4.4.6 Three-phase operation (800VA and 1200VA models only, see appendix D)
The MultiPlus can also be used in 3-phase wye (Y) configuration. To this end, a connection
between the devices is made by means of standard RJ45 UTP cables and a splitter (the
same as for parallel operation). The system (MultiPlus units plus an optional control panel)
will require subsequently configuration (see Section 5).
Pre-requisites: see Section 4.4.5.
Note: the MultiPlus is not suitable for 3-phase delta (Δ) configuration.
5. CONFIGURATION
Settings may only be changed by a qualified engineer
Carefully read the instructions before changes are made.
Batteries should be placed in a dry and well-ventilated area during charging.
5.1 Standard settings: ready for use
On delivery, the Multi is set to standard factory values. In general, these settings are
suitable for single-unit operation.
Warning: Possibly, the standard battery charging voltage is not suitable for your
batteries! Refer to the manufacturer's documentation or to your battery supplier!
Standard Multi factory settings
Inverter frequency 50 Hz
Input frequency range 45 - 65 Hz
Input voltage range 180 - 265 VAC
Inverter voltage 230 VAC
Stand-alone / parallel / 3-phase stand-alone
Search mode off
Ground relay on
Charger on/ off on
Battery charge algorithm four-stage adaptive with BatterySafe mode
Charge current 100% of the maximum charge current
Battery type Victron Gel Deep Discharge (also suitable
for Victron AGM Deep Discharge)
Automatic equalisation charging off
Absorption voltage 14.4 / 28.8 / 57,6V
Absorption time up to 8 hours (depending on bulk time)
Float voltage 13.8 / 27.6 / 55,2V
Storage voltage 13.2 / 26.4 / 52,8V (not adjustable)
Repeated absorption time 1 hour
Absorption repeat interval 7 days
Bulk protection off
AC input current limit 12A (= adjustable current limit for PowerControl and
PowerAssist functions)
UPS feature on
Dynamic current limiter off
WeakAC off
BoostFactor 2
Programmable relay alarm function
13


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Victron MultiPlus 12 500 20-16 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Victron MultiPlus 12 500 20-16 in the language / languages: English, German, Dutch, French, Italian, Spanish as an attachment in your email.

The manual is 1.58 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info