883-90-30007498Vermont Castings • Radiance RADVT Installation Manual_R32 • 10/23
The installation of your Vermont Castings stove must
conformwithlocalcodes,orintheabsenceoflocal
codes,withtheNationalFuelGasCodeANSIZ223.1/
NFPA 54 - latest edition, or CSA B149.1 Installation
code. (EXCEPTION: Do not derate this appliance
foraltitudeupto2,000(610m)fornaturalgasand
4,500feet(1,370m)forLPGas.Maintainthemanifold
pressure at 3.5" w.c. for Natural Gas and 10.0" w.c.
for LP Gas.
HIGH ELEVATIONS
Input ratings are shown in BTU per hour and are
certiedwithoutderationforelevationsupto2,000
feet(610m)fornaturalgasand4,500feet(1,370m)
forLPgasabovesealevel.
IntheUSAinstallationswithelevationsabove2,000
feet(610m)fornaturalgasand4,500feet(1,370m)for
LPgasmustbeinaccordancewiththecurrentANSI
Z223.1/NFPA54and/orlocalcodeshavingjurisdiction.
In Canada, please consult provincial and/or local
authorities having jurisdiction for installations at
elevations above 2,000 feet (610 m) for natural gas
and4,500feet(1,370m)forLPgas.
Horizontal Termination
The vent must rise vertically a minimum of 24" (610 mm) o󰀨
the top of the unit, before the rst elbow. The horizontal run
may extend up to 20’ (6m) and include a vertical rise of up
to 40’ (12 m). (Figure 2.7) Horizontal termination must also
meet the criteria shown in Figures 2.11 and 2.12.
Approved vent systems must terminate above and
including the heavy line in Figure 2.7.
Two 45° elbows may be substituted for each single 90°
elbow.
With a rise between 2’ - 5’, one 90° or two 45° elbows
may be used.
Figure 2.7 - Horizontal vent termination window.
Model Fuel Control
Max.
Input
BTU/h
Min. Input
BTU/h
RADVT Nat. Millivolt
Manual 38,000 25,000
RADVT LP Millivolt
Manual 36,000 25,000
RADVT-IFT Nat. IFT 38,000 25,000
RADVT-IFT LP IFT 36,000 25,000
Gas Inlet and Manifold Pressures
Natural Liquid Propane
Inlet Minimum 5.0" w.c. 11.0" w.c.
Inlet Maximum 14.0" w.c. 14.0" w.c.
Manifold Pressure 3.5" w.c. 10.0" w.c.
WARNING
!
Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage. Refer
to this manual for correct installation and operational pro-
cedures. For assistance or additional information consult
a qualied installer, service agency, or the gas supplier.
F.GasSpecications G. Vent Terminations & Clearances
20
19
18
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Vertical Run (in feet)
(Measured from the appliance flue collar to the top of the vent pipe.)
Horizontal Run (in feet)
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
ST134b
Radiance
Horizontal
vent run
6/07
May use up to
three 90° Elbows
One 90°
Elbow
Unacceptable
Venting Conguration
No Restrictor Plate
Required
8


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Vermont Castings Radiance Series at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Vermont Castings Radiance Series in the language / languages: English as an attachment in your email.

The manual is 6.69 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Vermont Castings Radiance Series

Vermont Castings Radiance Series User Manual - French - 46 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info