8 System diagram 0020181028
20 System diagram book multiMATIC 0020200783_02
8 System diagram 0020181028
8.1 System diagram limitation
An external expansion vessel must be included in the
designs for the cylinder charging circuit for boilers that do not
have an integrated diaphragm expansion tank.
The cylinder temperature limiter, which serves to pre-empt
overheating, must be installed in a suitable location in order
to avoid cylinder temperatures above 100 °C.
8.2 Terminal assignment
8.2.1 VR 70 expansion module terminal
assignment
R1/S7: Solar pump
R2: Legionella protection pump
R3/4: Circulation pump
S1: Cylinder temperature sensor
S2: Bottom cylinder temperature sensor (domestic hot water
cylinder)
S5: Collector temperature sensor
S6: Solar yield sensor
8.3 Required settings in the controller
System diagram: 1
Config.: VR70 addr. 1: 6
MA VR70, addr. 1: Circ. pump