
with
Natural gas E m
3
/h 1.77
Natural gas LL m
3
/h 2.05
LPG kg/h 1.31
Product ID _-0085 BO 0338
Note
The supply values are only for docu-
mentation purposes (e.g. in the gas
contract application) or to estimate
the supplementary volumetric set-
tings. Because of factory settings, the
gas pressure must not be altered from
these settings. Reference: 15 °C,
1013 mbar.