602543
49
Zoom out
Zoom in
Previous page
1/52
Next page
Appendix
0020147164_04 aroTHERM Installation instructions 49
Code Meaning Cause
F.537 High-pressure switch open Coolant volume too high or too low
Vacuum insufficient (10 mbar)
Incondensable particle in the coolant circuit
Pressure switch or electrical connection faulty
Premature expansion in the liquid area of the coolant circuit (loss
of charge)
Flow quantity too high (see defined maximum flow rate)
Flow rate monitor faulty
Insufficient heat transfer in the heat exchanger
F.539 Coolant pressure too low Coolant quantity too low
Air flow too low
No thawing
The resistance heating in the condensate receiver is faulty.
4-way valve faulty
Electronic expansion valve motor faulty, or connection faulty
F.546 Sensor fault: High pressure Faulty cabling
F.554 Coolant pressure not in operating range Coolant volume too high or too low
Incondensable particle in the coolant circuit
Electronic expansion valve faulty
Premature expansion in the liquid area of the coolant circuit (loss
of charge)
Flow quantity too high (see defined maximum flow rate)
Insufficient heat exchange in the plate heat exchanger or the
ribbed pipe heat exchanger
4-way valve faulty
F.582 EEV fault Cable insulation faulty
Connection broken
F.585
Sensor fault: Temp. building circuit EEV
2)
Sensor is faulty or incorrectly connected to the main PCB
F.685 Communication fault: eBUS The product is not connected to the controller
Polarity inverted
F.750 Connection fault: Compressor Cable insulation faulty
Connection broken
F.751 Compressor: Overcurrent fault The product's voltage supply is too low
The ribbed pipe heat exchanger or heat exchanger is dirty
F.752 Fault: Inverter Inverter box damaged
The cooler inverter box is blocked.
Faulty voltage supply
The "Max. duration power supply cut-off" parameter has been
set poorly (see the "Heat pump setting parameters" section in
the appendix).
F.753 Connection fault: Inverter not recognised The connection between the main PCB and the inverter box is
damaged or broken.
The inverter box is not switched on.
The "Max. duration power supply cut-off" parameter has been
set incorrectly (see the "Heat pump setting parameters" section
in the appendix).
F.754 Fault: Fan unit The connection between the main PCB and the fan PCB is dam-
aged or broken.
The fan PCB is faulty
F.755 Fault: 4-way valve position incorrect Mechanical or electrical problem. Move the 4-way valve away from
the controller. When moving it, check that the coil voltage is correct.
F.774 Sensor fault: Air inlet temperature The temperature sensor is faulty or incorrectly connected to the
main PCB.
F.1288 Fault: SP1 cylinder temperature sensor Sensor is faulty or has not been correctly connected to the VWZ AI
heat pump control module.
Connection fault: Accessory modules Fault in the VWZ AI heat pump control module (the connection
between the display and the main PCB is faulty).
1) Sensor on the evaporator
2) Sensor on the condenser
49


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Vaillant aroTHERM VWL 155-2 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Vaillant aroTHERM VWL 155-2 in the language / languages: English as an attachment in your email.

The manual is 3,09 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Vaillant aroTHERM VWL 155-2

Vaillant aroTHERM VWL 155-2 User Manual - German - 24 pages

Vaillant aroTHERM VWL 155-2 User Manual - Dutch - 20 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info