785528
17
Zoom out
Zoom in
Previous page
1/164
Next page
15
EN NL FR DE ES SE Appendix
5.5 Configuration with DIP switches
A number of settings can be changed using DIP switches (see appendix A, position M).
Note: When changing settings with DIP switches in a parallel or split-phase/3-phase system one should be aware that not all settings
are relevant on all Multis. This because some settings will be dictated by the Master or Leader.
Some settings are only relevant in the Master/Leader (i.e. they are not relevant in a slave or in a follower). Other settings are not
relevant for slaves but are relevant for followers.
A note on used terminology:
A system in which more than one Multi is used to create a single AC phase is called a parallel system. In this case one of the Multis will
control the whole phase, this one is called the master. The others, called slaves, will just listen to the master to determine their action.
It is also possible to create more AC phases (split-phase or 3-phase) with 2 or 3 Multis. In this case the Multi in phase L1 is called the
Leader. The Multis in phase L2 (and L3 if available) will generate the same AC frequency but will follow L1 with a fixed phase shift.
These Multis are called followers.
If more Multis are used per phase in a split-phase or 3-phase system (for instance 6 Multis used to build a 3-phase system with 2 Multis
per phase) then the Leader of the system is also the Master of phase L1. The Followers in phase L2 and L3 will also take the Master
role in phase L2 and L3. All others will be slaves.
Setting up parallel or split-phase/3-phase systems should be done by software, see paragraph 5.3.
TIP: If you don’t want to bother about a Multi being a master/slave/follower then the easiest and most straight forward way is to set
all settings identically on all Multis.
General procedure:
Turn the Multi on, preferably without load and without AC voltage on the input. The Multi will then operate in inverter mode.
Step 1: Set the DIP switches for:
- The required current limitation of the AC input (not relevant for slaves)
- AES (Automatic Economy Switch) (only relevant in systems with 1 Multi per phase)
- Limitation of the charging current (only relevant for Master/Leader)
Press the 'Up' button for 2 seconds (upper button to the right of the DIP switches, see appendix A, position K) to store the settings after
the required values have been set. You can now re-use the DIP switches to apply the remaining settings (step 2).
Step 2: other settings, set the DIP switches for:
- Charge voltages (only relevant for Master/Leader)
- Absorption time (only relevant for Master/Leader)
- Adaptive charging (only relevant for Master/Leader)
- Dynamic current limiter (not relevant for slaves)
- UPS function (not relevant for slaves)
- Converter voltage (not relevant for slaves)
- Converter frequency (only relevant for Master/Leader)
Press the 'Down' button for 2 seconds (lower button to the right of the DIP switches) to store the settings after the DIP switches have
been set in the correct position. You can now leave the DIP switches in the selected positions, so that the ’other settings’ can always be
recovered.
Remarks:
- The DIP switch functions are described in 'top to bottom' order. Since the uppermost DIP switch has the highest number (8),
descriptions start with the switch numbered 8.
- In parallel or split-phase/3-phase systems, this procedure must be repeated for all Multis.
Detailed instruction:
5.5.1 Step 1
5.5.1.1 AC input current limitation
(default: 16 A for models with max. 16 A feed through current, and 50 A for models with max. 50 A feed through current)
When the AC input current drawn by the Multi (due to the connected loads and the battery charger) rises and is about to exceed the AC
input current limit, the Multi will first reduce its charging current (PowerControl) and subsequently, if needed, supply additional power
from the battery (PowerAssist). This way the Multi will try to prevent that the input current exceeds the set limit.
The AC input current limit can be set to eight different values by means of DIP switches.
With a Multi Control Panel, a variable current limit can be set for the AC input.
17


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Victron MultiPlus 48 3000 35-16 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Victron MultiPlus 48 3000 35-16 in the language / languages: English, German, Dutch, French, Swedish, Spanish as an attachment in your email.

The manual is 2.06 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info