Battery charger / inverter COMBI-GAMMA
090138.02 57
B2-09=1
The effective AC input current limit depends on the load history. When the load is •
lower than the AC IN Current Limit (B2-05), the effective AC input current limit is
also lower but slightly above the load.
When the load increase, the effective current limit also increases with a delay. The •
thought behind this is that when a generator is running at a low load, it can’t switch
to full load immediately and it needs some time to increase the power.
An example:*
We have a 2KVA generator.•
We adjust the AC IN Current Limit (B2-05) setting to 8A and we enable Load Support
(C1-05=1). We have no load connected and the batteries are fully charged. Therefore,
no current from the generator is drawn.
At this moment, we connect a load of 7A to the Combi-Gamma with this setting (B2-09) •
disabled, the Combi-Gamma would not react because the load is below the AC IN Cur-
rent Limit (B2-05) setting. The result is that the full load is connected to the generator
which will drop in voltage because it can’t deliver that current instantly which could re-
sult in switching to the INVERTER.
If however we had this setting (Dynamic Current Limit) enabled, the effective AC input •
current limit would be far lower than 8A because the load was zero. So connecting a
load of 7A will result in Combi-Gamma starting to Load Support and no voltage drop is
being examined on the AC OUT. The generator starts to supply the load and the effective
AC input current limit will increase to 8A slowly. At the moment, the Combi-Gamma will
stop Load Support and the full load is on the generator.
This is a powerful option in combination with Load Support but also without Load Sup-•
port, it can prevent unnecessary switching to the INVERTER because the charge cur-
rent will reduce when the AC input current becomes higher than the effective AC input
current limit.
B2-10: MODE4: Bat Lo?V ATS ON
B2-11: MODE4: Bat Lo?S ATS ON
B2-12: MODE4: Bat Hi?V ATSOFF
B2-13: MODE4: Bat Hi?S ATSOFF
B2-14: MODE3: Bat Lo?V ATS ON
B2-15: MODE3: Bat Lo?S ATS ON
B2-16: MODE3: Bat Hi?V ATSOFF
B2-17: MODE3: Bat Lo?S ATSOFF
B2-10~B2-13 are used to set the condition of ATS to be ON/OFF in MODE4•
B2-14~B2-17 are used to set the condition of ATS to be ON/OFF in MODE3•
When Combi-Gamma is in either MODE4 or MODE3, the INVERTER mode takes prior-•
ity to supply voltage to the AC OUT for load consumption. When AC IN power is ready,
the INVERTER is active and the battery is about to be exhausted, ATS will be switched
on to ensure the AC OUT will continuously supply the load. At the moment, AC OUT will
be supplied by the AC IN power. At the same time, the battery can be charged by other
renewable energy such as a solar charger, wind charger or a DC generator charger
(MODE3) which is normally the solar house application in no need of an AC CHARGER.
The battery can be charged by AC IN (AC CHARGER) or other renewable energy such
as a solar charger, wind charger or DC generator charger (MODE4) which is normally
the application requesting both AC charging and DC charging.
57


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Vetus COMBI3012 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Vetus COMBI3012 in the language / languages: English as an attachment in your email.

The manual is 4,72 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Vetus COMBI3012

Vetus COMBI3012 Usermanual and installation guide - Dutch - 80 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info