Wiring diagram 4
L and N terminals are connected to live and neutral respectively. LT terminal is connected to live through the external
momentary switch that is activated by opening a door. The fan is in standby mode and does not run. As 24 HOURS Mode is
activated the fan runs permanently at low speed to ensure minimum round-the-clock ventilation. As the external momentary
switch is closed the fan switches to SILENT mode for the period adjusted in the off-delay timer. After that the fan reverts to
standby mode. As motion sensor is activated (for iFAN Move only) the fan switches to SILENT mode. After no motion is
detected the fan reverts to standby mode. As humidity level increases the fan switches to MAX mode (by default) or to
SILENT mode. After humidity level drops the fan reverts to standby mode.
Standby mode
(fan does not run)
or
24 Hours mode
3
(Fan operates at 40-33 m /h)
Humidity
change
Motion sensor
is activated
MAX (SILENT)
mode is activated
Fan operation in
Silent mode
Humidity
stabilization
Motion
if off
Signal to LI terminal
(light is on)
Humidity extraction
timer starts
(30-45-60 min)
Turn-off delay
timer starts
(5-15-30 min)
External switch
is activated
Turn-on delay
timer starts
(0-2-5 min)
Turn-on delay
timer starts
(0-2-5 min)
Signal to LI terminal
(light is off)
LILI
LTLT
LL
NN
SkSk
NN
LL
11


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for VENTS iFan Intelligente ventilator at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of VENTS iFan Intelligente ventilator in the language / languages: English as an attachment in your email.

The manual is 11,24 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info