The low current mode remains activated until the MODE button is
pressed again during 3 seconds.
2. BULK
Charges the battery with maximum current until absorption
voltage is reached. The battery will then be about 80%
charged and is ready for use.
3. ABS - Absorption
Charges the battery at constant voltage and with
decreasing current until it is fully charged.
See table above for absorption voltage at room
temperature.
Adaptive battery management:
The absorption time is short (minimum 30 minutes) if the
battery was (nearly) fully charged and increases to 8 hours
in case of a deeply discharged battery.
4. RECONDITION
Optional reconditioning for deeply discharged lead-acid
batteries.
Reconditioning is applicable to the charge algorithms
NORMAL and HIGH and can be selected by pressing the
MODE button one more time after selection of the required
algorithm.
When in RECONDITION mode the battery will be charged
with low current up to a higher voltage at the end of the
absorption phase.
The RECONDITION LED will be on during charging, and
will blink during the reconditioning period.
During reconditioning the maximum current is equal to 8%
of the nominal current until the maximum voltage is
reached. Reconditioning is terminated after one hour or
when the maximum voltage is reached, whichever comes
first. See table.
Example:
For a 12/15 charger: the recondition current is
15 x 0,08 = 1,2A.
5. FLOAT
Keeps the battery at constant voltage and fully charged.
6. STORAGE
Keeps the battery at reduced constant voltage to limit
gassing and corrosion of the positive plates.
Slow self-discharge is prevented by an automatic weekly
refresh of the battery with a short absorption charge.
9


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Victron Blue Smart IP65 Acculader 12 15 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Victron Blue Smart IP65 Acculader 12 15 in the language / languages: English, German, Dutch, French, Swedish, Spanish, Finnish as an attachment in your email.

The manual is 0.86 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info