785398
8
Zoom out
Zoom in
Previous page
1/86
Next page
6
WARNING: WHEN A GROUND FAULT IS INDICATED,
BATTERY TERMINALS AND CONNECTED CIRCUITS MAY BE
UNGROUNDED AND HAZARDOUS.
3.3 PV configuration (also see the MPPT Excel sheet on
our website)
Provide a means to disconnect all current-carrying conductors
of a photovoltaic power source from all other conductors in a
building or other structure.
A switch, circuit breaker, or other device, either ac or dc, shall
not be installed in a grounded conductor if operation of that
switch, circuit breaker, or other device leaves the grounded
conductor in an ungrounded state while the system remains
energized.
The controller will operate only if the PV voltage exceeds
battery voltage (Vbat).
PV voltage must exceed Vbat + 5V for the controller to start.
Thereafter minimum PV voltage is Vbat + 1V.
Maximum open circuit PV voltage: 100V.
For example:
12V battery and mono- or polycristalline panels
Minimum number of cells in series: 36 (12V panel).
Recommended number of cells for highest controller efficiency:
72 (2x 12V panel in series or 1x 24V panel).
Maximum: 144 cells (4x 12V or 2x 24V panel in series).
24V battery and mono- or polycristalline panels
Minimum number of cells in series: 72 (2x 12V panel in series
or 1x 24V panel).
Maximum: 144 cells.
Remark: at low temperature the open circuit voltage of a 144 cell
solar array may exceed 100V, depending on local conditions and
cell specifications. In that case the number of cells in series must
be reduced.
3.4 Cable connection sequence (see figure 1)
First: connect the battery.
Second: connect the solar array (when connected with reverse
polarity, the controller will heat up but will not charge the battery).
8


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Victron SmartSolar MPPT 100 50 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Victron SmartSolar MPPT 100 50 in the language / languages: English, German, Dutch, French, Swedish, Spanish as an attachment in your email.

The manual is 0.68 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info