602543
21
Zoom out
Zoom in
Previous page
1/52
Next page
For the competent person
Installation instructions
aroTHERM
VWL 55/2 A 230 V; VWL 85/2 A 230 V; VWL
115/2 A 230 V; VWL 155/2 A 230 V
UK
Installation instructions
Publisher/manufacturer
Vaillant GmbH
Berghauser Str. 40 D-42859 Remscheid
Telefon 02191180 Telefax 021911828 10
info@vaillant.de www.vaillant.de
Contents
2 Installation instructions aroTHERM 0020147164_04
Contents
1 Safety .................................................................... 3
1.1 Action-related warnings ......................................... 3
1.2 Required personnel qualifications ......................... 3
1.3 General safety information .................................... 3
1.4 Regulations (directives, laws, standards) .............. 4
1.5 CE label ................................................................. 4
1.6 Approvals............................................................... 5
1.7 Local regulations.................................................... 5
1.8 Regulations............................................................ 5
1.9 Other regulations ................................................... 5
1.10 Intended use.......................................................... 6
2 Notes on the documentation .............................. 7
2.1 Observing other applicable documents ................. 7
2.2 Storing documents................................................. 7
2.3 Applicability of the instructions .............................. 7
3 System overview.................................................. 7
3.1 Safety devices ....................................................... 7
3.2 Design of the heat pump system........................... 7
3.3 Functionality........................................................... 7
3.4 System diagram (VWL 55/2 A 230 V).................... 8
3.5 System diagram (VWL 85/2 A 230 V, VWL
115/2 A 230 V, VWL 155/2 A 230 V)..................... 8
4 Overview of the equipment................................. 9
4.1 Type designation and serial number ..................... 9
4.2 Information on the identification plate.................... 9
5 Assembly and installation .................................. 9
5.1 Preparing for fitting and installation ....................... 9
5.2 Carrying out the installation ................................. 14
5.3 Hydraulics installation.......................................... 14
5.4 Carrying out the electrical installation.................. 17
5.5 Connection diagrams........................................... 19
6 Start-up ............................................................... 21
6.1 Run the start-up................................................... 21
6.2 Heat pump operating concept ............................. 21
6.3 Running through the installation assistant........... 21
6.4 Calling up Live Monitor (checking status
codes).................................................................. 21
6.5 Calling up statistics.............................................. 21
6.6 Filling the heating circuit ...................................... 21
6.7 Preparing the heating water ................................ 22
6.8 Filling the heating installation .............................. 23
6.9 Activating the heat pump ..................................... 23
6.10 Checking the product's operation ........................ 23
6.11 Operating noises.................................................. 23
6.12 Adjusting the heating circuit................................. 23
6.13 Installing the side cladding .................................. 25
6.14 Instructing the operator........................................ 25
7 Maintenance....................................................... 25
7.1 Observing maintenance intervals ........................ 25
7.2 Preparing for maintenance .................................. 25
7.3 Instructions before carrying out maintenance
work ..................................................................... 25
7.4 Yearly maintenance............................................. 25
7.5 Cleaning the product............................................ 26
7.6 Draining the product ............................................ 26
7.7 Checking the product's status codes................... 27
7.8 Checking the electrical installation ...................... 27
7.9 Start-up following maintenance ........................... 27
8 Troubleshooting ................................................ 27
8.1 Troubleshooting................................................... 27
8.2 Fault codes .......................................................... 27
8.3 Carrying out the actuator test .............................. 27
9 Decommissioning.............................................. 28
9.1 Temporary decommissioning .............................. 28
9.2 Permanently decommissioning............................ 28
10 Vaillant customer service ................................. 28
10.1 Customer service................................................. 28
11 Disposal.............................................................. 28
11.1 Recycling and disposal........................................ 28
11.2 Arranging disposal of coolant .............................. 28
Appendix ............................................................................ 29
A Overview of accessories................................... 29
B System diagrams............................................... 30
B.1 System diagram 8 E ............................................ 30
B.2 System diagram 8 F............................................. 32
B.3 System diagram 10 B .......................................... 34
B.4 System diagram 12 A .......................................... 36
C Wiring diagrams................................................. 37
C.1 Wiring diagram 8 E .............................................. 37
C.2 Wiring diagram 8 F .............................................. 38
C.3 Wiring diagram 10 B ............................................ 39
C.4 Wiring diagram 12 A ............................................ 40
D Heat pump schematic........................................ 41
D.1 Heat pump schematic drawing (VWL 55/2 A
230 V) .................................................................. 41
D.2 Heat pump schematic drawing (VWL 85/2 A
230 V) .................................................................. 42
D.3 Heat pump schematic drawing (VWL 115/2 A
230 V) .................................................................. 43
D.4 Heat pump schematic drawing (VWL 155/2 A
230 V) .................................................................. 44
E Heat pump setting parameters......................... 44
F Technical data.................................................... 45
G Overview of fault codes .................................... 48
Index ................................................................................... 51
Safety 1
0020147164_04 aroTHERM Installation instructions 3
1 Safety
1.1 Action-related warnings
Classification of action-related warnings
The action-related warnings are classified in
accordance with the severity of the possible
danger using the following warning signs and
signal words:
Warning symbols and signal words
Danger!
Imminent danger to life or risk of
severe personal injury
Danger!
Risk of death from electric shock
Warning.
Risk of minor personal injury
Caution.
Risk of material or environmental
damage
1.2 Required personnel qualifications
Improper work carried out on the product
may cause material damage to the complete
installation and, as a consequence, may even
cause personal injury.
You should therefore only work on the
product if you are an authorised competent
person.
1.3 General safety information
1.3.1 Danger caused by improper
operation
Improper operation may present a danger to
you and others, and cause material damage.
Carefully read the enclosed instructions
and all other applicable documents, par-
ticularly the "Safety" section and the warn-
ings.
1.3.2 Risk of death from electric shock
There is a risk of death from electric shock if
you touch live components.
Before commencing work on the product:
Disconnect the product from the power
supply (electrical partition with a contact
opening of at least 3 mm, e.g. fuse or
power switch).
Secure against being switched back on
again.
Wait for at least 3 minutes until the con-
densers have discharged.
Check that there is no voltage.
Cover or insulate adjacent live parts.
1.3.3 Risk of death due to lack of safety
devices
A lack of safety devices (e.g. expansion re-
lief valve, expansion vessel) may lead to po-
tentially fatal scalding and other injuries, e.g.
due to explosions. The schematic drawings
included in this document do not show all
safety devices required for correct installa-
tion.
Install the necessary safety devices in the
system.
Inform the operator about the function and
position of the safety devices.
Observe the applicable national and inter-
national laws, standards and guidelines.
1.3.4 Risk of being scalded by hot
drinking water
There is a risk of scalding at the hot water
draw-off points if the hot water temperatures
are greater than 50 °C. Young children and
elderly persons are particularly at risk, even
at lower temperatures.
Select the temperature so that nobody is at
risk.
1.3.5 Risk of injury or material damage
due to incorrect handling of the
product
Using the fins on the front side of the product
as conductors may lead to injuries (due to
falling) or to material damage.
Do not use the fins as conductors.
1.3.6 Risk of material damage due to
additional elements in the heating
water
Unsuitable frost and corrosion protection
agents may damage seals and other com-
ponents of the heating circuit and may there-
fore also lead to leaks in the water outlet.
Only add approved frost and corrosion
protection agents to the heating water.
1 Safety
4 Installation instructions aroTHERM 0020147164_04
1.3.7 Risk of material damage caused by
using an unsuitable tool
Use the correct tool to tighten or loosen
screw connections.
1.3.8 Avoid environmental damage
caused by escaping coolant
The heat pump contains R410A coolant.
The coolant must not be allowed to escape
into the atmosphere. R410A is a fluorinated
greenhouse gas covered by the Kyoto Pro-
tocol, with a GWP of 1725 (GWP = Global
Warming Potential). If it escapes into the at-
mosphere, its impact is 1725 times stronger
than the natural greenhouse gas CO
2
.
Before the heat pump is disposed of, the
coolant it contains must be completely
drained into a suitable vessel so that it
can then be recycled or disposed of in
accordance with the regulations.
Ensure that only officially certified com-
petent persons with appropriate protective
equipment carry out maintenance work on
the coolant circuit or access it.
Arrange for the coolant contained in the
product to be recycled or disposed of by
accredited specialists in accordance with
regulations.
Only use coolant R410A.
Only use a suitable R410A tool for the
filling, pressure measurement, vacuum
generation and discharge.
Solder the lines using shielding gas. Check
the lines for leak-tightness using nitrogen.
In the event of a repair or maintenance
work, fill the coolant circuit with liquid
coolant.
If the coolant circuit is not leak-tight, check
which component must be repaired or re-
placed.
Lower the negative pressure in the coolant
circuit to max. 10 mbar (1000 Pa).
When filling the coolant circuit, observe the
values in the "Technical data" section.
1.4 Regulations (directives, laws,
standards)
As part of the installation, commissioning and
operation of the heat pump and the DHW
storage you must take into account the cur-
rent versions of the following regulations or
standards, along with any local directives or
guidelines that may apply.
Electricity at work act.
Health and safety at work act.
Relevant Utility supplier’s regulations.
Water regulations and by-laws.
Environment agency and local council re-
quirements regarding bore holes, water
courses, or noise levels.
Gas safety installation and use regulations
concerning any associated gas fired heat
source used within the heating system.
Building regulations part “L&P” and direct-
ives concerning energy saving.
Building regulations such as G3 covering
Hygiene and L8 Legieonella.
COSHH regulations.
Other relevant bodies such as HETAS and
OFTEC.
BS7671 requirements for electrical installa-
tions.
All other national and regional relevant regu-
lations for the installation of heat pumps and
heating systems must be followed.
1.5 CE label
The CE label shows that the products comply
with the basic requirements of the applicable
directives as stated on the identification plate.
The declaration of conformity can be viewed
at the manufacturer's site.
Safety 1
0020147164_04 aroTHERM Installation instructions 5
1.6 Approvals
This product has been fully tested in accord-
ance with:
BS EN 14511:2011
1.7 Local regulations
Benchmark places responsibilities on both
manufacturers and installers. The purpose is
to ensure that customers are provided with
the correct equipment for their needs, that it
is installed, commissioned and serviced in
accordance with the manufacturer’s instruc-
tions by a competent person approved at the
time by the Health and Safety Executive and
that it meets the requirements of the appro-
priate Building Regulations. The Benchmark
Checklist can be used to demonstrate compli-
ance with Building Regulations and should be
provided to the customer for future reference.
Installers are required to carry out installation,
commissioning and servicing work in accord-
ance with the Benchmark Code of Practice
which is available from the Heating and Hot-
water Industry Council who manage and pro-
mote the Scheme.
Visit www.centralheating.co.uk for more in-
formation.
Planning consent and Building works notific-
ation should be submitted either to Building
Control or to a Competent Person Provider.
1.8 Regulations
1.8.1 Statutory requirements
Where no British Standards exists, materials
and equipment should be fi t for their purpose
and of suitable quality and workmanship.
The installation of this appliance must be car-
ried out by a competent person in accord-
ance the rules in force in the countries of des-
tination.
Manufacturer’s instructions must not be taken
as overriding statutory requirements.
1.8.2 Standards
On installing and commissioning the appli-
ance you must adhere to the technical rules,
standards and provisions in eff ect at the
time.
1.8.3 Reminder of existing regulatory acts
EC regulation No. 20372000 from the 29th
of June 2000 This European regulation re-
peals regulation No. 3093/94 and presents
the elimination schedules of CFC and
HCFC. It also deals with the collection of
refrigerants, system leaks, particularly sys-
tems containing more than 3 kg of CFC
or HCFC, as well as the minimum level of
qualifi cation required by the technicians.
