Horizontal Termination
Except for straight-through the wall vent installations. The
vent must rise vertically a minimum of 24” (610 mm) after
the rst elbow directly o󰀨 the back of the unit, before the
next elbow. The horizontal run may extend up to 20’ (6 m)
and include a vertical rise of up to 40’ (12 m), Figure 2.8.
Horizontal termination must also meet the criteria
shown in Figures 2.10 and 2.11.
Approved vent systems must terminate above and
including the heavy line, Figure 2.8.
Two 45° elbows may be substituted for each single 90˚
elbow.
With a rise between 2’ - 5’, one 90° or two 45° elbows
may be used (Excluding the rst elbow directly o󰀨 the
back of the unit.
24" maximum horizontal termination directly o󰀨 back.
Corner installation using 45° elbow, maximum horizontal
after elbow is 24 inches.
F.GasSpecications G. Vent Terminations & Clearances
GasSpecications
Model Fuel
Gas
Control
Max.
Input
BTU/h
Min.
Input
BTU/h
INDVR Series Nat Millivolt 17,000 12,500
INDVR Series LP Millivolt 16,000 12,000
INDVR-IFT Nat IFT 17,000 12,500
INDVR-IFT LP IFT 16,000 12,000
The installation must conform with local codes or, in the
absence of local codes, with the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 - latest edition. (EXCEPTION:
Do not derate this appliance for altitude. Maintain the
manifold pressure at 3.5” w.c. for Natural Gas and 10”
w.c. for Propane.)
High Elevations
Input ratings are shown in BTU per hour and are
certiedwithoutderationforelevationsupto4,500
feet(1,370m)abovesealevel.
For elevations above 4,500 feet (1,370m) in USA,
installationsmustbeinaccordancewiththecurrent
ANSI Z223.1/NFPA 54 and/or local codes having
jurisdiction.
In Canada, please consult provincial and/or local
authorities having jurisdiction for installations at
elevationsabove4,500feet(1,370m).
Air Shutter Setting
Minimum injector air inlet opening
Model Natural Gas LP(Propane)
INDVR Series 1/2 Open 1/2 Open
Gas Inlet and Manifold Pressures
Natural Gas LP(Propane)
Inlet Minimum 5.0" W.C. 11.0" W.C.
Inlet Maximum 14.0" W.C. 14.0" W.C.
Manifold Pressure 3.5" W.C. 10" W.C.
Improper installation, adjustment, alteration, service
or maintenance can cause injury or property damage.
Refer to this manual for correct installation and
operational procedures. For assistance or additional
information consult a qualied installer, service
agency, or the gas supplier.
WARNING
!
Figure 2.8 - Horizontal vent termination window.
20
19
18
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Vertical Run (in feet)
Measured after the first elbow. (Transition elbow)
Horizontal Run (in feet)
21
22
23
24
25
26
27
28
29
30
ST134a
FDV28
Horizontal
vent run
12/3/99 djt
areas modified
1/11/00 djt
May use up to
four 90° Elbows
(Including elbow
directly o󰀨 back of
unit.)
Two 90°
Elbows
Unacceptable
Venting Conguration
Unacceptable
Venting Conguration
8


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Vermont Castings Intrepid - Gas at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Vermont Castings Intrepid - Gas in the language / languages: English as an attachment in your email.

The manual is 17.23 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info