EN NL FR DE ES Appendix
2.3. Other options
The wiring of these signals must be done with the mains disconnected from the charger.
CONNECTION BLOCK FOR EXTERNAL SENSORS, SWITCH AND RELAY
Figure 5 Connector block
2.3.1. External voltage sensor (see fig 5)
External voltage sensing may be used when accurate battery voltage sensing is important, such as high charging currents in
combination with long cables.
To connect the external voltage sensing option, proceed as follows:
connect a red wire (0.75mm2) between the positive battery pole and connector "+ Voltage sensor"
connect a black wire (0.75mm2) between the negative battery pole and connector "- Voltage sensor
check that the accompanying LED is lit, otherwise check cabling
2.3.2. External temperature sensor (see fig 5)
The external temperature sensor, supplied with the charger, can be connected to these terminals in order to perform
temperature compensated charging of the battery. The sensor is electrically isolated and must be connected to the negative
pole of the battery.
To connect the temperature sensor, proceed as follows:
connect the red wire to connector "+ Temperature sensor"
connect the black wire to connector "- Temperature sensor"
mount the temperature sensor on the negative pole of the battery
check that the accompanying LED is lit, otherwise check cabling
2.3.3. Remote on/off (see fig 5)
The wiring of the remote switch requires extra attention. Since this input is quite sensitive it is advised to use twisted wires for this
connection.
The remote on/off input can also be connected to an open collector optocoupler: the open circuit voltage is 3V and the closed circuit
current is 100 µA.
When no remote switch is connected the remote on/off terminals must be short circuited by a short wire.
The remote on/off input can be connected to a Lithium Battery Management System VE.Bus BMS ('charge disconnect' output)
with a Skylla-i remote on-off cable ASS030550400.
2.3.4. Alarm relay connections (see fig 5)
The alarm relay is active when the charger is charging normally, no error condition present and the battery voltage is within the
voltage range 23.7V and 33.6V. The relay is switched off when the charger stops, an error occurs or when the voltage drops
below 23.45V or rises above 33.85V.
2.3.5. CAN bus connection (VE.Can)
The VE.Can connectors (RJ45) provide access for control (Skylla-i remote control panel, Color Control GX or NMEA 2000). The
two RJ45 connecters in each charger (see figure 7) are parallel connected. There is therefore no functional difference between
these connectors.
The end of a CAN cable should have a bus terminator. This is achieved by inserting a bus terminator in one of the two RJ45
connectors and the CAN cable in the other. In case of a node (two CAN cables, one in each RJ45 connector), no termination is
needed.
Several Skylla-i control panels can be connected to one charger or to a set of synchronised and parallel connected chargers.
A Lynx Ion can be connected to the Skylla-i charger directly via the VE.Can bus, the 'allow-to-charge' condition will be
communicated via the VE.Can bus automatically, no separate wiring is required.
+ -
Voltage
sensor
+ -
Temperature
sensor
+ -
Remote
on/off
NO NC COM
Alarm relay
7


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Victron Skylla-i 24 80 (1 1) at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Victron Skylla-i 24 80 (1 1) in the language / languages: English, German, Dutch, French, Spanish as an attachment in your email.

The manual is 0.96 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info