EC regulation No. 0842/2006 from the 17th
of May 2006 regarding the containment,
use, collection and disposal of the fl uorin-
ated greenhouse gases, the labelling and
elimination of the products and equipment
containing these gases, the restriction of
use and banning of certain products from
the market, as well as the training and cer-
tifi cation of personnel and companies op-
erating in the activities targeted by this reg-
ulation: refrigeration, air-conditioning, heat
pumps and fi re protection systems con-
taining greenhouse gases.
1.9 Other regulations
1.9.1 Control of Substances Hazardous to
Health
Under Section 6 of The Health and Safety at
Work Act 1974, we are required to provide in-
formation on substances hazardous to health.
The adhesives and sealants used in this ap-
pliance are cured and give no known hazard
in this state.
The refrigerant used in this appliance is
R410a the use of which is strictly controlled
by F Gas regulation EN842/2006.
1 Safety
6 Installation instructions aroTHERM 0020147164_04
1.10 Intended use
There is a risk of injury or death to the user or
others, or of damage to the product and other
property in the event of improper use or use
for which it is not intended.
The heat pump is an air/water monoblock
system and uses the energy from the outside
air to supply heat to the building.
The heat pumps are intended exclusively for
domestic use as heat generators for closed
heating and hot water central heating sys-
tems and for hot water generation.
Intended use includes the following:
observance of accompanying operating,
installation and servicing instructions for
the product and any other system compon-
ents
installing and fitting the product in accord-
ance with the product and system approval
compliance with all inspection and main-
tenance conditions listed in the instruc-
tions.
Any other use that is not specified in these
instructions, or use beyond that specified in
this document, shall be considered improper
use. Any direct commercial or industrial use
is also deemed to be improper.
Caution.
Improper use of any kind is prohibited.
Notes on the documentation 2
0020147164_04 aroTHERM Installation instructions 7
2 Notes on the documentation
2.1 Observing other applicable documents
You must observe all the operating and installation in-
structions included with the system components.
2.2 Storing documents
Pass these instructions and all other applicable docu-
ments on to the system operator.
2.3 Applicability of the instructions
These instructions apply to units with the following type des-
ignations and article numbers only:
Type designation Art. no.
aroTHERM VWL 55/2 A 230 V 0010014566
aroTHERM VWL 85/2 A 230 V 0010011971
aroTHERM VWL 115/2 A 230 V 0010011972
aroTHERM VWL 155/2 A 230 V 0010014567
The seventh to sixteenth digits of the serial number on the
identification plate form the article number.
3 System overview
3.1 Safety devices
The product can work at the following outside temperat-
ures:
VWL 55/2 A 230 V VWL 85/2 A 230 V
VWL 115/2 A 230 V
VWL 155/2 A 230 V
Heating mode 15 … 28 20 … 28
Cylinder charging
mode
15 … 46 20 … 46
If the product's coolant circuit pressure exceeds the max-
imum pressure of 4.15 MPa (41.5 bar), the high-pres-
sure pressure switch switches the product off. Follow-
ing a waiting period, the product attempts to start once
more. After three failed start attempts in succession, a
fault message is displayed.
If the product is switched off, the crankcase housing
heating is switched on when the compressor outlet tem-
perature reaches 7 °C in order to prevent possible dam-
age caused by switching it back on.
If the compressor inlet temperature and the compressor
outlet temperature are below 1 °C, the compressor does
not start up.
A temperature sensor on the compressor outlet limits the
product's operation if the measured temperature exceeds
the maximum permissible temperature. The maximum
permissible temperature depends on the evaporation and
condensation temperature.
The product measures the flow rate of the connected
heating circuit when starting up the product.
If the heating circuit temperature falls below 3 °C, the
product's frost protection function is automatically ac-
tivated as the heating pump is started. In addition, frost
protection agent should be added to the heating water as
the heating water temperature may fall below the freez-
ing point in the event of a power cut, which poses a risk
of frost to the heating installation.
Note
Operating the heat pump outside the application
limits results in the heat pump being switched off
by the internal control and safety devices.
3.2 Design of the heat pump system
The heat pump system consists of the following components:
aroTHERM heat pump
VWZ AI heat pump control module
Additional hydraulic components, if required
VRC 470 system controller
The heat pump can be operated by the VWZ AI heat pump
control module. The extended operation of the heat pump is
carried out by the system controller.
3.3 Functionality
The product comprises the following circuits:
The coolant circuit releases heat into the heating circuit
by means of evaporation, compression, condensation
and expansion
The heating circuit
3.3.1 Heating mode
1
2
3
4
5
6
1 Evaporator
2 4-way valve
3 Fan
4 Compressor
5 Electronic expansion valve
6 Plate heat exchanger
3.3.2 Thawing
1
2
3
4
5
6
1 Evaporator 2 4-way valve
3 System overview
8 Installation instructions aroTHERM 0020147164_04
3 Fan
4 Compressor
5 Electronic expansion valve
6 Plate heat exchanger
3.3.3 Application limits
Operation of the pump outside the application limits results in
the heat pump being switched off by the internal control and
safety devices.
3.3.3.1 Application limits in heating mode (VWL
55/2 A 230 V)
60
50
70
40
30
20
10
0
-20 -10 0 10 20 30 40 50
[-15;22]
[-15;45]
[46;22]
[46;58]
[35;60]
[28;60]
[2;60]
[-10;55]
1
2
[28;22]
[35;22]
A
B
1 Heating mode application
limits
2 Hot water generation
application limits
A Water temperature
B Air temperature
3.3.3.2 Application limits in heating mode (VWL
85/2 A 230 V, VWL 115/2 A 230 V, VWL 155/2
A 230 V)
60
50
70
40
30
20
10
0
-20 -10 0 10 20 30 40 50
[-20;22]
[-20;43]
[46;22]
[46;58]
[35;63]
[28;63]
[2;63]
[-10;55]
1
2
[28;22]
[35;22]
A
B
1 Heating mode application
limits
2 Hot water generation
application limits
A Water temperature
B Air temperature
3.4 System diagram (VWL 55/2 A 230 V)
e
1 3 12161719
24
1521
14
11
4
23
20
2
22
5 13 8 9
6
7
10
A
B
18
1 Fan
2 Air inlet temperature
sensor
3 Ribbed pipe heat ex-
changer
4 Temperature sensor of
the ribbed pipe heat ex-
changer
5 4-way valve
6 Return heating circuit
temperature sensor
7 High-efficiency pump with
flow sensor
8 Purging valve
9 Flow heating circuit tem-
perature sensor
10 Drain valve
11 Plate heat exchanger
12 Temperature sensor after
the plate heat exchanger
13 Service valve for the high-
pressure range of the
coolant circuit
14 High-pressure pressure
switch in the coolant cir-
cuit
15 High-pressure sensor in
the coolant circuit
16 Compressor outlet temper-
ature sensor
17 Rotary piston compressor
18 Filter
19 Liquid separator
20 Electronic expansion valve
21 Compressor inlet temper-
ature sensor
22 Service valve for the low-
pressure range of the
coolant circuit
23 Filter
24 Fluid collector
A Heating return
B Heating flow
3.5 System diagram (VWL 85/2 A 230 V, VWL
115/2 A 230 V, VWL 155/2 A 230 V)
e
1 3 12161719
25
23
1521
14
11
4
24
20
2
22
5 13 8 9
6
7
10
A
B
18
1 Fan 2 Air inlet temperature
sensor
Overview of the equipment 4
0020147164_04 aroTHERM Installation instructions 9
3 Ribbed pipe heat ex-
changer
4 Temperature sensor of
the ribbed pipe heat ex-
changer
5 4-way valve
6 Return heating circuit
temperature sensor
7 High-efficiency pump with
flow sensor
8 Purging valve
9 Flow heating circuit tem-
perature sensor
10 Drain valve
11 Plate heat exchanger
12 Temperature sensor after
the plate heat exchanger
13 Service valve for the high-
pressure range of the
coolant circuit
14 High-pressure pressure
switch in the coolant cir-
cuit
15 High-pressure sensor in
the coolant circuit
16 Compressor outlet temper-
ature sensor
17 Rotary piston compressor
18 Filter
19 Liquid separator
20 Electronic expansion valve
21 Compressor inlet temper-
ature sensor
22 Service valve for the low-
pressure range of the
coolant circuit
23 Flow rate limiter (cooling
mode) on the VWL 85/2 A
230 V only
24 Filter
25 Gas buffer
A Heating return
B Heating flow
4 Overview of the equipment
4.1 Type designation and serial number
1
1
The type designation and serial number are on the identifica-
tion plate (1).
4.2 Information on the identification plate
Information on the identi-
fication plate
Meaning
Serial no. Unique unit identification number
P max Maximum rated power
I Max. operating current
I max Maximum start-up current
R410A Coolant type and fill quantity
PS
R
_LP
PS
R
_HP
Min. and max. operating pres-
sure in the coolant circuit
Information on the identi-
fication plate
Meaning
PS
H
min
PS
H
max
Minimum and maximum operat-
ing pressure in the heating circuit
COP (Ax/Wxx) Output figure (coefficient of
performance) at an air inlet
temperature of xx °C and a
heating flow temperature of
xx °C
(Ax/Wxx)
Heating output at an air inlet
temperature of xx °C and a
heating flow temperature of
xx °C
Volt Compressor, pump and control-
ler mains voltage
Hz Power frequency
IP Protection class
5 Assembly and installation
5.1 Preparing for fitting and installation
5.1.1 Delivery, transport and positioning
5.1.1.1 Transporting the product
Warning.
Risk of injury from lifting a heavy weight.
Lifting weights that are too heavy may cause
injury to the spine, for example.
5 Assembly and installation
10 Installation instructions aroTHERM 0020147164_04
When transporting the product, two
people should lift it.
Observe the product weight stated in the
technical data.
When transporting heavy loads, observe
the applicable directives and regulations.
Caution.
Risk of material damage due to incorrect
transportation.
Regardless of the mode of transport, the heat
pump must never be tilted by more than 45°.
Otherwise, this may lead to malfunctions in
the coolant circuit during subsequent opera-
tion. In the worst case scenario, this may lead
to a fault in the whole system.
During transport, do not tilt the heat pump
by any more than the maximum angle of
45°.
1. Use the transportation belt to carry the product to the
final installation site.
2. Only lift the product from the back and side where the
hydraulic connections are located.
3. When transporting the product using a hand truck, se-
cure the product using a belt.
4. In order to avoid scratches and damage, protect the
sides of the product that come into contact with the
hand truck.
5.1.1.2 Unpacking the product
13mm
1
2
3
4
B
A
D
E
C
1. Remove the accessory (2).
2. Remove the documentation supplied (1).
3. Remove the transport belt (4).
4. Carefully remove the packaging and padding without
damaging the product (3).
5. Remove the screws from the pallet at the front and rear
of the product.
5.1.1.3 Checking the scope of delivery
Check the contents of the packaging units
Quant-
ity
Description
1 Condensate discharge
1 Bag with seals
4 Vibration-isolating feet
1 Purge hose
5.1.2 Complying with clearances and installation
clearances
5.1.2.1 Unit dimensions and connection
dimensions
120
120
74 0
980
408
840*
386
VWL 55/2 A 230 V
386
11
* Size increases by 45 mm
when using the vibration
dampers supplied.
Assembly and installation 5
0020147164_04 aroTHERM Installation instructions 11
162
162
778
1103
463
975*
437
VWL 85/2 A 230V
VWL 115/2 A 230V
437
11
* Size increases by 45 mm
when using the vibration
dampers supplied.
162
162
778
1103
463
1380*
437
VWL 155/2 A 230V
437
11
* Size increases by 45 mm
when using the vibration
dampers supplied.
5 Assembly and installation
12 Installation instructions aroTHERM 0020147164_04
5.1.2.2 Installation clearance
C
B
D
A
A
E
0.5 m
Clearance For heating mode
A > 250 mm
B > 1000 mm
C > 120 mm*
D > 600 mm
E > 300 mm
*Caution: If the minimum clearances are not maintained, the
output of the product may be affected.
