Battery charger / inverter COMBI-GAMMA
56 090138.02
Note: With * Load Support enabled, there is a minimum value for the AC input current
limit. Please see the note at Load Support (page 60).
B2-06: AC IN Waveform Check
Use constant B2-06 to enable/disable the fast detection of input voltage wave shape.•
Setting Function
B2-06=0
(Ignore)
By disabling AC IN waveform check, • AC IN Low Disconnect (B2-01) is ignored. When the
load current is higher 1.5 times than AC In Current Limit (B2-05), this is used to prevent
unnecessary switching to INVERTER due to voltage drop when a high load is connected.
B2-06=1
(Initial setting)
(Active)
This detection checks the wave shape, if it is not sinusoidal within certain limits, the AC •
input voltage is rejected.
However, certain generator or very weak mains supply have an ill shaped sinusoidal •
output especially when the load suddenly changes. The fast detection will detect a failure
in such a case.
This will result in a slightly longer transfer time.•
B2-07: Ground Relay
Used to enable/disable the internal ground relay functionality. The ground relay is useful •
when an earth-leakage circuit-breaker is part of the installation.
When ATS (Auto Transfer Switch) is open (INVERTER mode), the Neutral of the inverter •
is connected to “Ground” terminal.
When ATS closes (AC IN is transferred to AC OUT), the Neutral is first disconnected •
from “Ground” terminal.
Setting Function
B2-07=0 The internal ground relay is open with “G” terminal.
B2-07=1
(Initial setting)
The internal ground relay is closed with “G” terminal.
B2-08: AC IN Frequency Range
Refer to (B1-01)
B2-09: AC IN Dynamic Current Limit
This setting is an expansion of the • AC IN Current Limit (B2-05) mechanism.
Setting Function
B2-09=0
(Initial setting)
The AC current limit is specified by the • AC IN Current Limit (B2-05) setting
56


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Vetus COMBI1524 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Vetus COMBI1524 in the language / languages: English as an attachment in your email.

The manual is 4,72 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Vetus COMBI1524

Vetus COMBI1524 Usermanual and installation guide - Dutch - 80 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info