785525
19
Zoom out
Zoom in
Previous page
1/164
Next page
17
EN NL FR DE ES SE Appendix
5.5.1.5 Examples
examples of settings:
DS-8 AC input
on
DS-7 AC input
on
DS-6 AC input
on
DS-5 AES
off
DS-4 Ch. current
on
DS-3 Ch. current
off
DS-2 N/A
off
DS-1 N/A
off
DS-8
on
DS-7
on
DS-6
on
DS-5
off
DS-4
on
DS-3
on
DS-2
off
DS-1
off
DS-8
off
DS-7
on
DS-6
on
DS-5
off
DS-4
on
DS-3
on
DS-2
off
DS-1
off
DS-8
on
DS-7
on
DS-6
off
DS-5
on
DS-4
off
DS-3
on
DS-2
off
DS-1
off
Step 1, Example 1 (factory
setting):
8, 7, 6 AC-in: 50 A*
5 AES: off
4, 3 Charging current: 75 %
2, 1 N/A
Step1, Example 2:
8, 7, 6 AC-in: 50 A*
5 AES: off
4, 3 Charge: 100 %
2, 1 N/A
Step1, Example 3:
8, 7, 6 AC-in: 16 A
5 AES: off
4, 3 Charge: 100 %
2, 1 N/A
Step1,Example 4:
8, 7, 6 AC-in: 30 A*
5 AES: on
4, 3 Charge: 50 %
2, 1 N/A
*Maximum is limited to 16 A in case of models with 16 A transfer switch
To store the settings after the DIP switches are set according to the required values: press the 'Up' button for 2 seconds (upper button
to the right of the DIP switches, see appendix A, position J). The overload and low-battery LEDs will flash to indicate acceptance of
the settings.
We recommend making a note of the settings, and filing this information in a safe place.
The DIP switches can now be used to apply the remaining settings (step 2).
5.5.2 Step 2: Other settings
The remaining settings are not relevant for slaves.
Some of the remaining settings are not relevant for followers (L2, L3). These settings are imposed on the whole system by the leader
L1. If a setting is irrelevant for L2, L3 devices, this is mentioned explicitly.
ds8-ds7: Setting charging voltages (not relevant for L2, L3)
ds8-ds7
Absorption
voltage
Float
voltage
Storage
voltage
Suitable for
off off
14.1
28.2
56.4
13.8
27.6
55.2
13.2
26.4
52.8
Gel Victron Long Life (OPzV)
Gel Exide A600 (OPzV)
Gel MK battery
off on 14.4
28.8
57.6
13.8
27.6
55.2
13.2
26.4
52.8
Gel Victron Deep Discharge
Gel Exide A200
AGM Victron Deep Discharge
Stationary tubular plate (OPzS)
on off 14.7
29.4
58.8
13.8
27.6
55.2
13.2
26.4
52.8
AGM Victron Deep Discharge
Tubular plate traction batteries in
semi-float mode
AGM spiral cell
on on 15.0
30.0
60.0
13.8
27.6
55.2
13.2
26.4
52.8
Tubular plate traction batteries or
OPzS batteries in cyclic mode
ds6: absorption time 8 or 4 hours (na for L2, L3) on = 8 hours off = 4 hours
ds5: adaptive charging algorithm (na for L2, L3) on = active off = inactive (inactive = fixed absorption time)
ds4: dynamic current limiter on = active off = inactive
ds3: UPS function on = active off = inactive
ds2: converter voltage on = 230 V off = 240 V
ds1: converter frequency (na for L2, L3) on = 50 Hz off = 60 Hz
(the wide input frequency range (45-55 Hz) is 'on' by default)
Note: - If “adaptive charging algorithm” is on, ds6 sets the maximum absorption time to 8 hours or 4 hours.
- If “adaptive charging algorithm” is off, the absorption time is set to 8 hours or 4 hours (fixed) by ds6.
19


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Victron MultiPlus 12 3000 120-50 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Victron MultiPlus 12 3000 120-50 in the language / languages: English, German, Dutch, French, Swedish, Spanish as an attachment in your email.

The manual is 2.06 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info