1010 3-90-30007498Vermont Castings • Radiance RADVT Installation Manual_R32 • 10/23
Your stove is approved to be vented either through the side
wall, or vertical through the roof.
HHT does not require any opening for inspection of vent
pipe.
Only HHT SLP venting components or DuraVent venting
components specically approved and labeled for this
stove may be used.
Maintain minimum clearances between vent pipes and
combustible materials.
Venting terminals shall not be recessed into a wall or
siding.
Any horizontal run must have a 1/4” rise for every one (1)
foot of run towards the vent termination. Never run the
vent level or down.
There must not be any obstruction such as bushes, garden
sheds, fences, decks or utility buildings within 24" from the
front of the termination hood.
Do not locate termination hood where excessive snow or ice
build up may occur. Be sure to check vent termination area
after snow falls, and clear to prevent accidental blockage of
venting system. When using snow blowers, make sure snow
is not directed towards vent termination area.
Location of Vent Termination
It is imperative the vent termination be located observing the
minimum clearances as shown in this manual.
Vent Termination Clearances
When planning the installation, consider the location of the
vent terminal and clearances. Some of the most common
clearances to keep in mind are shown in Figure 2.11.
Important:All vent clearances must be maintained.
Check your vent termination clearances against Figures
2.11 and 2.12.
The vent should be placed so that people cannot be burned
by accidentally touching the vent surfaces when the stove
is operating.
The vent termination should be located where it cannot be
damaged by such things as automobile doors, lawn mowers
or snowblowers and it should be located away from areas
where it could become blocked by snow, etc.
Some considerations are:
Obstructions or impediments to venting.
Nearby combustible materials that could come into
contact with combustion exhaust gases.
Other nearby openings {within 12" (305 mm)} through
which exhaust gas could reenter the building.
All vegetation within 3’ (76 mm) that may interfere with
the draft.
Other factors that inuence where the installation will be
sited include the location of outside walls, where additional
heat may be desired in the home, where the family members
gather most regularly, and perhaps most importantly, the
distance limitations of the venting system.
IMPORTANT
The horizontal termination must not be recessed into
the exterior wall or siding.
Horizontal vent runs must be level toward the vent
termination.
Clearances around the vent termination must be
maintained.
For installations using DuraVent pipe, parallel installations
with minimum wall clearance have restricted access for
connecting the Horizontal Vent Cap straps to the vent
pipe. See the maker’s instructions for recommended
installation procedures.
10


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Vermont Castings Radiance Series at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Vermont Castings Radiance Series in the language / languages: English as an attachment in your email.

The manual is 6.69 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Vermont Castings Radiance Series

Vermont Castings Radiance Series User Manual - French - 46 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info