Control strategy
The control strategy specifies in which operating
ranges the heat pump and/or external heat generator
operates.
These operating ranges also depend on the operating
mode set by your heating contractor.
Parallel operation
ABA
+
Fig. 16
ϑAOutside temperature
ALower temperature limit, value dependent on the
control strategy
BUpper temperature limit
The heat pump is switched on for room heating/
room cooling and DHW heating as required.
The external heat generator is switched on for cen-
tral heating and DHW heating as required.
When outside temperature is above the upper tem-
perature limit B:
Room heating/room cooling and DHW heating are
supplied only by the heat pump.
The external heat generator does not start.
When outside temperature is between the two tem-
perature limits:
For normal heat demand, only the heat pump is
switched on.
For increased heat demand, the external heat gen-
erator is switched on in addition to the heat pump.
The heat pump can be switched on for room cool-
ing.
When outside temperature is below the lower tem-
perature limit A:
The heat pump does not operate.
Room heating and DHW heating are supplied only
by the external heat generator.
Room cooling is switched off.
Alternative operation
AA
Fig. 17
ϑAOutside temperature
ATemperature limit, value dependent on the control
strategy
The heat pump is switched on for room heating/
room cooling and DHW heating as required.
The external heat generator is switched on for cen-
tral heating and DHW heating as required.
When the outside temperature is above temperature
limit A:
Room heating/room cooling and DHW heating are
supplied only by the heat pump.
The external heat generator does not start.
When the outside temperature is below temperature
limit A:
The heat pump does not operate.
Room heating and DHW heating are supplied only
by the external heat generator.
Room cooling is switched off.
The temperature limits of these operating ranges are
determined in the control strategy.
Ecological control strategy
The control unit specifies the temperature limit A
based on what will achieve the lowest CO2 emissions.
The heat pump control unit calculates the resulting
CO2 emissions on the basis of the primary energy fac-
tors for electricity and fossil fuels.
The primary energy factors are stored in the heat
pump control unit. During an update, the primary
energy factors are automatically updated.
Economical control strategy
The control unit specifies the temperature limit A
based on what will achieve the lowest running costs.
The heat pump control unit calculates the running
costs on the basis of the energy prices you have
entered for electricity and fossil fuels.
You can enter the energy prices via the ViCare app.
Appendix
Terminology (cont.)
6199646
64


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Viessmann VITOCAL 250-A at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Viessmann VITOCAL 250-A in the language / languages: English as an attachment in your email.

The manual is 4.93 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Viessmann VITOCAL 250-A

Viessmann VITOCAL 250-A User Manual - German - 80 pages

Viessmann VITOCAL 250-A User Manual - Dutch - 76 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info