Instructions for the installer
3.12 - DETERMINATION OF PRIMARY BOILER PUMP OR BOILER SYSTEM PUMP
The size of the pumps must be determined by
installers or technical engineers according to
boiler data and system design.
The water side resistance curve of the boiler
is shown in the following diagram.
The pump is not an integral part of the boiler.
It is recommended to choose a pump with
the rate and delivery head at about 2/3 of its
characteristic heating curve.
The boiler pump must have a delivery head which can ensure the
water flow rate as shown in the diagram “Water pressure losses”.
The following table gives an indication of the pump’s flow rate
in function of the Ät of the primary circuit if the installation has
a mixing header.
NOTE: The use of a mi-
xing header fitted bet-
ween the boiler circuit
and the system circuit is
always advisable.
It becomes INDISPENSABLE if the
system requires flow rates superior
to the maximum permitted boiler
flow rates, which is to say lower
than 15K.
For a T 20 K, of a MODU-
LEX 250 boiler, the max.
water flow rate requested
is 10514 l/h.
From the graph of the
boiler’s pressure losses,
it can be determined that the pump
must be able to guarantee a delive-
ry head of at least 1,6 m/H
2
O
WATER FLOW l/h
Pressure Losses (m/H
2
O)
3.13 - BALLSTOP VALVES
The installation of ballstop gate valves, on the C.H. flow and
return connection, is recommended.
Doing so, in case of normal or extraordinary service, the boiler
can be drained without emptying the whole C.H. sistem.
WARNING!
IT IS NOT ALLOWED TO ISOLATE THE SA-
FETY DEVICES, as the safety valve and the
expansion vessel, FROM THE BOILER.
23


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Unical MODULEX EXT 250 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Unical MODULEX EXT 250 in the language / languages: English as an attachment in your email.

The manual is 8,87 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Unical MODULEX EXT 250

Unical MODULEX EXT 250 Installation Guide - Dutch - 57 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info