3.3 PV configuration (also see the MPPT Excel sheet on our website)
● The controllers will operate only if the PV voltage exceeds
battery voltage (Vbat).
● PV voltage must exceed Vbat + 5V for the controller to start.
Thereafter minimum PV voltage is Vbat + 1V.
● Maximum open circuit PV voltage: 150V or 250V, depending on model.
For example:
24V battery, mono- or polycristalline panels, max PV voltage 150V:
● Minimum number of cells in series: 72 (2x 12V panel in series
or one 24V panel).
● Recommended number of cells for highest controller efficiency:
144 cells (4x 12V panel or 2x 24V panel in series).
● Maximum: 216 cells (6x 12V or 3x 24V panel in series).
48V battery, mono- or polycristalline panels, max PV voltage 250V:
● Minimum number of cells in series: 144
(4x 12V panel or 2x 24V panel in series).
● Maximum: 360 cells (10x 12V or 5x 24 panel in series).
Remark: at low temperature the open circuit voltage of a 216 cell solar
array may exceed 150V, and the open cicuit voltage of a 360 cell array
may exceed 250V, depending on local conditions and cell specifications. In
that case the number of cells in series must be reduced.
3.4 Cable connection sequence (see figure 1)
First: connect the battery.
Second: if required, connect the remote on-off and programmable relay
Third: connect the solar array (when connected with reverse polarity, the
controller will heat up but will not charge the battery).
3.5 Remote on-off
The left terminal is connected to the internal 3,3V supply, with a resistor in
series for short circuit protection.
The right terminal (marked as + or marked as H) will switch the controller
on if >3V is applied, and will switch the controller off if <2V is applied or if
the terminal is left free floating.
The recommended use of the remote on-off is:
a. A switch wired between the left and right terminal
b. A switch wired between battery plus and the right terminal.
c) A switch between the right terminal and the charge disconnect terminal of a VE.Bus
BMS
9


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Victron SmartSolar MPPT 250 60 MC4 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Victron SmartSolar MPPT 250 60 MC4 in the language / languages: English, German, Dutch, French, Swedish, Spanish as an attachment in your email.

The manual is 1.66 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info