To guarantee sufficient air flow and to facilitate mainten-
ance work, observe the minimum clearances that are
specified above.
Ensure that there is sufficient room to install the hydraulic
lines.
If the product is to be installed in areas where heavy
snow falls, ensure that the snow does not accumulate
around the product and that the minimum clearances
specified above are observed. If you cannot ensure this,
install an additional heat generator in the heating circuit.
An elevating socket is available as an accessory. In order
to adapt the product to higher levels of snow, only use
the Vaillant elevating socket.
5.1.2.3 Selecting the installation site
Observe all valid regulations.
Install the product outside the building.
Do not install the product:
Near a heat source,
Near flammable materials,
Near ventilation openings for adjacent buildings,
Under deciduous trees.
Note the following points when installing the product:
Prevailing winds,
The visual impression on the environment
Avoid places where strong winds blow on the product's
air outlet.
Point the fan away from nearby windows. Install noise
protection if necessary.
Install the product on one of the following supports:
Concrete slab,
Steel T-beam,
Concrete block,
Elevating socket (Vaillant accessory),
Wall bracket (permitted Vaillant accessory for VWL
55/2 A 230 V, VWL 85/2 A 230 V and VWL 115/2 A
230 V or VWL 115/2 A 400 V).
Do not expose the product to dusty or corrosive air (e.g.
near unsecured streets).
Do not install the product near ventilation shafts.
Prepare the routing for the electrical lines.
Assembly and installation 5
0020147164_04 aroTHERM Installation instructions 13
dB(A)
dB(A)
Note any noise emissions from the fan and compressor.
5.1.2.4 Installing the heat pump
1. Note the safety information in this manual and in the
operating instructions before installing the product.
2. Install the product on steel beams, concrete blocks or
using a wall holder (accessory).
3. Ensure that no water collects under the product.
4. In order to avoid ice formation, ensure that the ground
in front of the product can absorb water well.
5.1.2.5 Preparing the condensate discharge
>100mm
Danger!
Risk of injury due to frozen condensate.
Frozen condensate on paths may cause falls.
Ensure that condensate does not dis-
charge onto paths and that ice cannot
build up there.
The condensate is discharged centrally underneath the
product.
Prepare the condensate discharge using a drain line or in
a gravel bed.
5 Assembly and installation
14 Installation instructions aroTHERM 0020147164_04
5.2 Carrying out the installation
5.2.1 Removing the side casing
B
A
A
C
1. Remove both screws (A).
2. Pull the side casing downwards and then forwards.
Note
Note that the required tool is not included in
the scope of delivery.
5.2.2 Aligning the product
1. Only use bolts of a specific length.
Maximum length: 8 mm
2. Align the product horizontally so that condensate can
flow.
Note
The product must be installed with the vi-
bration-isolating feet supplied. The product
is lifted by the vibration-isolating feet, which
simplifies the condensate-discharge process
and reduces vibrations.
3. Screw in the vibration-damping feet using the concrete
foundation.
Note
The concrete foundation must not be joined
to the house foundations.
5.3 Hydraulics installation
In heating installations that are equipped primarily with ther-
mostatic or electrically controlled valves, a constant and suf-
ficient flow through the heat pump must be ensured. Irre-
spective of which heating installation is selected, the min-
imum volume of circulating heating water (40% of the nom-
inal flow, see the technical data table) must be guaranteed.
5.3.1 Carrying out the hydraulics installation
Caution.
Risk of damage caused by residue in the
heating flow and return.
Residue from the pipelines, such as welding
beads, scale, hemp, putty, rust and coarse
dirt, may be deposited in the product and
cause malfunctions.
Flush the heating installation thoroughly
before connecting the product in order to
remove any possible residue.
Caution.
Risk of material damage due to corrosion.
If plastic pipes that are not diffusion-tight are
used in the heating circuit, this may lead to
corrosion and deposits in the heating circuit
and in the product.
Do not treat the water with corrosion pro-
tection agents if plastic pipes that are not
diffusion-tight are used.
Danger!
Risk of material damage caused by sol-
dering work.
Carrying out soldering work on lines that
have already been installed may damage the
seals.
Solder the lines before installing the
product.
Assembly and installation 5
0020147164_04 aroTHERM Installation instructions 15
1. Insulate the lines (including those running below
ground) with UV-resistant and high-temperature-res-
istant insulation between the product and the heating
installation.
2. In order to avoid transferring vibrations to the surround-
ing buildings, use flexible connection pipes on the
product that have a length of at least 0.75 m.
3. When the product is not installed at the highest point in
the heating circuit, install additional purging valves in
suitable places.
4. Install the following accessories in the heating return.
Installation without decoupling hydraulic module
Drain cock
Air separator (if required)
Dirt filter
An expansion vessel suitable for the complete hydraulic
installation
Expansion relief valve 0.3 MPa (3 bar)
Pressure gauge (recommended)
Note
If you use glycol, you must collect it at the
expansion relief valve to prevent environ-
mental pollution.
0.75 m min.
1
4
5
6
7
3
2
1 Connection hose in the
heating flow to the building
(on-site)
2 O-ring seal
3 Covering cap
4 Heating flow connection
(diameter 1 1/4") to the
building
5 Heating return connection
(diameter 1 1/4") to the
heat pump
6 Connection hose in the
heating return to the heat
pump (on-site)
7 Insulation (on-site)
5. Remove the covering caps (3) from the product's hy-
draulic connections.
6. Install a dirt filter in the heating circuit return between
two stop valves so that the filter can be cleaned regu-
larly.
7. Install a flexible connection pipe (1) and (6) (to be
provided on-site) with an O-ring and a stop valve to
each of the connections for the heat pump heating flow
and return.
8. Check the connections for tightness.
5.3.2 Installing system diagram 8, variant E
1. Install the system in accordance with system diagram 8,
variant E ( Page 30).
Note
In this system, the circulation pump of the
heat pump functions as a heating pump. It
is also in operation when only the boiler is in
operation.
2. On start-up, set system diagram 8 on the controller.
3. In order to guarantee operation with two heat generat-
ors, install the flow temperature sensor.
4. Connect the eBUS-compatible boiler using a bus
coupler on the eBUS line.
5.3.3 Installing system diagram 8, variant F
1. Install the system in accordance with system diagram 8,
variant F ( Page 30).
2. On start-up, set system diagram 8 on the controller.
3. In order to guarantee a minimum circulation water
volume, install a differential-pressure bypass valve.
4. In order to guarantee the product's underfloor protective
circuit, install a limit thermostat.
5. In order to guarantee the hot water generation using the
heat pump, install a cylinder sensor and a 3-way valve.
5.3.4 Installing system diagram 10, variant B
1. Install the system in accordance with system diagram
10, variant B ( Page 30).
2. On start-up, set system diagram 10 on the controller.
3. In order to guarantee a minimum circulation water
volume, install a differential-pressure bypass valve.
4. In order to guarantee that the unit can be operated with
an auxiliary heating module, install the flow temperature
sensor.
5. In order to guarantee the hot water generation using the
heat pump, install a cylinder temperature sensor and a
3-way valve.
6. In order to guarantee the product's underfloor protective
circuit, install a limit thermostat.
7. Install an auxiliary electric heater on-site.
8. Set the hot water temperature for the pre-heating stage
on the system controller and the desired hot water tem-
perature on the on-site auxiliary heater.
5.3.5 Installing system diagram 12, variant A
1. Install the system in accordance with system diagram
12, variant A ( Page 30).
2. On start-up, set system diagram 12 on the controller.
3. Connect the area valves.
4. In order to guarantee a minimum circulation water
volume, install a differential-pressure bypass valve.
5. In order to guarantee the product's underfloor protective
circuit, install a limit thermostat.
6. In order to guarantee that the unit can be operated with
an auxiliary heating module, install the flow temperature
sensor.
5 Assembly and installation
16 Installation instructions aroTHERM 0020147164_04
7. In order to guarantee the hot water generation using the
heat pump, install a cylinder temperature sensor and a
3-way valve.
5.3.6 Connecting the swimming pool (optional)
Danger!
Risk of material damage due to a direct
connection to a swimming pool.
If the product is directly connected to a swim-
ming pool, damage may be caused by corro-
sion.
Do not connect the heat pump heating
circuit directly to a swimming pool.
If you want to connect a swimming pool to the heating
circuit, note the components (expansion vessels, etc.)
that are required for the installation.
5.3.7 Connecting the condensate drain pipework
Note
Observe all valid national regulations and rules.
B
A
365
Ø25
1
2
3
4
5
1 Condensate drain pipe
2 Adaptor
3 Cable tie
4 Elbow
5 Seal
1. Observe the various installation dimensions for the
products.
Product Dimension Value
VWL 55/2 A 70.0 mm
B 490.0 mm
VWL 85/2
VWL 115/2
VWL 155/2
A 102.5 mm
B 550.0 mm
2. Pull the heating wire in the condensate pan until the
elbow (4).
3. Connect the elbow (4) and adaptor (2) to the seal (5)
and secure them both using a cable tie (3).
4. Connect a condensate drain pipe to the elbow.
5. Install the heating wire in the condensate drain pipe (1)
in order to prevent the condensate from freezing in the
line.
6. Connect the adaptor (2) with the product's floor plate
and secure it with a 1/4 rotation.
Assembly and installation 5
0020147164_04 aroTHERM Installation instructions 17
7. Make sure that the condensate drain pipe ends in a
gravel bed.
Note
The condensate drain pipe must not be
longer than 365 mm, otherwise it may freeze
over.
8. Route the condensate drain pipework with a downward
gradient.
5.4 Carrying out the electrical installation
30 mm max.
1
2
1 Connecting wires 2 Insulation
Danger!
Risk of death from electric shock as a res-
ult of an improper electrical connection!
An improper electrical connection may neg-
atively affect the operational safety of the
product and result in material damage or per-
sonal injury.
The electrical installation must be carried
out by a suitably qualified competent per-
son who is responsible for complying with
the existing standards and directives.
1. Only strip a maximum of 3 cm from the outer sheathing
of the flexible lines.
2. Secure the conductors in the connection terminals.
5.4.1 Establishing the power supply
The external mains connection cable must be earthed and
connected with the correct polarity and in accordance with
the valid regulations.
Check that the mains connection cable is connected cor-
rectly.
The cables that connect the product to the fuse box must:
Be suitable for fixed installation,
Be weatherproof,
Be equipped with a wire cross-section that is necessary
for the product performance.
Connect the product using a fixed connection and a parti-
tion with a contact opening of at least 3 mm (e.g. fuses or
power switches).
In order to meet the overvoltage category II requirements,
further fuse protection may be required.
To meet the overvoltage category III conditions, the parti-
tions must ensure a complete separation of the power sup-
ply.
5.4.2 Standard tariff
5.4.2.1 230 V connection
X4
X9
EBUS
X7
FLOOR H
X2
21
2
1
1 Mains connection terminal
in the product
2 Partition
Caution.
Risk of material damage due to high con-
nected voltage.
At mains voltages greater than 253 V, elec-
tronic components may be damaged.
Ensure that the rated voltage of the mains
is 230 V.
Connect the mains connection cable to the product's
power supply connection.
VWL
55/2
230 V
VWL
85/2
230 V
VWL
115/2
230 V
VWL
155/2
230 V
Power supply 1/N/PE
230 V
50 Hz
1/N/PE
230 V
50 Hz
1/N/PE
230 V
50 Hz
1/N/PE
230 V
50 Hz
Fuse 16 A -
type C
or D
16 A -
type C
or D
20 A -
type C
or D
20 A -
type C
or D
Recommended
cable dimension
3G x
2.5 mm²
3G x
2.5 mm²
3G x
2.5 mm²
3G x
2.5 mm²
To ensure that people are safe, install a separate 30 mA
residual-current-operated circuit-breaker for the heat
pump.
Guide the mains connection cable through the product's
cable duct (PEG screwed connection).
