785512
15
Zoom out
Zoom in
Previous page
1/146
Next page
15
EN NL FR DE ES IT Appendix
Ground relay (see appendix B)
With this relay (H), the neutral conductor of the AC output is grounded to the chassis when
the back-feed safety relay is open. This ensures the correct operation of earth leakage
circuit breakers in the output.
If a non-grounded output is required during inverter operation, this function must be turned
off.
(Use VE-Configure)
The standard setting is ‘Four-stage adaptive with BatterySafe mode’. See Section 2 for a
description.
This is the recommended charge curve. See the help files in the software configuration
programs for other features.
Battery type
The standard setting is the most suitable for Victron Gel Deep Discharge, Gel Exide A200,
and tubular plate stationary batteries (OPzS). This setting can also be used for many other
batteries: e.g. Victron AGM Deep Discharge and other AGM batteries, and many types of
flat-plate flooded batteries. Four charging voltages can be set with DIP switches.
Automatic equalisation charging
This setting is intended for tubular plate traction batteries. During absorption the voltage
limit increases to 2,83V/cell (34V for a 24V battery) once the charge current has tapered
down to less than 10% of the set maximum current.
Absorption time
The absortion time depends on the bulk time (adaptive charge curve), so that the battery is
optimally charged. If the ‘fixed’ charging characteristic is selected, the absorption time is
fixed. For most batteries, a maximum absorption time of eight hours is suitable. If an extra
high absorption voltage is selected for rapid charging (only possible for open, flooded
batteries!), four hours is preferable. With DIP switches, a time of eight or four hours can be
set. For the adaptive charge curve, this determines the maximum absorption time.
Storage voltage, Repeated Absorption Time, Absorption Repeat Interval
See Section 2.
Bulk Protection
Default setting: off. When this setting is ‘on’, the bulk charging time is limited to 10 hours. A
longer charging time could indicate a system error (e.g. a battery cell short-circuit).
AC input current limit
These are the current limit settings at which PowerControl come into operation. The factory
setting is 12A.
UPS feature
If this setting is ‘on’ and AC on the input fails, the Multi switches to inverter operation
practically without interruption. The Multi can therefore be used as an Uninterruptible Power
Supply (UPS) for sensitive equipment such as computers or communication systems.
The output voltage of some small generator sets is too unstable and distorted for using this
setting* the Multi would continually switch to inverter operation. For this reason, the setting
can be turned off. The Multi will then respond less quickly to AC input voltage deviations. The
switchover time to inverter operation is consequently slightly longer, but most equipment
(most computers, clocks or household equipment) is not adversely impacted.
15


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Victron MultiPlus 24 500 10-16 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Victron MultiPlus 24 500 10-16 in the language / languages: English, German, Dutch, French, Italian, Spanish as an attachment in your email.

The manual is 1.58 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info