Operating and display functions 8
0020237057_00 Installation instructions 17
8.7.7 Setting the target return temperature for the
"increase in return flow" circuit type
Menu Installer level System configuration [HEAT-
ING1 ----] Target return temp.
You can use this function to set the target return temper-
ature for the "increase in return flow" circuit type.
8.7.8 Setting the minimum cooling flow target
value
Menu Installer level System configuration [HEAT-
ING1 ----] Min. cool. fl. tgt temp.
If a heat pump is connected and the Cooling possible
function is activated for the heating circuit, you can set
the minimum target flow value for the Cooling possible
mode.
The controller regulates the heating circuit at the minimum
cooling target flow value, even if the operator has set a lower
desired temperature for cooling.
8.7.9 Reading the current temperature
Menu Installer level System configuration [HEAT-
ING1 ----] Current temperature
You can use this function to read the current temperature
of the heating circuit.
8.7.10 Setting the excess temperature
Menu Installer level System configuration [HEAT-
ING1 ----] Excessive temp.
You can use this function to set the excess temperature.
The excess temperature increases the current set target
temperature of the heating circuit by the value that is set.
On mixer circuits with fixed mixing, this function means that
the set target temperature can be reached in pre-heat mode,
even though the temperature of the mixer circuit drops sub-
stantially.
The function also allows for an optimal control range for op-
erating the mixer valve. Stable operation is only possible if
the mixer valve only rarely has to move to the limit stop. This
ensures improved quality of control.
8.7.11 Setting the temperature threshold for
deactivating the heating circuit
Menu Installer level System configuration [HEAT-
ING1 ----] Max limit outs.temp.
You can use this function to set the temperature
threshold. If the outside temperature is greater than the
switch-off threshold set, the controller deactivates heating
mode.
8.7.12 Setting the minimum flow temperature for
the heating circuit
Menu Installer level System configuration [HEAT-
ING1 ----] Minimum temperature
You can use this function to specify a minimum value for
the flow temperature in heating mode for each heating
circuit; the control system will not fall below this value.
The controller compares the calculated flow temperature
with the value set for the minimum temperature and, if
there is a difference, adjusts this to the higher value.
8.7.13 Setting the maximum flow temperature for
the heating circuit
Menu Installer level System configuration [HEAT-
ING1 ----] Maximum temperature
You can use this function to specify a maximum value for
the flow temperature in heating mode for each heating
circuit; the control system will not exceed this value. The
controller compares the calculated flow temperature with
the value set for the maximum temperature and, if there
is a difference, adjusts to the lower value.
8.7.14 Specifying controller behaviour outside
time periods
Menu Installer level System configuration [HEAT-
ING1 ----] Auto Off mode
This function enables you to specify, for each heating
circuit separately, the controller functions in automatic
mode outside active time periods. Default setting: Eco
You can select from two controller behaviours, which you
can adapt further by using the room temperature control.
If you have set the Thermost. value in the Room temp.
mod. function, the Auto Off mode function is ineffective.
The controller always brings the target room temperature to
5 °C.
Eco: The operating mode Auto Off mode, Auto (outside
of the time period) and off are switched off. If a mixer cir-
cuit is connected, the heating pump is switched off and
the heating circuit mixer is closed. The outside temper-
ature is monitored. If the outside temperature falls be-
low 4 °C, the controller switches the heating function on
after the end of the frost protection delay time. The heat-
ing pump is activated. If a mixer circuit is connected, the
heating pump and the heating circuit mixer are activated.
The controller regulates the target room temperature at
the set temperature Set-back. Despite the heating func-
tion being switched on, the heat generator is only active
on demand. The heating function remains active until the
outside temperature rises above 4 °C, after which the
controller switches the heating function off again, but the
outside temperature monitoring remains active.
Set-back: The heating function is switched on and the
target room temperature is set to and maintained at the
set Set-back temperature.
8.7.15 Setting the heating curve
Menu Installer level System configuration [HEAT-
ING1 ----] Heating curve
If the heating curve setting is not sufficient to control the
living room climate according to the operator's wishes,
you can adapt the heating curve setting made during
installation.
If you activate the Adaptive heat. curve function, you must
always adjust the value for the heating curve to the heating
surface design.
17


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Vaillant VRC 700F-4 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Vaillant VRC 700F-4 in the language / languages: English as an attachment in your email.

The manual is 1,3 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info