5 Assembly and installation
18 Installation instructions aroTHERM 0020147164_04
5.4.3 Laying the 24 V cabling
PE N L
230 V~
+ -
Bus VF1 SP1
PE N L
230 V~
PE N L
MA1
PE N L
MA2
PE N
Auf
Zu
UV1
PE N 1 2
ZH
2 1 2 1
X4
X9
EBUS
X7
FLOOR H
3
1
2
1 eBUS connection in the
heat pump (observe the
polarity)
2 Limit thermostat connec-
tion (underfloor protective
circuit)
3 eBUS connection in the
VWZ AI heat pump control
module or in the VWZ
MEH 61
1. Feed the cable through the cable duct.
VWL 55/2 A 230 V
VWL 85/2 A 230 V
VWL 115/2 A 230 V
VWL 155/2 A 230 V
Recommended eBUS cable dimen-
sion
2 x 0.75 mm²
Recommended cable dimension for
eBUS + limit thermostat
4 x 0.75 mm²
2. Connect the eBUS cable to the system controller.
3. If you install a limit thermostat (e.g. 50 °C) in the heat-
ing circuit flow, remove the bridge from terminal (2) and
connect the limit thermostat to this terminal.
5.4.4 Installing the cable duct
Caution.
Risk of malfunction due to incorrect rout-
ing of the supply lines.
If you route the supply lines for the power
supply and the eBUS line through the same
cable duct, the signal will be disrupted.
Route the supply lines for the power sup-
ply and the eBUS line through various
cable ducts in the product.
123456789101112131415
16
1
2
3
4
ØA
ØA
1
2
1 eBUS line and limit ther-
mostat line cable duct
2 Power supply cable duct
1. Measure the diameter of the cable.
2. Drill a hole the same size as the cable diameter in the
cable duct.
3. Route the cable through the cable duct.
4. Tighten the cable duct with two open-end spanners.
Assembly and installation 5
0020147164_04 aroTHERM Installation instructions 19
5.5 Connection diagrams
5.5.1 Connection diagram (VWL 55/2 A 230 V, VWL 85/2 A 230 V, VWL 115/2 A 230 V, VWL 155/2 A
230 V)
X8
X1
X6
X4
X7
X60DA
X14
X700
X16
X11
F1
X1
X15
X13
X26
X23
X21
X22
X30 X25
X24
X25
X5
X10CA
X9
X2
RL1
X3
15
16
17
12
18
19
20
21
22
23
24
25
11
9
8
7
6
5
4
3
1
2
13
14
10
1 Temperature sensor of the ribbed pipe heat exchanger
2 Temperature sensor after the plate heat exchanger
3 Coolant circuit pressure switch
4 Compressor inlet temperature sensor
5 Compressor outlet temperature sensor
6 Coolant circuit temperature sensor
7 Heat pump heating flow temperature sensor
8 Heat pump heating return temperature sensor
5 Assembly and installation
20 Installation instructions aroTHERM 0020147164_04
9 Air inlet temperature sensor
10 Electronic expansion valve
11 Main PCB
12 Coding resistance
13 Diagnosis software connection
14 Fan 1
15 Fan 2 (for VWL 155/2 only)
16 Fan PCB
17 Crankcase heating
18 Drain pan electrical heating rod
19 LED status display
20 Heating circuit high-efficiency pump with flow sensor
21 4-way valve
22 PCB installation
23 Rotary piston compressor
24 Inverter box
25 Temperature sensor for ribbed pipe heat exchanger
Start-up 6
0020147164_04 aroTHERM Installation instructions 21
6 Start-up
6.1 Run the start-up
1. Before starting up the product, read through the operat-
ing instructions.
2. Check that the electrical partition is installed.
3. Check that the hydraulic and electric connections are
correctly designed.
4. Check that a dirt filter is installed in the heat pump re-
turn.
5. Check whether an expansion relief valve, an expansion
vessel and a pressure gauge are installed.
6. Check the leak-tightness of the connections.
7. Open all the heating circuit valves.
6.2 Heat pump operating concept
Caution.
Risk of material damage caused by incor-
rect handling.
Incorrect settings at installer level may cause
damage to the heating installation.
Only access the installer level if you are
an approved competent person.
The operating concept and operation of the heat pump is
described in the operating instructions for the heat pump.
Menu Installer level
You can call up the installer level using code 17.
6.3 Running through the installation assistant
The installation assistant is launched when the heat pump is
switched on for the first time.
You must confirm the launching of the installation assistant.
Once confirmed, all heating demands from the heat pump
are blocked. This status remains until the installation assist-
ant is completed or cancelled.
Set the system diagram number in the VWZ AI heat pump
control module in accordance with the schematic drawings in
the appendix ( Page 30).
6.3.1 Setting the language
Menu Basic setting Language
You can use this function to set the desired language.
6.3.2 Telephone number for the competent
person
You can store your telephone number in the appliance
menu.
The operator can display it in the information menu. The tele-
phone number can be up to 16 digits long and must not con-
tain any spaces. If the telephone number is shorter, end the
entry after the last digit by pressing the right-hand selection
button .
All of the digits to the right will be deleted.
6.4 Calling up Live Monitor (checking status
codes)
Menu Live Monitor
You can use this function to call up the status code of the
heat pump, which provides you with information about
the current operating condition of the heat pump.
6.5 Calling up statistics
Menu Installer level Test menu Statistics
You can use this function to call up the statistics for the
heat pump.
6.6 Filling the heating circuit
Note
We recommend using ethylene glycol with corro-
sion-inhibiting additives.
If no frost protection has been poured in, the
product will not be protected in the event of a
power cut when there is frost.
Conditions: SW10 open-end spanner
A
B
10mm
2
1
3
4
1 Heating circuit purging
valve
2 Open-end spanner (on-
site)
3 Hose
4 Collecting container (on-
site)
To purge the heating circuit during the filling procedure,
use a filling pump.
Connect one end of the hose (3) to the drain valve.
When purging, insert the other end of the hose (3) into
the mixing container (4).
Open the filling valve using an open-end spanner (2).
To purge the heating circuit, open the purging valve by a
1/4 rotation (B) using an open-end spanner.
6 Start-up
22 Installation instructions aroTHERM 0020147164_04
Increase the operating pressure in the heat pump heat-
ing circuit.
Operating pressure: 0.15 … 0.2 MPa (1.50
… 2.0 bar)
Note
The pressure level may fall in the first month
following start-up. It may also vary depending
on the outside temperature.
Conditions: If you are using glycol
The glycol must not escape into the outflow or the envir-
onment.
Prepare a mixture with suitable glycol (max. 50% ethyl-
ene glycol) in order to protect the heat pump against
frost according to the regional minimum temperatures.
Note
If no frost protection has been poured in, the
product will not be protected in the event of a
power cut when there is frost.
Use a frost protection tester to ensure the correct
dosage.
6.7 Preparing the heating water
Caution.
Risk of material damage if the heating
water is treated with unsuitable frost and
corrosion protection agents.
Frost and corrosion protection agents may
cause changes in the seals, noises during
heating and may lead to further damage.
Do not use any unsuitable frost and corro-
sion protection agents.
Mixing additives with the heating water may result in material
damage. However, no incompatibility with Vaillant units has
been detected with proper use of the following products over
a long period.
When using additives, follow the manufacturer's instruc-
tions without exception.
Note
Vaillant accepts no liability for the compatibility
of any additive or its effectiveness in the rest
of the heating installation.
Additives for cleaning measures (subsequent
flushing required)
Fernox F3
Sentinel X 300
Sentinel X 400
Additives intended to remain permanently in the
system
Fernox F1
Fernox F2
Sentinel X 100
Sentinel X 200
Additives for frost protection intended to remain
permanently in the system
Fernox HP 15 or HP15c
Sentinel X 500
Inform the operator about the measures required if you
have used these additives.
Inform the operator about the measures required for frost
protection.
Permissible water hardness
Note
Contact the local water supply company for further
information on water quality.
Observe all applicable national regulations and technical
standards when treating the filling and supplementary
water.
Provided the national regulations and technical standards
do not stipulate more stringent requirements, the following
applies:
You must treat the heating water in the following cases:
If the entire filling and supplementary water volume dur-
ing the operating life of the system exceeds three times
the nominal volume of the heating installation,
If the limit values shown in the following tables are not
observed.
Total heating
output
Total hardness at smallest boiler heating
surface
1)
20 l/kW
> 20 l/kW
< 50 l/kW
> 50 l/kW
kW
mol/m³ (mg/l
CaCO)
mol/m³ (mg/l
CaCO)
mol/m³ (mg/l
CaCO)
< 50
No require-
ment
2 (200) 0,02 (2,0)
< 3
2)
(300
2)
)
> 50 to 200 2 (200) 1,5 (150) 0,02 (2,0)
1) Of the specific system volume (nominal capacity in
litres/heating output; on systems with more than one boiler, the
lowest individual heating output must be set). These values only
apply up to three times the system volume for filling and supple-
mentary water. If three times the system volume is exceeded,
the water must be treated in accordance with the specifications
from the VDI (softening, desalting, hardness stabilisation or
blowing down). This is exactly the same as if the limit values in
the table were exceeded
2) On systems with circulation water heaters and for systems
with electric heating elements
Permissible salt content
Heating water char-
acteristics
Unit Low-salt Saline
Electrical conductivity
at 25 °C
μS/cm < 100 100 … 1,500
Appearance
Free of sedimentary materi-
als
pH value at 25 °C
8,2 … 10,0
1)
8,2 … 10,0
1)
Start-up 6
0020147164_04 aroTHERM Installation instructions 23
Heating water char-
acteristics
Unit Low-salt Saline
Oxygen mg/l < 0.1 < 0.02
6.8 Filling the heating installation
Caution.
Risk of material damage due to heating
water that is extremely calciferous or cor-
rosive or contaminated by chemicals.
Unsuitable tap water damages the seals
and diaphragms, blocks components in the
product and heating installation through
which the water flows and causes noise.
Only fill the heating installation with suit-
able heating water.
Note
If a heat exchanger module is used, the heating
circuit must be topped up with heating water.
Conditions: System separation with a heat exchanger module
Connect the filling cock with the heating water supply
using a cold water valve where possible.
Open all radiator valves (thermostatic radiator valves) of
the heating installation.
Open the cold water valve.
Slowly open the filling cock.
Fill it with water until the required filling pressure is
reached.
Close the cold water valve.
Purge all radiators.
Then check the filling pressure on the display.
Top up with more water if necessary.
Close the filling cock.
6.9 Activating the heat pump
1. Ensure the maximum flow temperature setting matches
the heating installation.
2. To fully activate the heating installation, observe the
installation instructions for the system controller.
3. Switch on the line protection switch in the fuse box
which is connected to the heat pump.
6.10 Checking the product's operation
1. Ensure that the external control equipment (thermo-
stats, external sensors, etc.) are sending a heating
demand to the heat pump. When configuring several
areas, test heating circuit by heating circuit and ensure
that the appropriate heating circuit gets warmer.
2. Ensure that all heating circuit thermostatic radiator
valves are open.
3. If necessary, balance the heat generator.
6.11 Operating noises
"Hhmmm..." (*)
"Ttsheeh...!"
"Eeee..."
“Clink!"
"Chug, chug,
chug,..."
"Whirr..." (*)
1
2
3
4
5
6
* Permanent operating
noises
The noises listed do not constitute a fault with the heat
pump.
In various operating modes, the noises come from the heat
pump (Start, Thawing, Stop).
6.12 Adjusting the heating circuit
6.12.1 Purging the heating circuit
Conditions: SW14 open-end spanner
Connect one end of the hose to the purging valve.
In order to collect the residual glycol when purging the
heating circuit, insert the other end of the hose into the
mixing container.
Close the stop valves on the back of the product.
Increase the pressure in the heating circuit.
Open the purging valve with an open-end spanner.
Open the lower stop valve on the back of the product.
If liquid escapes from the pipe, close the purging valve.
