C = Clearance to permanently closed window12" (305mm) recommended to prevent window
condensation
12" (305mm) recommended to prevent window
condensation
D = Vertical clearance to ventilated sot located
above the terminal within a horizontal distance
of 2' (610 mm) from the center line of the
terminal
18" (458mm)18" (458mm)
E = Clearance to unventilated sot12" (305mm) 12" (305mm)
F = Clearance to outside corner see next pagesee next page
G = Clearance to inside corner see next pagesee next page
H = Clearance to each inside of center line
extended above meter/regulator assembly
3' (91cm) within a height of 15' (5m) above the
meter/regulator assembly
3' (91cm) within a height of 15' (5m) above the
meter/regulator assembly
I = Clearance to service regulator vent outlet3' (91cm)3' (91cm)
J = Clearance to non-mechanical air supply inlet
to building or the combustion air inlet to any
other appliance
6" (15cm) for appliances <10,000 BTU/h (3kW)
12" (30cm) for appliances >10,000 BTU/h (3kW)
and <100,000 BTU/h (30kW)
36" (91cm) for appliances >100,000 BTU/h (30kW)
6" (15cm) for appliances <10,000 BTU/h (3kW)
9" (23cm) for appliances >10,000 BTU/h (3kW) and
<50,000 BTU/h (15kW)
12" (30cm) for appliances >50,000 BTU/h (15kW)
K = Clearance to mechanical air supply inlet6' (1.83m)3' (91cm) above if within 10' (3m) horizontally
L = Clearance above paved sidewalk or paved
driveway located on public property
7' (2.13m)†7' (2.13m)†
M = Clearance under veranda, porch, deck or
balcony
12" (30cm)‡12" (30cm)‡
N = Clearance above a roof shall extend a minimum of 24” (610mm) above the highest point when it passes through the roof surface, and any other obstruction
within a horizontal distance of 18” (450mm).
Figure 2.10 - Vent termination clearances.
NOTE:
1. Local codes or regulations may require dierent clearances.
2. The special venting system used on Direct Vent Fireplaces are
certied as part of the appliance, with clearances tested and
approved by the listing agency.
3. HHT assumes no responsibility for the improper performance
of the appliance when the venting system does not meet these
requirements.
1. In accordance with the current CSA-B149 Installation Codes
2. In accordance with the current ANSI Z223.1/NFPA 54 National
Fuel Gas Codes
† A vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings
and serves both dwellings
‡Only permitted if veranda, porch, deck or balcony is fully open
on a minimum 2 sides beneath the oor.
V
X
X
X
D
E
B
B
B
C
B
M
B
A
J
K
F
L
VENT TERMINATION AIR SUPPLY INLETAREA WHERE TERMINAL IS NOT PERMITTED
Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.
Product:
Forumrules
To achieve meaningful questions, we apply the following rules:
First, read the manual;
Check if your question has been asked previously;
Try to ask your question as clearly as possible;
Did you already try to solve the problem? Please mention this;
Is your problem solved by a visitor then let him/her know in this forum;
To give a response to a question or answer, do not use this form but click on the button 'reply to this question';
Your question will be posted here and emailed to our subscribers. Therefore, avoid filling in personal details.
Register
Register getting emails for Vermont Castings Intrepid - Gas at:
new questions and answers
new manuals
You will receive an email to register for one or both of the options.
Get your user manual by e-mail
Enter your email address to receive the manual of Vermont Castings Intrepid - Gas in the language / languages: English as an attachment in your email.
The manual is 17.23 mb in size.
You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.
The manual is sent by email. Check your email
If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.
The email address you have provided is not correct.
Please check the email address and correct it.
Your question is posted on this page
Would you like to receive an email when new answers and questions are posted? Please enter your email address.