Vitocell 300-W/V, EVIA/EVIB Installation, Operating and Service
Installation
Domestic Water Connections (continued)
WARNING
The valve test lever must be operated at least once per
year by the owner to ensure that waterways are clear.
A licensed professional heating contractor shall reinspect
the T&P valve at least once every three years. Failure
to inspect can result in unsafe temperature or pressure
build-up, which can result in death, serious injury or
substantial product/property damage.
Proper installation of the T&P valve shall include all of the
following:
- The T&P valve shall be installed in the pipe connection
point as shown in this manual.
- The discharge line from the T&P valve shall be 7 ¾ in.
(19 mm) and run to a safe place of discharge
approximately 1 ft. (305 mm) above the floor, close to
a floor drain.
- The discharge line must be as short as possible and
pitch downward from the T&P valve and terminate plain
not threaded.
Always ensure the use of type approved devices.
Safety devices include the following components:
- Isolation valves
- Drain valve
- Pressure reducing valve
where required by local jurisdiction
- Drinking water filter
where required by local jurisdiction
- Backflow preventer
Where backflow preventers are required, a domestic
water expansion tank installation is required in the
cold water inlet piping before the cold water enters
the tank. The backflow device must be installed
according to the manufacturer’s installation
instructions. Observe local codes and regulations.
- Tempering valve
A tempering valve must be field installed where
storage tank (domestic hot water temperature)
exceeds local restricted temperatures or 140°F
(60°C). Check code requirements.
IMPORTANT
In situations where a booster pump is used to maintain
DHW pressure, Viessmann strongly recommends the
installation of an oversized large expansion tank to
ensure longer, less frequent pump cycles with less
severe pressure gradients. If possible, use flexible piping
before and after booster pump to isolate system piping
from vibration and shocks.
WARNING
The discharge line for the T&P valve must be oriented to
prevent scalding of attendants.
- Do not route discharge line directly to the outdoors.
- Do not install any type of valve or restriction of any
kind between the tank and the T&P valve, or
between the T&P valve and the discharge line outlet.
- Temperature and pressure relief valve
A temperature and pressure relief valve (T&P valve)
is supplied with the tank. The heating contractor must
install the valve on each tank in a method meeting
code requirements.
If local codes require a different relief valve, consult
Viessmann Manufacturing for a substitute valve.
The tank is approved for 150 psig. Maximum operating
pressure is 150 psig.
The T&P valve supplied with the tank is tested under
ANSI Z21.22 Code for Relief Valves and Automatic
Gas Shut-off Devices for Hot Water Supply Systems.
T&P Valve set pressure 150 psig
CSA discharge capacity 205 MBH*
Relief temperature 210°F (99°C)
Inlet thread c” male
Outlet thread c” female
*105 MBH for 42 USG (160 L)
16


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Viessmann Vitocell 300-V EVIB at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Viessmann Vitocell 300-V EVIB in the language / languages: English as an attachment in your email.

The manual is 1.24 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Viessmann Vitocell 300-V EVIB

Viessmann Vitocell 300-V EVIB Usermanual and installation guide - French - 32 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info