Check the pressure in the heating circuit. If necessary,
increase it.
6 Start-up
24 Installation instructions aroTHERM 0020147164_04
Operating pressure: 0.15 … 0.2 MPa (1.50
… 2.0 bar)
Open the service valves on the back of the product.
Remove the hose and the mixing container.
6.12.1.1 Available pressure in the heat pump
heating circuit
A
B
0
10
20
30
40
50
60
70
80
5000 1000 1500 2000
C
100
200
300
400
500
600
700
800
90 900
2500
3
2
1
4
1 VWL 55/2 A 230 V (water
temperature 20 °C)
2 VWL 85/2 A 230 V (water
temperature 20 °C)
3 VWL 115/2 A 230 V (water
temperature 20 °C)
4 VWL 155/2 A 230 V (water
temperature 20 °C)
A Remaining feed head
(kPa)
B Flow rate (l/h)
C Remaining feed head
[mbar]
6.12.2 Adjusting the heating circuit flow rate
Caution.
Risk of material damage due to frost
If the minimum flow rate is too low, the heat
exchanger may become damaged by frost.
Operate the product with a sufficient flow
rate (see table).
The product is designed for operation between the minimum
flow rate and maximum flow rate, as specified in the table. If
the product is operated with the minimum flow rate, this res-
ults in a loss of energy and efficiency. The heating comfort is
still guaranteed but the energy savings are reduced.
VWL 55/2 VWL 85/2 VWL 115/2 VWL 155/2
Minimum
flow rate
380 l/h 380 l/h 540 l/h 1,200 l/h
Maximum
flow rate
860 l/h 1,400 l/h 1,900 l/h 2,590 l/h
You can read the flow rate directly from the controller. De-
pending on the type of liquid in the heating circuit, the flow
rate displayed on the controller may be exaggerated.
Example: If you use a 30% mixture of propylene glycol and
the liquid temperature is 5 °C, you must subtract 400 l/h from
the value shown on the display.
Use the following table to compare the various exaggera-
tion flow rate values depending on liquid type.
Applies for: VWL 55/2 A 230 V,
VWL 85/2 A 230 V,
VWL 115/2 A 230 V
Flow rate increase (l/h) Temper-
ature
5 °C
Temper-
ature
15 °C
Temper-
ature
25 °C
Liquid
type
Water 0 0 0
60% alcohol 0 0 0
30% propylene
glycol
400 240 120
50% propylene
glycol
650 500 400
30% ethylene
glycol
120 0 0
50% ethylene
glycol
400 140 50
Applies for: VWL 155/2 A 230 V
Flow rate increase (l/h) Temper-
ature
5 °C
Temper-
ature
15 °C
Temper-
ature
25 °C
Liquid
type
Water 0 0 0
60% alcohol 0 0 0
30% propylene
glycol
600 440 280
50% propylene
glycol
1050 740 580
30% ethylene
glycol
520 350 300
50% ethylene
glycol
880 680 540
Note
Insufficient purging may lead to deviations in the
flow rate.
If you cannot reach the minimum flow rate, install an ad-
ditional pump.
If you cannot reach the recommended flow rate, adjust
the heating circuit pressure on the controller and, if ne-
cessary, use a bypass valve (item 50).
6.12.3 Adapting the unit to the heating installation
The installation assistant is launched when the product is
switched on for the first time.
If you have already filled the heating installation and termin-
ated the installation assistant, but want to set the most im-
portant system parameters again, you can also call up the
Configuration menu point.
Menu Installer level Configuration
Maintenance 7
0020147164_04 aroTHERM Installation instructions 25
6.12.3.1 Heat pump setting parameters
To individually set the heat pump, you can adjust certain
parameters in the Configuration menu.
Menu Installer level Configuration
Additional setting data is listed in the appendix.
Heat pump setting parameters ( Page 44)
6.13 Installing the side cladding
C
C
B
A
Install the side cladding.
6.14 Instructing the operator
1. Explain the how the system operates to the operator.
2. Draw particular attention to the safety information,
which the operator must follow.
3. Make the operator aware of the need for regular main-
tenance (maintenance contract).
4. Explain to the operator how to check the system's water
volume/filling pressure.
7 Maintenance
7.1 Observing maintenance intervals
1. Only carry out maintenance work if you are a competent
person.
2. Carry out annual maintenance.
7.2 Preparing for maintenance
7.2.1 Procuring spare parts
The original components of the unit were also certified as
part of the CE declaration of conformity. Information about
available Vaillant genuine spare parts is available by con-
tacting the contact address provided on the reverse of this
document.
If you require spare parts for maintenance or repair work,
use only Vaillant genuine spare parts.
7.3 Instructions before carrying out
maintenance work
Observe the basic safety rules before carrying out mainten-
ance work or installing spare parts.
Danger!
Risk of injury due to unauthorised access
to the coolant circuit.
Escaping coolant may cause freezing if the
exit point is touched.
Only carry out work on the coolant circuit if
you have been trained to do so and if you
have the required protective clothing.
Avoid skin and eye contact with the
coolant.
Switch the system off.
Disconnect the system from the power supply.
Where necessary, disconnect the heating circuit from the
product by using the stop valves.
If you have to replace parts on the heating circuit, you
must first drain the product.
When working on the product, protect all electric com-
ponents from spray water.
7.4 Yearly maintenance
Check that the safety devices are functioning properly.
Check the heating circuit's fill pressure.
Ensure that there are no traces of rust or oil on the
coolant circuit components.
Ensure that the product components are neither worn nor
defective.
Check that all wires sit securely in the connectors.
Check the product's earthing.
Check the heating pump's flow temperature and the set-
tings.
Remove any dust from the electronics box and the in-
verter box.
Clean the ribbed pipe heat exchanger and ensure that air
circulates between the fins and around the product.
Check that the fan rotates freely.
Check that condensate can escape freely from the heat
pump by removing the adaptor underneath the heat
pump.
Clean the product as described in the operating instruc-
tions.
Check that the vibration dampers are correctly seated on
the coolant lines.
7 Maintenance
26 Installation instructions aroTHERM 0020147164_04
7.5 Cleaning the product
7.5.1 Cleaning the front
Warning.
Risk of injury due to sharp-edged casing.
The product's casing sections have sharp
edges.
Wear gloves when installing or dismant-
ling the product's casing sections.
3
4
5
3.
6.
5.
1
2
1. Remove the side casing. ( Page 14)
2. Remove both screws (1).
3. Lift off the cover.
4. Remove both screws (2) on the right front casing.
5. Remove the right front casing.
6. Lift the louvred grill (3) upwards.
7. Remover the fan grill casing (4).
8. Remove the nut (5) from the fan.
9. Remove the fan.
10. Clean the product and the ribbed pipe heat exchanger.
7.5.2 Cleaning the back
Warning.
Risk of injury due to sharp-edged casing.
The product's casing sections have sharp
edges.
Wear gloves when installing or dismant-
ling the product's casing sections.
1
2
3
1. Remove the side casing. ( Page 14)
2. Remove both screws (1).
3. Lift off the cover.
4. Remove the four screws (2) and remove the mesh (3).
5. Clean the product.
7.6 Draining the product
Conditions: SW10 open-end spanner
Disconnect the product from the power supply.
10mm
2
1
1 Heating circuit drain cock 2 Drain hose
1. Close the stop valves on the back of the heat pump.
2. To drain the heating circuit, connect a hose to the drain
cock or place a vessel underneath the drain cock.
3. Open the drain cock with an open-end spanner.
Troubleshooting 8
0020147164_04 aroTHERM Installation instructions 27
Note
If necessary, you can drain the heating
installation using this drain cock by opening
the stop valves on the back of the heat
pump.
7.7 Checking the product's status codes
Menu Live Monitor
You can check the product's status codes at any time to see
which operating condition the heat pump is in. You can read
these codes on the display of the heat pump control module
or hydraulic station VWZ MEH 61.
7.8 Checking the electrical installation
Check the electrical installation and take all relevant dir-
ectives into account.
Checking the cable
If the product's mains power cable is damaged, then, in order
to avoid danger, only the manufacturer, the Customer Ser-
vice team or a similarly qualified person should replace the
mains power cable.
To replace the mains power cable, see Carrying out the
electrical installation ( Page 17).
7.9 Start-up following maintenance
1. After the maintenance work has been completed, start
up the product see Start-up ( Page 21).
2. If you have carried out work on load-bearing parts,
check that they are securely fitted.
3. When you have completed work on the product, carry
out an operational and safety test.
8 Troubleshooting
8.1 Troubleshooting
You should carry out the following tests before introducing
additional steps:
Make absolutely sure that the power supply was not cut
and that the product is correctly connected.
Ensure that the service valves are open.
Check that all external controllers are correctly connec-
ted.
8.2 Fault codes
The fault codes are described in a table in the Appendix.
Fault codes ( Page 48)
In the event of a fault, a fault code number is shown in the
controller's display.
Carry out all necessary repairs.
Switch the product on/off using the partition.
8.3 Carrying out the actuator test
Menu Installer level Test menu Sensor/actuator
test
You can check that the components of the heating installa-
tion are functioning correctly using the sensor/actuator test.
Display Test programme
T.0.01 Heating pump power
T.0.05 Fan power
T.0.07 4-way valve (circuits for thawing are not counted)
T.0.08 Position of the electronic expansion valve
T.0.09 Heating coil compressor
T.0.13 Flow temperature
T.0.14 Return temperature
T.0.15 Heating circuit pressure
T.0.16 Heating circuit flow rate
T.0.17 Lockout contact S20
T.0.66 Air inlet temperature
T.0.26 Compressor outlet temperature
T.0.27 Compressor inlet temperature
T.0.29 Heat exchanger temperature
T.0.30 High pressure
T.0.31 Condensation temperature
T.0.33 Evaporation temperature
T.0.34 Superheating target value
T.0.35 Superheating actual value
T.0.36 Subcooling actual value
T.1.37 Outside temperature
T.1.38 DCF status
T.1.59 Multi-function output 1
T.1.60 Multi-function output 2
T.1.61 Diverter valve 1
T.1.62 Flow sensor
T.1.63 Cylinder sensor
T.1.64 Multi-function input
T.1.65 Energy supply company input
T.1.66 Inlet temperature
T.1.67 High-pressure switch
T.1.68 Compressor rotational speed
T.1.69 Condensate pan heating
T.1.15 Water pressure
9 Decommissioning
28 Installation instructions aroTHERM 0020147164_04
9 Decommissioning
9.1 Temporary decommissioning
1. Switch the product off.
2. Disconnect the product from the power supply.
9.2 Permanently decommissioning
1. Switch the product off.
2. Disconnect the product from the power supply.
3. Drain the product. ( Page 26)
4. Dispose of or recycle the product and its components.
10 Vaillant customer service
10.1 Customer service
To ensure regular servicing, it is strongly recommended
that arrangements are made for a Maintenance Agreement.
Please contact Vaillant Service Solutions (0870 6060 777)
for further details.
To ensure efficient and reliable operation of your boiler it is
recommended that regular servicing is carried out by your
service provider:
Vaillant Applied System Sales
Vaillant Group UK Ltd.
Nottingham Road
Belper
Derbyshire DE56 1JT
United Kingdom
VaillantTraining: 84560188 85
E-mail: commercial@vaillant.co.uk
Commercial service assistance: 87085030 72 (Mon-Fri
8:30am 5:30pm)
Technical advice: 84469331 33 (Mon-Fri 8:30am 5:30pm,
Sat 9:00am - 4:00pm)
E-mail: technical@vaillant.co.uk
11 Disposal
11.1 Recycling and disposal
The competent person who installed your product is re-
sponsible for the disposal of the packaging.
If the product or any batteries that it contains are
marked with this symbol, they contain substances hazardous
to human health and to the environment.
In this case, do not dispose of the product and any bat-
teries that it contains with your normal household waste.
Instead, bring the product and any batteries to a collec-
tion centre for batteries and electrical or electronic appli-
ances.
11.2 Arranging disposal of coolant
Warning.
Risk of damage to the environment.
This heat pump contains R 410 A coolant.
The coolant must not be allowed to escape
into the atmosphere. R 410 A is a fluorinated
greenhouse gas covered by the Kyoto Pro-
tocol, with a GWP of 1725 (GWP = Global
Warming Potential).
Before the product is disposed of, have
the coolant which it contains completely
drained into a suitable vessel so that it
can then be recycled or disposed of in
accordance with regulations.
The competent person who installed the heat pump must
dispose of the coolant.
Personnel who are approved for energy recovery must have
the relevant certification that corresponds to the valid regula-
tions.
Appendix
0020147164_04 aroTHERM Installation instructions 29
Appendix
A Overview of accessories
System diagrams
8E 8F 9B* 9A* 10A 10B 10C 11A*
12A** 12B**
Auxiliary heat generator
VWZ MEH 60 X X X X
VWZ MEH 61
Heat generator X X X X
Heat generator without
eBUS/external heat
generator
X
Frost protection
Without heat exchanger X X X X X X
VWZ MWT 150 X X X X
Decoupling/cylinder
Without decoupling module X X X X X
VWZ MPS 40 X X X X
External cylinder X
Hot water generation
Heat generator with hot
water generation
X
Domestic hot water cylinder X X X X X
Solar-powered domestic hot
water cylinder
X
Bivalent domestic hot water
cylinder (heat pump and heat
generator)
X X
Zone/heating circuit con-
trol
1-zone/heating circuit X X X
2-zone/heating circuit X X X X X
1- or 2-zone/heating circuit X X
*) With VR470/4 only
**) If the installation is not carried out correctly and no auxiliary heat generator is installed, this may affect the comfort level.
Appendix
30 Installation instructions aroTHERM 0020147164_04
B System diagrams
B.1 System diagram 8 E
M
q
P2 P1
1
2
38
16
KW
43
42a
VF1
50
91
13h
13e
3
93
10
42a
32
42b
3
2 BUS
3(5)
3
2
2 BUS2 BUS
2 BUS
230 V ~ 3
230 V ~
230(400) V ~
1 Heat generator
2 Hear generator pump
3 Heat pump
10 Thermostatic radiator valve
13e System controller
13h Bus coupler
16 Outside temperature sensor/DCF receiver
32 Cap valve
Appendix
0020147164_04 aroTHERM Installation instructions 31
38 Diverter valve
42a Expansion relief valve
42b Diaphragm expansion tank
43 Safety group drinking water connection
50 Differential-pressure bypass valve
91 VWZ AI VWL X/2 heat pump control module
93 VWZ MPS 40 compact buffer cylinder
KW Cold water
VF1 Flow temperature sensor 1
Appendix
32 Installation instructions aroTHERM 0020147164_04
B.2 System diagram 8 F
P2 P1
M
q
M
q
M
16
KW
5
43
42c
42a
SP2
13a
VF1
ZH
52
19
52
19
50
ZP
3030
39
13b
SP1
58
25
KOL1-P
48
42b
32
58
64
65
42a
Ertrag
63
KOL1
13g
13e
3
94
28
(HK1-P)
28
(HK2-P)
42a
91
UV1
32
42b
Auf
Zu
3(5)
3
2 BUS
3(5)
2 BUS
2 BUS
230 V ~
3
2 BUS
4
2
2
2
2
3 230 V ~
2 BUS
4
2
2
3 230 V ~
2 BUS
2
2
3
3
230(400) V ~
230(400) V ~
q
3 Heat pump
5 Domestic hot water cylinder
13a Remote control unit
13b Mixer module
13e System controller
13g Solar module
16 Outside temperature sensor/DCF receiver
19 Maximum thermostat
25 Solar pump unit
28 Zone valve
30 Non-return valve
32 Cap valve
Appendix
0020147164_04 aroTHERM Installation instructions 33
39 Thermostat mixing valve
42a Expansion relief valve
42b Diaphragm expansion tank
42c Diaphragm expansion tank drinking water
43 Safety group drinking water connection
48 Pressure gauge
50 Differential-pressure bypass valve
52 Individual room control valve
58 Fill and drain valve
63 VFK solar flat collector
64 Solar in-line vessel
65 Collecting container
91 VWZ AI VWL X/2 auxiliary module
94 VWZ MEH 60 auxiliary heating module
HK1-P Heating pump 1
HK2-P Heating pump 2
KOL1 Collector temperature sensor for collector field 1
KOL1-
P
Solar pump for collector field 1
KW Cold water
SP1 Cylinder temperature sensor
SP2 Cylinder temperature sensor (solar cylinder)
VF1 Flow temperature sensor 1
ZP Circulation pump
Appendix
34 Installation instructions aroTHERM 0020147164_04
B.3 System diagram 10 B
48
48
q
P2 P1
M
q
M
q
M
16
KW
5
43
42c
42a
SP1
52
19
52
19
50
13a
VF1
ZH
ZP
30
13b
13e
3
94
92
40
28
(HK1-P)
28
(HK2-P)
42a
42a
65
91
UV1
32
42b
32
42b
MA1
(HK-P)
Auf
Zu
3(5)
3
2 BUS
3(5)
2 BUS2 BUS
230 V ~ 3
3(5)
2
2
2 BUS
2
4
2
3
4
3 230 V ~
2 BUS
3
230(400) V ~
230(400) V ~
230(400) V ~
2
VF2
1b
1b Auxiliary heater for hot water support
3 Heat pump
5 Domestic hot water cylinder
13a Remote control unit
13b Mixer module
13e System controller
16 Outside temperature sensor/DCF receiver
19 Maximum thermostat
28 Zone valve
30 Non-return valve
32 Cap valve
40 Heat exchanger
Appendix
0020147164_04 aroTHERM Installation instructions 35
42a Expansion relief valve
42b Diaphragm expansion tank
42c Diaphragm expansion tank drinking water
43 Safety group drinking water connection
48 Pressure gauge
50 Differential-pressure bypass valve
52 Individual room control valve
65 Collecting container
91 VWZ AI VWL X/2 auxiliary module
92 VWZ MWT 150 heat exchanger module
94 VWZ MEH 60 auxiliary heating module
HK-P Heating pump 1
HK1-P Heating pump 1
HK2-P Heating pump 2
KW Cold water
MA Multi-relay output
UV1 Diverter valve 1
SP1 Cylinder temperature sensor
VF1 Flow temperature sensor 1
VF2 Flow temperature sensor 2
ZP Circulation pump
Appendix
36 Installation instructions aroTHERM 0020147164_04
B.4 System diagram 12 A
q
P2 P1
M
q
M
q
M
16
KW
5
43
42c
42a
SP1
52
19
52
19
50
13a
VF1
ZH
13e
3
94
28(MA1) 28(MA2)
42a
91
UV1
32
42b
Auf
Zu
3(5)
3
2 BUS
3(5)
2 BUS2 BUS
230 V ~ 3
22
2 BUS
4
2
3
2
3(5)
230(400) V ~
230(400) V ~
230(400) V ~
1b
48
1b Auxiliary heater for hot water support
3 Heat pump
5 Domestic hot water cylinder
13a Remote control unit
13e System controller
16 Outside temperature sensor/DCF receiver
19 Maximum thermostat
28 Zone valve
32 Cap valve
42a Expansion relief valve
42b Diaphragm expansion tank
42c Diaphragm expansion tank drinking water
Appendix
0020147164_04 aroTHERM Installation instructions 37
43 Safety group drinking water connection
48 Pressure gauge
50 Differential-pressure bypass valve
52 Individual room control valve
91 VWZ AI VWL X/2 auxiliary module
94 VWZ MEH 60 auxiliary heating module
KW Cold water
UV1 Diverter valve 1
VF1 Flow temperature sensor 1
C Wiring diagrams
C.1 Wiring diagram 8 E
UV1
MA2
MA1
230 V~
230 V~
ME
EVU
2
1
SP1
DCF/AF
VF1
+
-
BUS
ZH
230 V~
2
1
PE
1
2
N
PE
Auf
Zu
N
PE
N
PE
N
PE
N
PE
N
L
L
L
L
16
DCF 0 AF
91
VRC 470
13e
VF1
230 V~
X41
1
L
N
230 V~
FB
AF
RF
DCF
0
0
-
+
6
230 V~
eBUS
13h
1
VR32
VWZ AI VWL X/2
VWL x5/2 A 230 V
-
+
EBUS
FLOOR HX7
X4
230 V~
L
N
X9
X2
3
1
2
400 V~
L3
N
L2
L1
X2
VWL x5/2 A 400 V
AF
DCF
T0
3,3 V / 5 V /
24 V
2
1
2
1
X31
VCW
1 Heat generator
3 Heat pump
13e System controller
13h Bus coupler
16 Outside temperature sensor/DCF receiver
91 VWZ AI VWL X/2 auxiliary module
VF1 Flow temperature sensor 1
Appendix
38 Installation instructions aroTHERM 0020147164_04
C.2 Wiring diagram 8 F
UV1
MA2
MA1
230 V~
230 V~
ME
EVU
2
1
SP1
DCF/AF
VF1
+
-
BUS
ZH
230 V~
2
1
PE
1
2
N
PE
Auf
Zu
N
PE
N
PE
N
PE
N
PE
N
L
L
L
L
L1 L2
L3
PE N N
1
2
400 V~
230 V~
16
DCF 0 AF
M
VRC 470
13e
13b
230 V~
BUS
2
1
VF2
VWZ AI VWL X/2
91
VWZ MEH 60
94
VR 61
VR 81
13a
VF2
LEG-P
KOL1-P
MA
230 V~
3,3 V / 5 V / 24 V
13g
230 V~
+
-
BUS
2
1
KOL1
VR 68
L
N
PE
L
N
PE
L
N
PE
L
N
PE
2
1
SP1
2
1
SP2
2
1
Ertrag
2
1
TD1
2
1
TD2
230 V~
KOL1-P
KOL1
SP1
SP2
Ertrag
VWL x5/2 A 230 V
-
+
EBUS
FLOOR HX7
X4
230 V~
L
N
X9
X2
3
1
2
400 V~
L3
N
L2
L1
X2
VWL x5/2 A 400 V
AF
DCF
T0
3,3 V / 5 V /
24 V
2
1
2
1
HK1-P
230 V~
L
N
PE
L
N
PE
L
N
PE
230 V~
HK2-P
nc
19
HK2
HK2-P
LP/ZP
Auf
Zu
N
PE
L
N
PE
HK1-P
ZP
nc
19
VF1
MM
3 Heat pump
13a Remote control unit
13b Mixer module
13e System controller
13g Solar module
16 Outside temperature sensor/DCF receiver
19 Maximum thermostat
91 VWZ AI VWL X/2 auxiliary module
94 VWZ MEH 60 auxiliary heating module
HK1-P Heating pump 1
HK2-P Heating pump 2
KOL1 Collector temperature sensor for collector field 1
Appendix
0020147164_04 aroTHERM Installation instructions 39
KOL1-
P
Solar pump for collector field 1
SP1 Cylinder temperature sensor
SP2 Cylinder temperature sensor (solar cylinder)
VF1 Flow temperature sensor 1
ZP Circulation pump
C.3 Wiring diagram 10 B
UV1
MA2
MA1
230 V~
230 V~
ME
EVU
2
1
SP1
DCF/AF
VF1
+
-
BUS
ZH
230 V~
2
1
PE
1
2
N
PE
Auf
Zu
N
PE
N
PE
N
PE
N
PE
N
L
L
L
L
L1 L2
L3
PE N N
1
2
400 V~
16
DCF 0 AF
VRC 470
13e
13b
230 V~
BUS
2
1
VF2
VR 61
VR 81
13a
91
VWZ AI VWL X/2
UV1
VF1
94
VWZ MEH 60
230 V~
VF2
M
UV1
SP1
HK-P
92
VWZ MWT 150
VWL x5/2 A 230 V
-
+
EBUS
FLOOR HX7
X4
230 V~
L
N
X9
X2
3
1
2
400 V~
L3
N
L2
L1
X2
VWL x5/2 A 400 V
AF
DCF
T0
3,3 V / 5 V /
24 V
2
1
2
1
28 (HK2-P)
19
nc
ZP
M
28 (HK1-P)
19
nc
M
HK1-P
230 V~
L
N
PE
L
N
PE
L
N
PE
HK2
HK2-P
LP/ZP
Auf
Zu
N
PE
L
N
PE
230 V~
3 Heat pump
13a Remote control unit
13b Mixer module
13e System controller
Appendix
40 Installation instructions aroTHERM 0020147164_04
16 Outside temperature sensor/DCF receiver
19 Maximum thermostat
91 VWZ AI VWL X/2 auxiliary module
92 VWZ MWT 151 heat exchanger module
94 VWZ MEH 60 auxiliary heating module
HK-P Heating pump 1
HK1-P Heating pump 1
HK2-P Heating pump 2
UV1 Diverter valve 1
SP1 Cylinder temperature sensor
VF1 Flow temperature sensor 1
VF2 Flow temperature sensor 2
ZP Circulation pump
C.4 Wiring diagram 12 A
UV1
MA2
MA1
230 V~
230 V~
ME
EVU
2
1
SP1
DCF/AF
VF1
+
-
BUS
ZH
230 V~
2
1
PE
1
2
N
PE
Auf
Zu
N
PE
N
PE
N
PE
N
PE
N
L
L
L
L
16
DCF 0 AF
M
91
VWZ AI VWL X/2
UV1
230 V~
SP1
VWL x5/2 A 230 V
-
+
EBUS
FLOOR HX7
X4
230 V~
L
N
X9
X2
3
1
2
400 V~
L3
N
L2
L1
X2
VWL x5/2 A 400 V
L1 L2
L3
PE N N
1
2
400 V~
VF1
94
VWZ MEH 60
M
19
nc
28 (MA2)
M
19
nc
28 (MA1)
VRC 470
13e
VR 81
13a
AF
DCF
T0
3,3 V / 5 V /
24 V
2
1
2
1
3 Heat pump
13a Remote control unit
13e System controller
16 Outside temperature sensor/DCF receiver
19 Maximum thermostat
28 Zone valve
91 VWZ AI VWL X/2 auxiliary module
94 VWZ MEH 60 auxiliary heating module
UV1 Diverter valve
SP1 Cylinder temperature sensor
VF1 Flow temperature sensor
Appendix
0020147164_04 aroTHERM Installation instructions 41
D Heat pump schematic
D.1 Heat pump schematic drawing (VWL 55/2 A 230 V)
PZHH
-
TI
-
TCE
TI
-
TI
-
PT
-
TI
-
TI
-
TI
-
TI
-
7
9
8
23
22
18
15
16
17
14
12
6
1
4
5
13
19
21
24
10
25
11
20+
2
3
1 Flow heating circuit temperature sensor
2 Return heating circuit temperature sensor
3 High-efficiency pump with flow sensor
4 Expansion vessel (not for Vaillant)
5 Drain valve
6 Purging valve
7 Fan
8 Air inlet temperature sensor
9 Ribbed pipe heat exchanger
10 Temperature sensor of the ribbed pipe heat exchanger
11 4-way valve
12 Plate heat exchanger
13 Temperature sensor after the plate heat exchanger
14 Service valve for the high-pressure range of the coolant
circuit
15 High-pressure pressure switch in the coolant circuit
16 High-pressure sensor in the coolant circuit
17 Compressor outlet temperature sensor
18 Rotary piston compressor
19 Filter
20 Liquid separator
21 Electronic expansion valve
22 Compressor inlet temperature sensor
23 Service valve for the low-pressure range of the coolant
circuit
24 Filter
25 Fluid collector
Appendix
42 Installation instructions aroTHERM 0020147164_04
D.2 Heat pump schematic drawing (VWL 85/2 A 230 V)
PZHH
-
TI
-
TCE
TI
-
TI
-
PT
-
TI
-
TI
-
TI
-
TI
-
7
9
8
23
22
18
15
16
17
14
12
6
1
4
5
13
19
21
24
10
25
11
20+
2
26
3
1 Flow heating circuit temperature sensor
2 Return heating circuit temperature sensor
3 High-efficiency pump with flow sensor
4 Expansion vessel (not for Vaillant)
5 Drain valve
6 Purging valve
7 Fan
8 Air inlet temperature sensor
9 Ribbed pipe heat exchanger
10 Temperature sensor of the ribbed pipe heat exchanger
11 4-way valve
12 Plate heat exchanger
13 Temperature sensor after the plate heat exchanger
14 Service valve for the high-pressure range of the coolant
circuit
15 High-pressure pressure switch in the coolant circuit
16 High-pressure sensor in the coolant circuit
17 Compressor outlet temperature sensor
18 Rotary piston compressor
19 Filter
20 Liquid separator
21 Electronic expansion valve
22 Compressor inlet temperature sensor
23 Service valve for the low-pressure range of the coolant
circuit
24 Filter
25 Gas buffer
26 Flow rate limiter (cooling mode)
Appendix
0020147164_04 aroTHERM Installation instructions 43
D.3 Heat pump schematic drawing (VWL 115/2 A 230 V)
PZHH
-
TI
-
TCE
TI
-
TI
-
PT
-
TI
-
TI
-
TI
-
TI
-
7
9
8
23
22
18
15
16
17
14
12
6
1
4
5
13
19
21
24
10
25
11
20+
2
3
1 Flow heating circuit temperature sensor
2 Return heating circuit temperature sensor
3 High-efficiency pump with flow sensor
4 Expansion vessel (not for Vaillant)
5 Drain valve
6 Purging valve
7 Fan
8 Air inlet temperature sensor
9 Ribbed pipe heat exchanger
10 Temperature sensor of the ribbed pipe heat exchanger
11 4-way valve
12 Plate heat exchanger
13 Temperature sensor after the plate heat exchanger
14 Service valve for the high-pressure range of the coolant
circuit
15 High-pressure pressure switch in the coolant circuit
16 High-pressure sensor in the coolant circuit
17 Compressor outlet temperature sensor
18 Rotary piston compressor
19 Filter
20 Liquid separator
21 Electronic expansion valve
22 Compressor inlet temperature sensor
23 Service valve for the low-pressure range of the coolant
circuit
24 Filter
25 Gas buffer
Appendix
44 Installation instructions aroTHERM 0020147164_04
D.4 Heat pump schematic drawing (VWL 155/2 A 230 V)
PZHH
-
TI
-
TCE
TI
-
TI
-
PT
-
TI
-
TI
-
TI
-
TI
-
7
9
8
23
22
18
15
16
17
14
12
6
1
3
4
5
13
19
21
24
10
25
11
20+
2
1 Flow heating circuit temperature sensor
2 Return heating circuit temperature sensor
3 High-efficiency pump with flow sensor
4 Expansion vessel (not for Vaillant)
5 Drain valve
6 Purging valve
7 Fan
8 Air inlet temperature sensor
9 Ribbed pipe heat exchanger
10 Temperature sensor of the ribbed pipe heat exchanger
11 4-way valve
12 Plate heat exchanger
13 Temperature sensor after the plate heat exchanger
14 Service valve for the high-pressure range of the coolant
circuit
15 High-pressure pressure switch in the coolant circuit
16 High-pressure sensor in the coolant circuit
17 Compressor outlet temperature sensor
18 Rotary piston compressor
19 Filter
20 Liquid separator
21 Electronic expansion valve
22 Compressor inlet temperature sensor
23 Service valve for the low-pressure range of the coolant
circuit
24 Filter
25 Gas buffer
E Heat pump setting parameters
Note
If repairs are carried out on the heat pump electronics (e.g. replacing the PCB), you must reset the parameters.
Appendix
0020147164_04 aroTHERM Installation instructions 45
Parameter Explanation Default
setting
Adjustment
range
Own setting
Language Select the required language here. 02 English 01 Deutsch
02 English
03 Français
04 Italiano
05 Dansk
07 Castellano
08 Türkçe
09 Magyar
11 Українська
15 Svenska
16 Norsk
18 Čeština
19 Hrvatski
20 Slovenčina
22 Slovenščina
Contact
details
As a competent person, you can enter your telephone num-
ber here. The end customer can read this number in the
menu Information.
Max. remain-
ing heating
circuit feed
head
Limiting the remaining heating circuit feed head. If the value
is reduced, the pump speed is reduced as far as necessary
in order to prevent the remaining feed head from being
exceeded.
Maximum
value
100 mbar
Max. remain-
ing hot water
feed head
Limiting the remaining hot water circuit feed head. If the
value is reduced, the pump speed is reduced as far as ne-
cessary in order to prevent the remaining feed head from
being exceeded.
Maximum
value
100 mbar
Max. dura-
tion of the
power inter-
ruption
If the set value is exceeded when the power supply is dis-
connected, fault messages F.103, F.752 or F.753 may be
displayed.
If the heat pump is to be operated in the normal or spe-
cial tariff, set the value to 3 h in the special tariff during
installation.
0 h 0 - 99 h
F Technical data
Note
The following performance data is only applicable to new products with clean heat exchangers.
Technical data General
VWL 55/2 A
230 V
VWL 85/2 A
230 V
VWL 115/2 A
230 V
VWL 155/2 A
230 V
Heat pump type
Monoblock
air/water heat
pump
Monoblock
air/water heat
pump
Monoblock
air/water heat
pump
Monoblock
air/water heat
pump
Flow/return heating con-
nections, boiler side
1 1/4" 1 1/4" 1 1/4" 1 1/4"
Product dimensions,
width
970 mm 1,103 mm 1,103 mm 1,103 mm
Product dimensions,
height
834 mm 975 mm 975 mm 1,375 mm
Product dimensions,
depth
408 mm 463 mm 463 mm 463 mm
Net weight
90 kg 106 kg 126 kg 165 kg
Hydraulic lines material
Copper Copper Copper Copper
Hydraulic connections
material
Brass Brass Brass Brass
Hydraulic seals material
EPDM EPDM EPDM EPDM
Appendix
46 Installation instructions aroTHERM 0020147164_04
VWL 55/2 A
230 V
VWL 85/2 A
230 V
VWL 115/2 A
230 V
VWL 155/2 A
230 V
Plate heat exchanger ma-
terial
AISI 304
stainless steel
AISI 304
stainless steel
AISI 304
stainless steel
AISI 304
stainless steel
Pump casing material
Painted cast
iron
Painted cast
iron
Painted cast
iron
Painted cast
iron
Pollution rating
2 2 2 2
Electric connection
230 V/50 Hz 230 V/50 Hz 230 V/50 Hz 230 V/50 Hz
Fuse type
T4A T4A T4A T4A
Inverter controller fuse
HRC 20 A 550
V
HRC 20 A 550
V
HRC 32 A 550
V
HRC 32 A 550
V
Level of protection
IP 25 IP 25 IP 25 IP 25
Maximum start-up cur-
rent
16 A 16 A 20 A 25 A
Maximum current con-
sumption
16 A 16 A 20 A 25 A
Pump power consump-
tion
15 … 70 W 15 … 70 W 15 … 70 W 6 … 87 W
Fan power consumption
15 … 42 W 15 … 42 W 15 … 76 W 15 … 76 W
Note
2 x
Electrical classification
I I I I
Overvoltage category
II II II II
Fan rotational speed
550 rpm 550 rpm 700 rpm 600 rpm
Sound power level for
A7W35 according to EN
12102 and EN ISO 9614-1
58 dB(A) 60 dB(A) 65 dB(A) 65 dB(A)
Sound power level for
A7W45 according to EN
12102 and EN ISO 9614-1
59 dB(A) 60 dB(A) 65 dB(A) 65 dB(A)
Sound power level for
A7W55 according to EN
12102 and EN ISO 9614-1
61 dB(A) 61 dB(A) 66 dB(A) 66 dB(A)
Maximum cylinder tem-
perature
60 63 63 63
Minimum air temperature
(heating and cylinder
charging)
15 20 20 20
Maximum air temperature
(heating)
28 28 28 28
Max. air temperature (cyl-
inder charging)
46 46 46 46
Max. air flow
2,000 m³/h 2,700 m³/h 3,400 m³/h 5,500 m³/h
Technical data Heating circuit
VWL 55/2 A
230 V
VWL 85/2 A
230 V
VWL 115/2 A
230 V
VWL 155/2 A
230 V
Minimum operating pres-
sure
0.1 MPa
(1.0 bar)
0.1 MPa
(1.0 bar)
0.1 MPa
(1.0 bar)
0.1 MPa
(1.0 bar)
Maximum operating pres-
sure
0.3 MPa
(3.0 bar)
0.3 MPa
(3.0 bar)
0.3 MPa
(3.0 bar)
0.3 MPa
(3.0 bar)
Heating circuit water con-
tents in the heat pump
1.1 l 1.6 l 2.1 l 2.7 l
Minimum heating circuit
water contents
17 l 21 l 35 l 60 l
Min. volume flow rate
380 l/h 380 l/h 540 l/h 1,200 l/h
Appendix
0020147164_04 aroTHERM Installation instructions 47
VWL 55/2 A
230 V
VWL 85/2 A
230 V
VWL 115/2 A
230 V
VWL 155/2 A
230 V
Nominal volume flow
rate, max. volume flow
rate
860 l/h 1,400 l/h 1,900 l/h 2,590 l/h
Hydraulic pressure differ-
ence
640 mbar 450 mbar 300 mbar 370 mbar
Technical data Coolant circuit
VWL 55/2 A
230 V
VWL 85/2 A
230 V
VWL 115/2 A
230 V
VWL 155/2 A
230 V
Coolant type
R410A R410A R410A R410A
Coolant contents
1.80 kg 1.95 kg 3.53 kg 4.40 kg
Maximum permissible
operating overpressure
4.15 MPa
(41.50 bar)
4.15 MPa
(41.50 bar)
4.15 MPa
(41.50 bar)
4.15 MPa
(41.50 bar)
Compressor type
Rotary piston Rotary piston Rotary piston Rotary piston
Oil type
Specific
polyvinyl ether
(PVE)
Specific
polyvinyl ether
(PVE)
Specific
polyvinyl ether
(PVE)
Specific
polyvinyl ether
(PVE)
Coolant circuit control
system
Electronic Electronic Electronic Electronic
Technical data Heat pump system performance data
VWL 55/2 A
230 V
VWL 85/2 A
230 V
VWL 115/2 A
230 V
VWL 155/2 A
230 V
Heating output A-7/W35
4.90 kW 6.70 kW 7.90 kW 11.80 kW
A-7/W35 output figure/EN
14511 coefficient of per-
formance
2.40 2.80 2.50 2.60
A7/W35 heating output
4.70 kW 8.10 kW 10.50 kW 14.60 kW
A7/W35 output figure/EN
14511 coefficient of per-
formance
4.70 4.80 4.20 4.50
Power consumption ef-
fective at A7/W35
1.10 kW 1.80 kW 2.50 kW 3.40 kW
Input current at A7/W35
4.80 A 7.80 A 10.90 A 14.80 A
A7/W45 heating output
4.40 kW 7.80 kW 10.20 kW 13.40 kW
A7/W45 output figure/EN
14511 coefficient of per-
formance
3.40 3.80 3.40 3.40
Power consumption ef-
fective at A7/W45
1.30 kW 2.10 kW 3.00 kW 4.10 kW
Input current at A7/W45
5.70 A 9.10 A 13.00 A 17.80 A
A7/W55 heating output
4.20 kW 7.00 kW 9.80 kW 11.20 kW
A7/W55 output figure/EN
14511 coefficient of per-
formance
2.70 3.00 2.90 2.30
Power consumption ef-
fective at A7/W55
1.60 kW 2.40 kW 3.50 kW 5.00 kW
Input current at A7/W55
7.00 A 10.40 A 15.20 A 21.70 A
Appendix
48 Installation instructions aroTHERM 0020147164_04
G Overview of fault codes
Code Meaning Cause
F.022 Water pressure too low Insufficient water in the heating system
F.037 Fan fault Obstruction in the product's air guiding
Fan motor not connected or faulty
The connection between the main PCB and the fan PCB is dam-
aged or broken.
F.042 Fault: Coding resistance The product's coding resistance is missing or is faulty
Coding resistance value outside the permissible range
X25 plug not connected or was connected incorrectly
F.073 Fault: Water pressure sensor Line to water pressure sensor is broken or has a short circuit
F.086 Contact thermostat has opened. Underfloor heating temperature too high
Heating circuit flow rate too low
Underfloor heating circuit is closed
F.103 Fault: Spare part detection The main PCB that is fitted as a spare part or the inverter does
not match the product
The "Max. duration power supply cut-off" parameter has been
set poorly (see the "Heat pump setting parameters" section in
the appendix).
F.514 Sensor fault: Comp. inlet temp.
Sensor is faulty or incorrectly connected to the main PCB
F.517 Sensor fault: Comp. outlet temp.
F.519 Sensor fault: Return temperature
F.520 Sensor fault: Flow temperature
F.523 Sensor fault: VF1 Line to VF1 temperature sensor is broken or has a short circuit.
F.526
Sensor fault: Temp. environment circuit EEV
1)
Sensor is faulty or incorrectly connected to the main PCB
F.532 Building circuit: Flow rate too low Pump faulty
Check the specific flow rate in the heating circuit during the
sensor/actuator test
Between 7000 and 7700 l/h: The power supply is not suffi-
cient
Between 7700 and 8200 l/h: The pump runs dry (no water in
the heating circuit; the heating circuit loses water)
Between 8200 and 8700 l/h: Fault in the electronics
Between 8700 and 9200 l/h: The pump is blocked
Between 9200 and 10,000 l/h: No PWM signal (cable faulty
or not connected; fault in the main PCB)
Pump faulty
Pump cabling faulty
Low water pressure
Dirt filter in the heating circuit return is missing or blocked
Heating circuit not fully purged
Pressure loss in the heating circuit too high
F.536 Compressor outlet temp. too high Coolant quantity too low
Sensor is faulty or incorrectly connected to the main PCB
Premature expansion in the liquid area of the coolant circuit (loss
of charge)
Electronic expansion valve faulty
Heat exchanger blocked
1) Sensor on the evaporator
2) Sensor on the condenser
Appendix
0020147164_04 aroTHERM Installation instructions 49
Code Meaning Cause
F.537 High-pressure switch open Coolant volume too high or too low
Vacuum insufficient (10 mbar)
Incondensable particle in the coolant circuit
Pressure switch or electrical connection faulty
Premature expansion in the liquid area of the coolant circuit (loss
of charge)
Flow quantity too high (see defined maximum flow rate)
Flow rate monitor faulty
Insufficient heat transfer in the heat exchanger
F.539 Coolant pressure too low Coolant quantity too low
Air flow too low
No thawing
The resistance heating in the condensate receiver is faulty.
4-way valve faulty
Electronic expansion valve motor faulty, or connection faulty
F.546 Sensor fault: High pressure Faulty cabling
F.554 Coolant pressure not in operating range Coolant volume too high or too low
Incondensable particle in the coolant circuit
Electronic expansion valve faulty
Premature expansion in the liquid area of the coolant circuit (loss
of charge)
Flow quantity too high (see defined maximum flow rate)
Insufficient heat exchange in the plate heat exchanger or the
ribbed pipe heat exchanger
4-way valve faulty
F.582 EEV fault Cable insulation faulty
Connection broken
F.585
Sensor fault: Temp. building circuit EEV
2)
Sensor is faulty or incorrectly connected to the main PCB
F.685 Communication fault: eBUS The product is not connected to the controller
Polarity inverted
F.750 Connection fault: Compressor Cable insulation faulty
Connection broken
F.751 Compressor: Overcurrent fault The product's voltage supply is too low
The ribbed pipe heat exchanger or heat exchanger is dirty
F.752 Fault: Inverter Inverter box damaged
The cooler inverter box is blocked.
Faulty voltage supply
The "Max. duration power supply cut-off" parameter has been
set poorly (see the "Heat pump setting parameters" section in
the appendix).
F.753 Connection fault: Inverter not recognised The connection between the main PCB and the inverter box is
damaged or broken.
The inverter box is not switched on.
The "Max. duration power supply cut-off" parameter has been
set incorrectly (see the "Heat pump setting parameters" section
in the appendix).
F.754 Fault: Fan unit The connection between the main PCB and the fan PCB is dam-
aged or broken.
The fan PCB is faulty
F.755 Fault: 4-way valve position incorrect Mechanical or electrical problem. Move the 4-way valve away from
the controller. When moving it, check that the coil voltage is correct.
F.774 Sensor fault: Air inlet temperature The temperature sensor is faulty or incorrectly connected to the
main PCB.
F.1288 Fault: SP1 cylinder temperature sensor Sensor is faulty or has not been correctly connected to the VWZ AI
heat pump control module.
Connection fault: Accessory modules Fault in the VWZ AI heat pump control module (the connection
between the display and the main PCB is faulty).
1) Sensor on the evaporator
2) Sensor on the condenser
Appendix
50 Installation instructions aroTHERM 0020147164_04
Code Meaning Cause
Connection fault: Heat pump The eBUS connection between the heat pump and the VWZ AI heat
pump control module is faulty.
1) Sensor on the evaporator
2) Sensor on the condenser
For further technical information, please call 0844 6933 133.
Index
0020147164_04 aroTHERM Installation instructions 51
Index
A
Actuator test ........................................................................ 27
B
Back
Cleaning......................................................................... 26
C
Cable duct ........................................................................... 18
CE label................................................................................. 4
Connection diagram ............................................................ 19
D
Documents ............................................................................ 7
E
Electrical diagram................................................................19
Electricity ...............................................................................3
F
Filling ................................................................................... 23
Front
Cleaning......................................................................... 26
Function menu.....................................................................27
H
Heating water
Preparing ....................................................................... 22
Hot water temperature........................................................... 3
I
Identification plate ................................................................. 9
Installer level ....................................................................... 21
L
Live Monitor
Calling up....................................................................... 21
M
Manual
Applicability...................................................................... 7
P
Product
Unpacking...................................................................... 10
R
Regulations ........................................................................... 4
Risk of scalding .....................................................................3
S
Safety devices..................................................................... 7
Expansion relief valve......................................................3
Expansion vessel.............................................................3
Sensor/actuator test ............................................................ 27
Setting the language ...........................................................21
Side casing
Removing....................................................................... 14
Spare parts..........................................................................25
Statistics
Calling up....................................................................... 21
T
Terminal connection diagram.............................................. 19
Tool ....................................................................................... 4
V
Voltage .................................................................................. 3
0020147164_04 05.05.2014
Vaillant Ltd
Nottingham Road Belper Derbyshire DE56 1JT
Telephone 4484 56 02 29 22 Vaillant Service Solutions 4480706 06 07 77
Spares Technical Enquiries 4417 73 59 66 15
info@vaillant.co.uk technicalspares@groupservice.co.uk
www.vaillant.co.uk
© These instructions, or parts thereof, are protected by copyright and may be reproduced or distributed only with
the manufacturer's written consent.
21


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Vaillant aroTHERM VWL 155-2 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Vaillant aroTHERM VWL 155-2 in the language / languages: English as an attachment in your email.

The manual is 3,09 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Vaillant aroTHERM VWL 155-2

Vaillant aroTHERM VWL 155-2 User Manual - German - 24 pages

Vaillant aroTHERM VWL 155-2 User Manual - Dutch - 20 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info